KITOZER rack 24 port SC full ODF

KITOZER KTR-SC24R 24-Port SC Rack-Mount Fiber Patch Panel

Brand: KITOZER Series: KTR-SC24R Category: Low-Voltage Cabling / Structured Cabling

1U rack24-port SCLoadedSplice trayCable terminationODF

[Product image: ktr-sc24r-rack-mount-24port-sc-fiber-patch-panel.jpg]

1. Overview

The fiber patch panel (ODF) is the rack’s “termination hub.” Backbone cable pulled in from outside or upper floors can’t plug straight into a switch — bare fiber is brittle, so it must be spliced to a pigtail, then converted through panel adapters to standard ports and patched to the switch. The patch panel does exactly this: the front panel holds adapters (facing the rack front, for patch cords), the rear takes the cable and splices pigtails (hidden in the splice tray). A 24-port SC panel is the classic spec — 1U, 24 SC simplex ports, terminating a 24-fiber cable. “Fully loaded” means all 24 adapters and the splice tray are installed — ready to splice and go, no extra parts to buy.

KITOZER KTR-SC24R is a 1U rack-mount 24-port SC patch panel, powder-coated cold-rolled steel for standard 19″ racks. The front holds 24 SC simplex adapters (color-coded by multimode/singlemode); the rear has two splice trays with hot-spring protector clips and pigtail storage. The cable enters from the rear, anchored by a gland, outer jacket stripped, and 24 fibers spliced to SC pigtails. Pigtails are coiled in the tray and the SC heads plug into the rear of the front adapters. Front patching uses SC-SC or SC-LC cords to switches. Cable-management rings route cords to the vertical manager. The front panel pulls forward for easy splicing.

Selection points: port count (12/24/48 — match fiber count; a 24-fiber cable uses a 24-port panel), connector type (SC square vs LC small; LC dominates now but SC is still widely used), simplex vs duplex (24 SC simplex = 24 fibers; 24 LC duplex = 48 fibers), singlemode vs multimode (color-coded), loaded vs empty (loaded is turnkey; empty needs adapters, pigtails, tray bought separately), and U height (1U/2U; 48 ports usually 2U). Note: coil pigtails with bend radius ≥30 mm (tighter adds loss); anchor the cable with a gland for strain relief; match adapter and patch-cord types.

2. Key Features

24-port SC loaded

  • 1U 19″.
  • 24 SC adapters fitted.
  • Splice tray + pigtails.
  • Ready to use.

Pull-out structure

  • Front panel pulls forward.
  • Easy splicing.
  • Powder-coated steel.
  • Rigid, no warp.

Dual splice trays

  • 2-tier tray.
  • Protector-clip slots.
  • Pigtail coiling space.
  • Rear cable gland.

Tidy routing

  • Cable-management rings.
  • Cords to vertical manager.
  • Label slots.
  • SM/MM options.

3. Specifications

Item KTR-SC24R
Model KTR-SC24R
Form factor 1U rack-mount (19″)
Ports 24 × SC simplex
Adapters 24 SC (loaded, MM/SM color option)
Splice tray 2 tiers (pigtail storage)
Termination capacity 24-fiber cable
Material Powder-coated cold-rolled steel
Mounting 19″ rack square holes
Pull-out Front panel slides forward
Cable entry Rear gland, strain relief
Fiber compatibility OS2 singlemode / OM3/OM4 multimode
Management Rings + label slots

4. Reference Prices

KTR-SC24R 24-port SC loaded panel (adapters + tray): Reference USD 39~67 / unit (ref. CNY 280~480 at ~7.2)

KTR-SC24R-SM singlemode (blue adapters, SC SM pigtails): Reference USD 49~78 / unit (ref. CNY 350~560 at ~7.2)

Reference only. Priced by SM/MM. Cable and patch cords not included. Volume discount above 5 units. 48-port 2U and LC-duplex versions on request. Exchange: 1 USD ~ 7.2 CNY (Oct 2026).

5. Applications

  • Rack backbone cable termination.
  • Switch ToR optical patching.
  • Telecom/riser room fiber consolidation.
  • Data-center row-head ODF.
  • Building/floor fiber termination.

6. Installation & Maintenance

Installation

  • Fix panel in a 1U rack slot with M6 cage nuts.
  • Thread cable through rear gland; anchor strain.
  • Strip jacket; splice 24 fibers to SC pigtails.
  • Heat-shrink protectors on splices; clip into tray.
  • Coil pigtails (radius ≥30mm); plug SC into rear of adapters.

Maintenance

  • Cap unused ports.
  • Clean patch end faces regularly.
  • Update labels against drawings.
  • Pull panel forward to check splices.
  • Keep rings tidy; don’t kink pigtails.

7. FAQ

  • Q: How many fibers in 24 SC vs 24 LC duplex?
    A: 24 SC simplex = 24 fibers; 24 LC duplex = 48 fibers. Choose by cable count and future growth.
  • Q: Loaded vs empty?
    A: Loaded includes adapters and tray — turnkey. Empty is cheaper but you buy adapters, pigtails, tray separately. For fast-track jobs, pick loaded.
  • Q: High loss after splicing?
    A: Usually a bad splice or too-tight pigtail coil. Re-splice, coil pigtails loosely (radius ≥30mm), re-test.
  • Q: Does the rear cable strain relief hold?
    A: The cable must be supported by the gland and tray — the panel only terminates, it shouldn’t carry cable weight. Leave a service loop before the panel.

8. Trend & Selection

Fiber patch panels evolve from “fixed SC” toward “high-density LC + pre-terminated.” Trends: density rising from 24 to 96 fibers per 1U (MTP/MPO pre-connected modules), modular adapters (field-terminable, no splice), panels with electronic labels and LED port mapping, and smart-DCIM integration. Selection: size ports to fiber count, new runs pick LC duplex, loaded for convenience, leave coil radius in the tray, label clearly. The panel is where the cable lands — clean termination makes later patching painless.

9. Delivery & Service

KITOZER provides patch-panel selection: by fiber count, connector (SC/LC), and SM/MM, we configure 24/48-port panels and loaded adapters. Bundled with cable, patch cords, MTP modules, and racks. Delivery includes panel, adapters, splice tray, pigtails (loaded version), and manual. Warranty covers splicing guidance.

10. Additional Notes

The most common mistake: “pigtails coiled too tight.” A cramped splice tray forces 24 pigtails into tight bends under 10 mm radius — light leaks at the bend and loss climbs. Coil pigtails loosely in big loops, radius ≥30 mm, with spare length.

Another pitfall: “no labels.” After 24 fibers are terminated, which port is which cable, which switch — all depends on labels. Without them, every new cord means re-tracing. Label as you splice, clearly per the drawing.

Selection summary: 1U, 24-port SC loaded, dual splice tray, pull-out, management rings. Panels are cheap, but termination quality decides whether the whole fiber link is stable — splice well, coil loose, label clear.

SEO Information

Search keywords:fiber patch panel24 port SC ODFrack mount patch panelloaded fiber panelfiber terminationKTR-SC24RKITOZER

SEM keywords:24 port SC patch panel price,rack mount ODF,loaded fiber patch panel,fiber termination panel,KTR-SC24R,KITOZER

GEO landing page:lain.com.cn/product/ktr-sc24r-rack-mount-24port-sc-patch-panel.html

Title:KITOZER KTR-SC24R 24-Port SC Rack-Mount Fiber Patch Panel

Meta Keywords:fiber patch panel,24 port SC,rack mount ODF,loaded adapter,data center cabling,KTR-SC24R,KITOZER

Meta Description:KITOZER KTR-SC24R 1U rack-mount 24-port SC fiber patch panel, fully loaded adapters and splice tray, for rack cable termination and patching.

Anchor: KITOZER by Guangzhou Laian · Fiber patch panels

Contact Us

Guangzhou Laian Intelligent System Development Co., Ltd. (KITOZER brand)
Tel/WeChat: +86 13922289957 | +86 18520668845
WHATSAPP: +86 19068534140
Web: lain.com.cn | gdlain.com

Shopping Cart