ToggleKITOZER KTR-SD2 Aspirating Smoke Detector Early Warning
Brand: KITOZER Series: KTR-SD2 Category: Environmental Monitoring / Fire Alarm
AspiratingEarly warning2-stageAir samplingRS485In-rack
1. Overview
Fire is the data center’s worst fear — live servers, dense racks, cable-filled ceilings mean it spreads fast. Traditional point smoke detectors (the ones hanging from the ceiling) only alarm once smoke reaches the ceiling — by then the fire has been burning for a while, too late for a hall. An aspirating smoke detector (air-sampling, e.g. VESDA-style) reverses this: a sampling pipe runs across the ceiling with holes drilled in it, and a pump in the detector continuously draws air in, measuring particle concentration with laser scattering. It detects a fire while it is still smoldering and just beginning to smoke — dozens of minutes before a point detector. That is “very early warning,” giving ops time to power down, investigate, and suppress before flames erupt.
KITOZER KTR-SD2 is an aspirating smoke detector with a built-in pump and laser-scatter chamber. Sampling pipe runs from the unit to the hall ceiling or inside racks, drawing air through sampling holes in the pipe. Two alarm stages: pre-alarm (low concentration, notify ops to investigate) and fire alarm (high concentration, link suppression). Sensitivity adjustable, up to 0.005%/m — about 100× more sensitive than point detectors. Four relay outputs (pre-alarm/fire/fault/auxiliary) and RS485 Modbus to DCIM. LCD shows real-time concentration and flow; a filter protects the laser chamber. One detector supports up to 200 m of sampling pipe (up to 4 runs), suiting small-to-mid halls or a single rack row.
Selection points: sampling-pipe length (max 200 m per unit; large halls use multiple units in zones), hole placement (in-rack pipe above the rack or in the cold aisle), sensitivity grade (high-value halls pick high-sensitivity), alarm stages (two-stage pre+fire suffices), linkage (fire panel vs DCIM), and dust filtration (replace filters in dusty halls). Note: keep sampling holes clear of dust and insulation; use flame-retardant PVC pipe; mount the detector in a clean, serviceable spot; mind RS485 polarity.
2. Key Features
Early detection
- Laser-scatter particles.
- Alerts at smolder stage.
- Dozens of minutes earlier.
- 0.005%/m sensitivity.
Two-stage alarm
- Pre-alarm + fire alarm.
- 4 relay outputs.
- Links sounder/suppression.
- Self-diagnostic fault.
Air sampling
- Built-in pump.
- Up to 200 m pipe.
- Up to 4 runs.
- Samples inside racks.
Smart network
- RS485 Modbus.
- LCD concentration display.
- Replaceable filter.
- DCIM integration.
3. Specifications
| Item | KTR-SD2 |
|---|---|
| Model | KTR-SD2 |
| Detection | Aspirating (laser scatter + pump) |
| Sensitivity | 0.005%/m (adjustable, high-sensitivity grade) |
| Alarm stages | Two (pre-alarm/fire) + fault |
| Sampling pipe | Up to 200 m (4 runs) |
| Relay outputs | 4 (pre/fire/fault/aux) |
| Communication | RS485 Modbus RTU |
| Display | LCD concentration + status |
| Filter | Replaceable inlet filter |
| Power | DC24V / AC220V selectable |
| Operating temp. | -10~+50℃ |
| Mounting | Wall/rack; pipe on ceiling |
4. Reference Prices
KTR-SD2 aspirating detector (unit only, no pipe): Reference USD 486~833 / unit (ref. CNY 3500~6000 at ~7.2)
KTR-SD2-KIT set (unit + 50 m pipe + hole fittings): Reference USD 625~1042 / set (ref. CNY 4500~7500 at ~7.2)
Reference only. Priced by pipe length and runs. Fire panel and gas suppression not included. Volume discount above 2 units. VESDA-grade ultra-sensitive version on request. Exchange: 1 USD ~ 7.2 CNY (Oct 2026).
5. Applications
- Data-center early fire warning.
- In-rack server monitoring.
- UPS/battery room overheat warning.
- Libraries, archives, museums.
- Clean rooms, precision equipment rooms.
6. Installation & Maintenance
Installation
- Mount detector near hall entrance (serviceable).
- Run flame-retardant PVC pipe on ceiling; drill holes every 0.5~1 m.
- Route above racks; aim holes at cold aisle.
- Connect pipe to detector inlet; seal joints.
- Power on self-test; set RS485 address; wire DCIM.
Maintenance
- Quarterly blow out sampling pipe (dust clogs holes).
- Replace inlet filter every 6 months.
- Annual test with standard smoke pencil.
- Check pump flow.
- Ensure holes not blocked by insulation/dust.
7. FAQ
- Q: Is aspirating worth the premium over point detectors?
A: In a hall, yes. Point detectors wait for smoke at the ceiling; aspirating alarms at smolder, leaving time to power down. A fire costs millions; the detector costs a few thousand. - Q: Lots of false alarms?
A: Not in clean halls. In dusty halls, replace filters and blow the pipe; don’t set sensitivity to max; staged alarms cut false calls. - Q: How much area per unit?
A: Up to 200 m of pipe covers about 200~400 m². Large halls zone multiple units, one per fire zone. - Q: Can it join the existing fire panel?
A: Yes. Fire-alarm relay to the fire panel input module; RS485 to DCIM for both paths.
8. Trend & Selection
Fire detection evolves from “point detectors” toward “aspirating early warning + multi-sensor fusion.” Trends: finer sensitivity grading, sampling pipe with combined temp/humidity, linkage with rack BMS and DCIM (pre-alarm sheds load, powers down), IoT remote filter-life monitoring, and AI to tell real fire from dust. Selection: high-value halls must use aspirating; pipe along racks; two-stage alarm; dual-wire to fire panel and DCIM; blow the pipe and replace filters regularly. The aspirating detector is the hall’s “fire stethoscope” — hearing the abnormal heartbeat before the fire starts.
9. Delivery & Service
KITOZER provides aspirating detection selection: by hall area, rack count, and asset value, we configure unit count, sampling-pipe routing, and sensitivity grade. Bundled with fire panel, DCIM, and gas suppression. Delivery includes detector, sampling pipe, hole fittings, and manual. Warranty includes pipe-routing design and alarm commissioning.
10. Additional Notes
The most common fault: “sampling holes clogged.” Halls are dusty; holes block after six months without blowing, so the pump draws but doesn’t sample real air — the detector thinks the air is clean and won’t alarm even on smoke. Blow the pipe quarterly with compressed air and verify holes are open.
Another pitfall: “sensitivity maxed out.” At max sensitivity, walking in or dusting triggers alarms; ops eventually disable it. Set staged sensitivity: medium pre-alarm, high fire alarm — neither misses nor over-alarms.
Selection summary: aspirating, laser detection, two-stage alarm, pipe along racks, RS485 to DCIM, regular blow/filter. Earlier fire detection means smaller loss — aspirating buys those dozens of minutes of lead time.
SEO Information
Search keywords:aspirating smoke detectorearly fire warningair sampling detectordata center smoke detectionVESDA detectorKTR-SD2KITOZER
SEM keywords:aspirating smoke detector price,early fire warning,air sampling detector,data center smoke detection,KTR-SD2,KITOZER
GEO landing page:lain.com.cn/product/ktr-sd2-aspirating-smoke-detector.html
Title:KITOZER KTR-SD2 Aspirating Smoke Detector Early Warning
Meta Keywords:aspirating smoke detector,very early warning,VESDA,data center smoke monitoring,air sampling,KTR-SD2,KITOZER
Meta Description:KITOZER KTR-SD2 aspirating smoke detector, air-sampling early warning, two-stage sensitivity, for data center and rack early fire detection.