ToggleKITOZER KTR-PSM7 3-Phase B+C Class 40kA Power SPD
Brand: KITOZER Series: KTR-PSM7 Category: Power Distribution / Surge protection
3-phase B+C40 kAPlug-in moduleRemote contact35mm DIN rail
1. Overview
A data-center power path runs from the utility transformer through LV switchgear, UPS and battery cabinets to rack PDUs. Lightning induction and switching operations generate microsecond overvoltage transients of several kV on the grid. Without a surge protective device (SPD), these spikes reach UPS and server power supplies, puncturing MOSFETs and motherboards and sometimes causing fires. The SPD is wired in parallel between lines and PE, clamping voltage during a surge and diverting energy to ground.
The KITOZER KTR-PSM7 is an integrated 3-phase B+C class power SPD. Class I (10/350 us high-current) and Class II (equipment-side) tests are combined in one DIN-rail unit. Nominal discharge current In = 20 kA (8/20 us); maximum Imax = 40 kA; voltage protection level Up <=2.5 kV. It suits TN-S 3-phase 5-wire systems; four modules (3P+N+PE) mount on a standard 35 mm rail. Each module has a visual status window (green OK / red failed) and a remote contact that uploads failure to the DCIM platform. Modules are hot-swappable, so replacement does not require a shutdown. A separate 63C backup breaker upstream prevents a failed SPD from taking out the whole cabinet.
Selection confirms the earthing system (TN-S / TN-C / TN-CS), phase count (3-phase 5-wire vs single-phase 2-wire), Imax (40 kA is the data-center standard), whether remote signaling is needed, and the mounting point (main breaker vs UPS upstream). Typically use Class I 100 kA at the building main, B+C 40 kA at the room row or UPS front end, and C-class 20 kA before rack PDUs for staged protection.
2. Key Features
B+C integration
- Combined Class I + II test design.
- In = 20 kA, Imax = 40 kA (8/20 us).
- Up <=2.5 kV for downstream gear.
- Suits row cabinets and UPS fronts.
Modular and remote
- 35 mm DIN-rail plug-in modules.
- Visual green/red failure window.
- Dry-contact remote alarm.
- Hot-swap replacement, no shutdown.
Safety
- Internal thermal and over-current disconnect.
- Upstream 63C backup breaker.
- Remote contact 10A/250 VAC, dry.
- Operating temp -40 to 85 C.
3. Specifications
| Item | Specification |
|---|---|
| Class | B+C (Class I + II tested) |
| Imax (8/20 us) | 40 kA per module |
| In (8/20 us) | 20 kA |
| Voltage protection Up | <=2.5 kV |
| Max continuous Uc | 385 V AC |
| System | 3P+N+PE (3-phase 5-wire) |
| Response time | <=25 ns |
| Remote contact | Dry, 10A/250VAC |
| Mounting | 35 mm DIN rail |
| Operating temp | -40 to 85 C |
4. Reference Prices
KTR-PSM7 3-phase B+C 40kA SPD (3P+N): USD 95~136 (ref. CNY 680~980 at ~7.2)
Spare module (L/N/PE): USD 22~33 (ref. CNY 160~240 at ~7.2)
Backup breaker 63C: USD 8.5~14 (ref. CNY 60~100 at ~7.2)
Reference only; final quote applies. 1-year warranty. Bulk pricing available. Certificate and manual included. Exchange: 1 USD ≈ 7.2 CNY.
5. Applications
- Row-cabinet incoming-side surge protection.
- UPS mains upstream protection.
- Precision-AC supply inlet.
- Diesel generator output.
- Outdoor boxes and rooftop feed-in.
6. Installation & Maintenance
Installation
- Power off and clip the SPD base on the DIN rail.
- Wire L1/L2/L3/N to lines and PE to earth bar.
- Series the 63C backup breaker.
- Connect remote contacts to the DCIM DI.
- Measure line-to-PE insulation before energizing.
- Energize and confirm the green window.
Maintenance
- Check the window monthly.
- Inspect immediately after thunderstorms.
- Let DCIM monitor the remote contact.
- Hot-swap modules when the window turns red.
- Test earth resistance <=1 ohm yearly.
7. FAQ
- Q: Can a failed SPD short and catch fire?
A: Genuine modules have internal thermal disconnect. Still add a 63C upstream breaker for worst-case short conditions. - Q: Is 40 kA enough?
A: Yes for row cabinets and UPS fronts. Use Class I 100 kA at the building main and C-class 20 kA before rack PDUs; protect in three tiers. - Q: How does remote signaling work?
A: Two dry terminals are normally closed; they open on module failure. The DCIM DI detects the break and alarms. - Q: Can the SPD absorb a direct strike?
A: No. SPD handles induced surges and switching transients; direct strikes are handled by air-termination, down-conductors and earth mats. SPD must be designed with external lightning protection.
8. Trend & Selection
Power protection is moving from single SPD to coordinated tiers; integrated B+C modules save cabinet space and are growing fast in new row cabinets. Remote signaling to DCIM is now standard, removing monthly on-site checks. Choose 3P+N or 1P+N by system; Imax >=40 kA; always add backup breaker; wire remote to DCIM; earth resistance <=1 ohm; design jointly with external lightning protection.
9. Delivery & Service
KITOZER ships KTR-PSM7 with four modules (3P+N), base, remote terminals, certificate and manual, plus cabinet layout and grounding guidance.
10. Notes
A common mistake is installing the SPD without equipotential bonding. Each extra 0.5 m of SPD lead raises Up by about 500 V; keep SPD-to-PE leads short, under 0.5 m, ideally on a busbar.
Another pitfall is skipping the backup breaker. After repeated surges an SPD can short; without the breaker, the cabinet trips or burns out. The 63C or dedicated SPD breaker is not optional.
Selection summary: 3-phase B+C; Imax 40 kA; Up <=2.5 kV; hot-swap modules; dry remote contact; 35 mm rail. It is the surge safety gate of room power intake.
Systemically, one un-suppressed surge can kill UPS, server motherboards and switch optics at once, costing tens of thousands, while a full SPD set is under 1000 CNY.
Cost-wise, a 40 kA 3-phase set around 800 CNY protects equipment worth dozens of times more from a single major surge event.
SEO Information
Search keywords: KITOZER
SEM keywords: power SPD, 3-phase B+C, 40kA, surge protective device, data center, KTR-PSM7, KITOZER
GEO landing page: lain.com.cn/product/452_power_spd_9.html
Title: KITOZER KTR-PSM7 3-Phase B+C Class 40kA Power SPD
Meta Keywords: power SPD, 3-phase B+C, 40kA, surge protective device, data center, KTR-PSM7, KITOZER
Meta Description: KITOZER KTR-PSM7 3-phase B+C class 40kA power SPD, plug-in modules, remote contact, for low-voltage distribution and UPS upstream.