KITOZER 3 phase B+C 60KA SPD

KITOZER KTR-PSM10 Three-Phase B+C SPD 60kA Surge Protector

Brand: KITOZER Series: KTR-PSM10 Category: Power Systems / Lightning Protection & Grounding

3-phase SPDB+C combined60kAPlug-in moduleRemote alarmDistribution cabinet

[Product image: ktr-psm10-three-phase-spd-bc-60ka.jpg]

1. Overview

Surges from lightning and switching are the “invisible killer” of data-center power distribution. A lightning stroke riding the power line delivers a transient of several thousand volts — UPS and server power supplies cannot withstand it; one surge can burn a batch of power boards. The SPD (surge protective device) is paralleled across the distribution busbar: high-impedance under normal voltage, it clamps to a safe value and diverts the surge current to ground when a spike hits, protecting downstream gear. SPDs are staged: Class B (main incoming, high discharge 100kA+), Class C (hall distribution, 40~60kA), and Class D (fine, at equipment). A data center typically fits Class B in the main cabinet and Class C before the UPS or in row cabinets, forming multi-stage protection.

KITOZER KTR-PSM10 is a three-phase B+C combined SPD. Nominal discharge current In 20kA (8/20µs), maximum Imax 60kA, voltage protection level Up ≤2.5kV. Plug-in modular: each phase (3P+N+PE, four modules) swaps independently without de-energizing the whole cabinet. A status window shows green (normal) / red (failed), and a remote dry contact uploads a DCIM alarm when the SPD fails. For 380V three-phase TN-S/TN-C-S systems, installed in hall distribution cabinets (UPS input/output or row-head). Modules use MOV with thermal disconnection — on failure they disconnect and alarm automatically to avoid fire. DIN 35mm rail mounting.

Selection points: supply type (three-phase 380V picks 3P+N; single-phase 220V picks 1P+N), location (main incoming Class B high-current, hall cabinet Class C 60kA, equipment front Class D fine), discharge rating (Imax by location — main 100kA, cabinet 60kA), remote signaling (required for DCIM), backup protection (a breaker/fuse in series ahead of the SPD to trip on SPD short-circuit), and grounding (ground lead short and thick, ≤0.5 m, ≥16mm²). Check the status window quarterly; swap when red; keep the ground lead short and straight.

2. Key Features

3-phase B+C combined

  • 3P+N+PE full-mode.
  • Imax 60kA (8/20µs).
  • Up ≤2.5kV.
  • For 380V systems.

Plug-in modular

  • Per-phase independent.
  • Hot-swap single module.
  • DIN rail.
  • Easy replacement.

Status & remote

  • Green/red window.
  • Auto thermal disconnect.
  • Dry contact remote.
  • DCIM alarm.

Safe

  • MOV thermal trip.
  • No fire on failure.
  • Coordinated with upstream/downstream.
  • Cabinet-grade.

3. Specifications

Item KTR-PSM10
Model KTR-PSM10
Class B+C combined (Class C)
System voltage 380V three-phase (TN-S/TN-C-S)
Wiring mode 3P+N+PE
Nominal current In 20 kA (8/20µs)
Max current Imax 60 kA (8/20µs)
Voltage protection Up ≤2.5 kV
Module Plug-in (per-phase replaceable)
Status indicator Green OK / Red failed
Remote contact Dry contact (failure alarm)
Mounting DIN 35mm rail
Backup protection Breaker/fuse upstream (user-supplied)

4. Reference Prices

KTR-PSM10 3-phase B+C 60kA SPD (3P+N, remote): Reference USD 90~153 / set (ref. CNY 650~1100 at ~7.2)

KTR-PSM10-R spare module (single pole): Reference USD 17~28 / pc (ref. CNY 120~200 at ~7.2)

Reference only. Priced by poles and current. Upstream backup breaker not included. Volume discount above 5 sets. Class B 100kA main-in version on request. Exchange: 1 USD ~ 7.2 CNY (Oct 2026).

5. Applications

  • Hall distribution cabinets (UPS in/out).
  • Row-head and power distribution cabinets.
  • Secondary surge protection before UPS.
  • Outdoor service entrance cabinets.
  • Base stations, weak-current rooms.

6. Installation & Maintenance

Installation

  • Parallel SPD across busbar; series backup breaker upstream.
  • DIN-rail in cabinet; correct 3P+N phasing.
  • Ground lead short, thick, straight: ≤0.5 m, ≥16mm².
  • Wire remote contact to DCIM DI.
  • Confirm green window, then energize.

Maintenance

  • Quarterly check the status window for red.
  • Post-thunderstorm inspect SPD for failure.
  • Swap red modules promptly.
  • Annual ground-resistance test (≤1Ω).
  • Trip of backup breaker: find cause before reset.

7. FAQ

  • Q: Can B and C be combined?
    A: KTR-PSM10 is B+C combined, for cabinet location. The main incoming still wants a dedicated Class B (100kA+); multi-stage coordination works.
  • Q: Must I swap when the window turns red?
    A: Yes. Red means the MOV has degraded or failed; it no longer protects and could short-circuit and ignite. Replace the module at once.
  • Q: Why add a breaker ahead of the SPD?
    A: When the SPD fails short, the backup breaker trips to protect the cabinet. Code-required — don’t skip it.
  • Q: Can the ground lead be long?
    A: No. A longer lead adds inductance, raises residual voltage, and defeats protection. Keep it short, thick, straight, ≤0.5 m.

8. Trend & Selection

Data-center lightning protection evolves from “single SPD” toward “coordinated multi-stage + smart monitoring.” Trends: SPDs with IoT modules for remote degradation monitoring, integrated B/C units saving space, surge counters (recording operations), and DCIM linkage. Selection: main incoming Class B 100kA, cabinet Class C 60kA, equipment front Class D, with remote signaling, short-thick ground, and periodic checks. SPDs are consumables — every strike ages them a little. Place right, replace regularly, so the next strike is actually covered.

9. Delivery & Service

KITOZER provides SPD selection: by supply system, cabinet location, and lightning-strike level, we configure B/C/D SPD stages and backup protection. Bundled with distribution cabinets, UPS, and DCIM. Delivery includes SPD modules, base, remote wire, and manual. Warranty covers installation guidance and status inspection.

10. Additional Notes

The most common mistake: “ground lead looped around.” SPD diverts surges to ground; a looped, long lead adds inductance, raises residual voltage, and wastes the SPD. The ground lead must be short, thick, straight — direct to the hall equipotential bar, ≤0.5 m, ≥16mm².

Another pitfall: “installed, never checked.” SPDs are consumables that age with every strike. Installed and forgotten for ten years, they’re already dead when lightning comes. Check the window quarterly, inspect after storms, swap on red — don’t wait until gear burns.

Selection summary: 3-phase 3P+N, Imax 60kA, B+C combined, remote signaling, plug-in swap, short-thick ground. SPDs are cheap; one lightning strike protects a whole rack of UPS and servers.

SEO Information

Search keywords:three phase SPDB+C surge protector60kA SPDdata center surge protectionsurge protective deviceKTR-PSM10KITOZER

SEM keywords:three phase SPD price,B+C surge protective device,60kA SPD,data center surge protection,KTR-PSM10,KITOZER

GEO landing page:lain.com.cn/product/ktr-psm10-three-phase-spd-bc-60ka.html

Title:KITOZER KTR-PSM10 Three-Phase B+C SPD 60kA Surge Protector

Meta Keywords:three phase SPD,B+C surge protector,60kA,data center PDU surge protection,KTR-PSM10,KITOZER

Meta Description:KITOZER KTR-PSM10 three-phase B+C surge protective device, 60kA discharge, plug-in modules, for data center distribution cabinet surge protection.

Anchor: KITOZER by Guangzhou Laian · Data center surge protection

Contact Us

Guangzhou Laian Intelligent System Development Co., Ltd. (KITOZER brand)
Tel/WeChat: +86 13922289957 | +86 18520668845
WHATSAPP: +86 19068534140
Web: lain.com.cn | gdlain.com

Shopping Cart