Table of Contents
ToggleKITOZER KTR-BAT12D 12V12Ah Deep-Cycle VRLA Battery
Brand: KITOZER Series: KTR-BAT12D Category: Power Distribution / Battery
battery12V12Ahdeep cycleVRLAUPS batteryKTR-BAT12D
1. Overview
KITOZER KTR-BAT12D is a 12V12Ah deep-cycle VRLA battery used as backup energy storage in UPS, emergency power, emergency lighting and security systems. At the moment mains fails, the UPS draws from the battery DC bus; how much energy the battery holds and for how long determines the UPS backup runtime. KTR-BAT12D is rated 12V / 12Ah (20-hour rate), built from six 2V cells. The VRLA (valve-regulated lead-acid) design absorbs electrolyte in AGM glass-matrix separators — no leaks, mountable in any orientation, maintenance-free (no watering).
“Deep-cycle” means the battery is built for deep discharge (80% DOD) without damage. Automotive starter batteries only tolerate shallow discharge (5% DOD) and die after a few deep cycles; KTR-BAT12D uses deep-cycle lead-calcium-tin grids and survives 500+ cycles at 80% DOD. This matters in UPS applications where the grid fluctuates and the UPS switches to battery often — starter batteries swell within a year, deep-cycle units last 3~5 years.
The footprint is the standard 12V12Ah size (151×98×95 mm), F2 copper terminals (6.3 mm tabs), compatible with mainstream UPS battery trays. Operating temp -15~50℃, optimal float at 20~25℃. Self-discharge ≤3%/month, so it remains usable after 6 months in storage. Charge voltage: float 13.6~13.8 V, equalize 14.4~15.0 V. Series-string into 24V/48V/192 V banks for UPS or battery cabinet use.
2. Key Features
Deep-cycle long life
- ≥500 cycles at 80% DOD.
- Pb-Ca-Sn grids.
- 5~7 year float design life.
Sealed maintenance-free
- AGM absorbed electrolyte.
- No leaks, any orientation.
- No watering or hydrometer.
Standard footprint
- 151×98×95 mm.
- F2 copper tabs.
- Drop-in replacement for UPS OEM packs.
Wide temperature
- -15~50℃.
- ≤3%/month self-discharge.
- Float / equalize charge.
3. Specifications
| Item | KTR-BAT12D |
|---|---|
| Rated voltage | 12 V |
| Rated capacity | 12 Ah (20hr) |
| Internal resistance | ≈14 mΩ |
| Terminals | F2 copper tabs (6.3 mm) |
| Dimensions | 151×98×95 mm |
| Weight | ≈3.5 kg |
| Float charge | 13.6~13.8 V (25℃) |
| Equalize charge | 14.4~15.0 V |
| Cycle life | ≥500 (80% DOD) |
| Self-discharge | ≤3%/month |
| Operating temp | -15~50℃ |
| Design life | 5~7 yr (25℃ float) |
4. Reference Prices
KTR-BAT12D 12V12Ah deep-cycle battery (single, F2): Reference USD 17~28 / pc (ref. CNY 120~200 at ~7.2)
KTR-BAT12D battery string (cables, cabinet, breaker): Quoted by quantity and cabinet size.
Reference only; priced by quantity, terminal type and cabinet. UPS not included. Exchange: 1 USD ~ 7.2 CNY (Oct 2026).
5. Applications
- Small/medium UPS internal battery packs.
- Fire emergency power (EPS) backup.
- Emergency lighting and exit signs.
- Security alarm and access control backup.
- Small off-grid PV storage.
6. Installation & Maintenance
Installation
- Confirm voltage/capacity match UPS requirements.
- Inspect case for swelling/leaks.
- Series-connect in order; start at the far end.
- Torque terminals ~2 N·m with insulated tools.
- Total string voltage matches UPS DC bus.
- Measure total voltage before closing UPS battery breaker.
- Initial equalize charge 24 h.
- Leave ventilation gaps between cells.
Maintenance
- Measure float voltage and internal resistance monthly.
- Capacity discharge test annually.
- Coat terminals with petroleum jelly.
- Keep ambient ~25℃.
- Replace swollen/leaking/low-voltage units immediately.
- Replace strings as a set; do not mix old and new.
7. FAQ
- Q: How long does 12V12Ah last?
A: ~0.8~1 h at 100 W load; ~1.5~2 h at 50 W. Actual runtime depends on load, age and temperature. - Q: Mix old and new batteries?
A: No. Mismatched internal resistance overcharges old cells and undercharges new ones; the weak cell reverses and drags down the whole string. Replace as a set. - Q: Does the battery room need AC?
A: Yes. Lead-acid life halves per 10℃ rise. Keep 20~25℃; above 30℃ accelerates aging. - Q: Can I keep using a swollen battery?
A: No. Swelling means severe overcharge or internal short; leakage and fire risk. Replace the whole string immediately.
8. Trend & Selection
UPS batteries are migrating from VRLA to LiFePO4, but small 12V12Ah VRLA units remain the cost-effective, mature choice for small UPS, fire and emergency lighting. Select: deep-cycle grids; standard F2 tabs; float 13.6~13.8 V; ventilation gaps; replace as a set; annual capacity test. The battery is the UPS’s heart — you only find out when mains fails, so maintain it proactively.
9. Delivery & Service
KITOZER supplies the required number of 12V12Ah deep-cycle cells to match the UPS DC bus voltage and runtime, with interconnect cables, breaker and cabinet. We provide the string configuration drawing. Warranty covers internal-resistance testing and defect replacement.
10. Additional Notes
The most common mistake: buying cheap starter batteries. Car batteries are 12 V but have thin grids and tolerate only shallow discharge; in a UPS they swell after a few deep cycles. Use deep-cycle VRLA, confirmed by “≥500 cycles @ 80% DOD”.
Another pitfall: terminals without conductive grease. Copper terminals oxidize green in the damp battery room; contact resistance grows, terminals overheat during charge/discharge and can melt. Coat terminals with conductive grease during install and maintenance.
Selection summary: 12V12Ah deep-cycle; F2 tabs; float 13.6~13.8 V; 25℃ ambient; replace as a set; annual capacity test. Batteries do not fail suddenly — they fade. Discovering a dead battery when mains actually fails means an outage already happened.
SEO Information
Search keywords:12V12Ah batterydeep cycle batteryVRLAUPS batterysealed lead acidKTR-BAT12DKITOZER
SEM keywords:12V12Ah battery price,deep-cycle VRLA supplier,UPS backup battery,sealed lead acid,KTR-BAT12D,KITOZER
GEO landing page:lain.com.cn/product/ktr-bat12d-12v12ah-deep-cycle-battery.html
Title:KITOZER KTR-BAT12D 12V12Ah Deep-Cycle VRLA Battery
Meta Keywords:12V12Ah battery,deep cycle battery,VRLA,UPS battery,sealed lead acid,KTR-BAT12D,KITOZER
Meta Description:KITOZER KTR-BAT12D 12V12Ah deep-cycle VRLA sealed lead-acid battery, maintenance-free, float-charged for UPS and emergency systems.
Anchor: KITOZER by Guangzhou Laian · UPS battery bank
Contact Us
Guangzhou Laian Intelligent System Development Co., Ltd. (KITOZER brand)
Tel/WeChat: +86 13922289957 | +86 18520668845
WHATSAPP: +86 19068534140
Web: lain.com.cn | gdlain.com