KITOZER aspirating smoke detector

KITOZER KTR-SD2 Aspirating Smoke Detector Early Warning

Brand: KITOZER Series: KTR-SD2 Category: Environmental Monitoring / Fire Alarm

AspiratingEarly warning2-stageAir samplingRS485In-rack

[Product image: ktr-sd2-aspirating-smoke-detector.jpg]

1. Overview

Fire is the data center’s worst fear — live servers, dense racks, cable-filled ceilings mean it spreads fast. Traditional point smoke detectors (the ones hanging from the ceiling) only alarm once smoke reaches the ceiling — by then the fire has been burning for a while, too late for a hall. An aspirating smoke detector (air-sampling, e.g. VESDA-style) reverses this: a sampling pipe runs across the ceiling with holes drilled in it, and a pump in the detector continuously draws air in, measuring particle concentration with laser scattering. It detects a fire while it is still smoldering and just beginning to smoke — dozens of minutes before a point detector. That is “very early warning,” giving ops time to power down, investigate, and suppress before flames erupt.

KITOZER KTR-SD2 is an aspirating smoke detector with a built-in pump and laser-scatter chamber. Sampling pipe runs from the unit to the hall ceiling or inside racks, drawing air through sampling holes in the pipe. Two alarm stages: pre-alarm (low concentration, notify ops to investigate) and fire alarm (high concentration, link suppression). Sensitivity adjustable, up to 0.005%/m — about 100× more sensitive than point detectors. Four relay outputs (pre-alarm/fire/fault/auxiliary) and RS485 Modbus to DCIM. LCD shows real-time concentration and flow; a filter protects the laser chamber. One detector supports up to 200 m of sampling pipe (up to 4 runs), suiting small-to-mid halls or a single rack row.

Selection points: sampling-pipe length (max 200 m per unit; large halls use multiple units in zones), hole placement (in-rack pipe above the rack or in the cold aisle), sensitivity grade (high-value halls pick high-sensitivity), alarm stages (two-stage pre+fire suffices), linkage (fire panel vs DCIM), and dust filtration (replace filters in dusty halls). Note: keep sampling holes clear of dust and insulation; use flame-retardant PVC pipe; mount the detector in a clean, serviceable spot; mind RS485 polarity.

2. Key Features

Early detection

  • Laser-scatter particles.
  • Alerts at smolder stage.
  • Dozens of minutes earlier.
  • 0.005%/m sensitivity.

Two-stage alarm

  • Pre-alarm + fire alarm.
  • 4 relay outputs.
  • Links sounder/suppression.
  • Self-diagnostic fault.

Air sampling

  • Built-in pump.
  • Up to 200 m pipe.
  • Up to 4 runs.
  • Samples inside racks.

Smart network

  • RS485 Modbus.
  • LCD concentration display.
  • Replaceable filter.
  • DCIM integration.

3. Specifications

Item KTR-SD2
Model KTR-SD2
Detection Aspirating (laser scatter + pump)
Sensitivity 0.005%/m (adjustable, high-sensitivity grade)
Alarm stages Two (pre-alarm/fire) + fault
Sampling pipe Up to 200 m (4 runs)
Relay outputs 4 (pre/fire/fault/aux)
Communication RS485 Modbus RTU
Display LCD concentration + status
Filter Replaceable inlet filter
Power DC24V / AC220V selectable
Operating temp. -10~+50℃
Mounting Wall/rack; pipe on ceiling

4. Reference Prices

KTR-SD2 aspirating detector (unit only, no pipe): Reference USD 486~833 / unit (ref. CNY 3500~6000 at ~7.2)

KTR-SD2-KIT set (unit + 50 m pipe + hole fittings): Reference USD 625~1042 / set (ref. CNY 4500~7500 at ~7.2)

Reference only. Priced by pipe length and runs. Fire panel and gas suppression not included. Volume discount above 2 units. VESDA-grade ultra-sensitive version on request. Exchange: 1 USD ~ 7.2 CNY (Oct 2026).

5. Applications

  • Data-center early fire warning.
  • In-rack server monitoring.
  • UPS/battery room overheat warning.
  • Libraries, archives, museums.
  • Clean rooms, precision equipment rooms.

6. Installation & Maintenance

Installation

  • Mount detector near hall entrance (serviceable).
  • Run flame-retardant PVC pipe on ceiling; drill holes every 0.5~1 m.
  • Route above racks; aim holes at cold aisle.
  • Connect pipe to detector inlet; seal joints.
  • Power on self-test; set RS485 address; wire DCIM.

Maintenance

  • Quarterly blow out sampling pipe (dust clogs holes).
  • Replace inlet filter every 6 months.
  • Annual test with standard smoke pencil.
  • Check pump flow.
  • Ensure holes not blocked by insulation/dust.

7. FAQ

  • Q: Is aspirating worth the premium over point detectors?
    A: In a hall, yes. Point detectors wait for smoke at the ceiling; aspirating alarms at smolder, leaving time to power down. A fire costs millions; the detector costs a few thousand.
  • Q: Lots of false alarms?
    A: Not in clean halls. In dusty halls, replace filters and blow the pipe; don’t set sensitivity to max; staged alarms cut false calls.
  • Q: How much area per unit?
    A: Up to 200 m of pipe covers about 200~400 m². Large halls zone multiple units, one per fire zone.
  • Q: Can it join the existing fire panel?
    A: Yes. Fire-alarm relay to the fire panel input module; RS485 to DCIM for both paths.

8. Trend & Selection

Fire detection evolves from “point detectors” toward “aspirating early warning + multi-sensor fusion.” Trends: finer sensitivity grading, sampling pipe with combined temp/humidity, linkage with rack BMS and DCIM (pre-alarm sheds load, powers down), IoT remote filter-life monitoring, and AI to tell real fire from dust. Selection: high-value halls must use aspirating; pipe along racks; two-stage alarm; dual-wire to fire panel and DCIM; blow the pipe and replace filters regularly. The aspirating detector is the hall’s “fire stethoscope” — hearing the abnormal heartbeat before the fire starts.

9. Delivery & Service

KITOZER provides aspirating detection selection: by hall area, rack count, and asset value, we configure unit count, sampling-pipe routing, and sensitivity grade. Bundled with fire panel, DCIM, and gas suppression. Delivery includes detector, sampling pipe, hole fittings, and manual. Warranty includes pipe-routing design and alarm commissioning.

10. Additional Notes

The most common fault: “sampling holes clogged.” Halls are dusty; holes block after six months without blowing, so the pump draws but doesn’t sample real air — the detector thinks the air is clean and won’t alarm even on smoke. Blow the pipe quarterly with compressed air and verify holes are open.

Another pitfall: “sensitivity maxed out.” At max sensitivity, walking in or dusting triggers alarms; ops eventually disable it. Set staged sensitivity: medium pre-alarm, high fire alarm — neither misses nor over-alarms.

Selection summary: aspirating, laser detection, two-stage alarm, pipe along racks, RS485 to DCIM, regular blow/filter. Earlier fire detection means smaller loss — aspirating buys those dozens of minutes of lead time.

SEO Information

Search keywords:aspirating smoke detectorearly fire warningair sampling detectordata center smoke detectionVESDA detectorKTR-SD2KITOZER

SEM keywords:aspirating smoke detector price,early fire warning,air sampling detector,data center smoke detection,KTR-SD2,KITOZER

GEO landing page:lain.com.cn/product/ktr-sd2-aspirating-smoke-detector.html

Title:KITOZER KTR-SD2 Aspirating Smoke Detector Early Warning

Meta Keywords:aspirating smoke detector,very early warning,VESDA,data center smoke monitoring,air sampling,KTR-SD2,KITOZER

Meta Description:KITOZER KTR-SD2 aspirating smoke detector, air-sampling early warning, two-stage sensitivity, for data center and rack early fire detection.

Anchor: KITOZER by Guangzhou Laian · Data center fire alarm