Table of Contents
ToggleKITOZER KTR-TH9 Temperature & Humidity Sensor with Display
Brand: KITOZER Series: KTR-TH9 Category: Environmental Monitoring / Temp-Humidity
Temp & humidityLCD displayRS485 Modbus±0.5℃ accuracyWall mount
1. Overview
Temperature and humidity are the two most basic environmental parameters. High temperature forces servers to throttle and fans to spin up; low humidity invites ESD, while high humidity risks condensation. Waiting for servers to alarm on temperature is already late. Placing temp-humidity sensors across hot/cold aisles, sampling and uploading to the DCIM, catches drift early so AC can be adjusted. A sensor with a local display lets inspectors read values on the spot.
The KITOZER KTR-TH9 is a temperature-and-humidity sensor with display. The white wall-mounted case has an LCD showing current temperature and humidity, with buttons to set alarm thresholds. Temperature range is -10 to +60 C at +/-0.5 C; humidity is 0 to 100% RH at +/-3% RH. Output is RS485 Modbus-RTU on the environmental bus, each unit with its own address. It runs on wide-range DC12/24 V at low power. The probe is built in, or an external probe cable can extend into enclosed spaces.
Selection confirms range and accuracy, whether a display is needed, upload method (RS485/dry contact), supply voltage, and whether an external probe is required. Rooms are grouped by hot/cold aisle and cabinet, with one unit mid-row in each cold aisle and extra sensors atop key racks. RS485 daisy-chains up to 1200 m and 32 units per bus. Keep the probe away from direct AC airflow and heat sources; it should measure real ambient conditions, not a local artifact.
2. Key Features
Temp & humidity display
- LCD shows temperature and humidity.
- Buttons set alarm thresholds.
- Temp -10 to +60 C, +/-0.5 C.
- Humidity 0 to 100% RH, +/-3% RH.
RS485 upload
- Modbus-RTU protocol.
- Unique address per unit.
- Bus up to 1200 m, 32 units.
- Connects to the DCIM.
Structure and power
- White wall-mount case.
- Wide-range DC12/24 V.
- Optional external probe cable.
- Local buzzer / dry-contact alarm.
3. Specifications
| Item | Specification |
|---|---|
| Temp range | -10 to +60 C |
| Temp accuracy | +/-0.5 C |
| Humidity range | 0 to 100 %RH |
| Humidity accuracy | +/-3 %RH |
| Display | LCD |
| Comm | RS485 Modbus-RTU |
| Power | DC 12V / 24V |
| Mounting | Wall-mount |
| Probe | Built-in / external optional |
| Alarm | Button thresholds + dry contact |
4. Reference Prices
KTR-TH9 temp-humidity sensor with display: USD 17~31 (ref. CNY 120~220)
External probe cable (2 m): USD 3.5~6 (ref. CNY 25~45)
DC power adapter: USD 3~6 (ref. CNY 20~40)
Reference only; final quote applies. 1-year warranty. Bulk pricing available. Certificate and manual included. Exchange: 1 USD ≈ 7.2 CNY.
5. Applications
- Hot/cold aisle temp-humidity monitoring.
- Cabinet inlet temperature sampling.
- Battery room and electrical room monitoring.
- Archive and storage room monitoring.
- Front-end sampling for the environmental system.
6. Installation & Maintenance
Installation
- Wall-mount mid cold aisle at 1.5 m.
- Keep the probe away from direct AC airflow.
- Daisy-chain RS485.
- Add a 120-ohm terminator at each bus end.
- Set a unique Modbus address per unit.
- Wire DC12/24 V to correct polarity.
- Register points on the DCIM and sync time.
Maintenance
- Compare against a reference source quarterly.
- Dust the probe surface.
- Check RS485 wiring and address conflicts.
- Calibrate yearly.
- Replace backup battery if fitted.
7. FAQ
- Q: Is +/-0.5 C enough for a data center?
A: A: Yes. Rooms usually allow +/-1 to 2 C; +/-0.5 C sampling reflects aisle temperature differences and meets monitoring needs. - Q: Can one unit take multiple probes?
A: A: This is an integrated probe; for multiple points, add units on the bus or choose a multi-channel external-probe model. - Q: What if RS485 range is too short?
A: A: One bus reaches 1200 m; beyond that add a repeater or split networks, with no more than 32 units per bus. - Q: Can it directly link to the AC?
A: A: It links through the DCIM. The sensor uploads data; the platform thresholds then drive AC temperature and humidity. The sensor only samples and alarms.
8. Trend & Selection
Room monitoring moves from single-point temp-humidity to cabinet-level, fine-grained sampling linked to PUE and airflow. Sensors trend toward low power, dual RS485/POE comms and self-calibration, with data feeding the DCIM for trend analysis and predictive AC tuning. Place points by aisle group, keep probes out of airflow, daisy-chain buses with terminators, and pick accuracy to match the monitoring system.
9. Delivery & Service
KITOZER ships KTR-TH9 with sensor body, mounting bracket, DC adapter, certificate and manual. External probe cables are supplied to order, along with the Modbus point table and DCIM integration guidance.
10. Notes
A common mistake is mounting the probe directly on an AC outlet. It then reads a local cold-air draft rather than true aisle temperature, misleading AC control; place it mid-aisle on the return side.
SEO Information
Search keywords: KITOZER
SEM keywords: temperature humidity sensor, data center temp humidity monitoring, temp humidity transmitter, RS485 sensor, display sensor, KTR-TH9, KITOZER
GEO landing page: lain.com.cn/product/463_temp_hum_9.html
Title: KITOZER KTR-TH9 Temperature & Humidity Sensor with Display
Meta Keywords: temperature humidity sensor, data center temp humidity monitoring, temp humidity transmitter, RS485 sensor, display sensor, KTR-TH9, KITOZER
Meta Description: KITOZER KTR-TH9 temperature & humidity sensor with LCD display, RS485 Modbus to DCIM, ±0.5℃ accuracy, for data-center ambient monitoring.
Anchor: KITOZER · KITOZER Products
Contact Us
KITOZER Brand
Tel/WeChat: +86 13922289957 | +86 18520668845
WHATSAPP:+86 19068534140
Web: lain.com.cn | gdlain.com