KITOZER rack 12 port SC SM ODF

KITOZER KTR-SC12R2 Rack-mount 12-port SC SM Fiber Patch Panel (ODF)

Brand: KITOZER Series: KTR-SC12R2 Category: Data Center Engineering / Fiber Cabling

fiber patch panel12-port SCsingle-moderack mountODFKTR-SC12R2

[Product image: KITOZER KTR-SC12R2 1U rack-mount ODF with 12 SC simplex adapters]

1. Overview

KITOZER KTR-SC12R2 is a rack-mount 12-port SC single-mode fiber patch panel (also called ODF) mounted in a 19-inch rack to terminate backbone cables and cross-connect between cable and patch cords. In the data hall, backbone cable from the campus or outdoor vault enters the rear splicing tray — each fiber inside the cable is fusion-spliced to a pigtail whose SC connector plugs into the front SC adapter. The front then accepts SC patch cords to switch optical modules or horizontal cabling. The panel is the hub between cable termination and patch management.

12-port SC single-mode means 12 SC simplex adapters on the front — terminating up to 12 SM fibers. Single-mode fiber (OS2) has a yellow jacket, 9/125 μm core, supports long reach (10 km+) and high speed (10G/100G) for inter-rack and inter-building backbones. SC simplex adapters use a blue flange for SM UPC end faces. 1U height (44.45 mm), 19-inch rack mount, with a removable splicing tray.

KTR-SC12R2 is bent from cold-rolled steel, powder-coated, 1U, pre-loaded with 12 SC simplex adapters on the front, and holds up to 12 pigtail splices on the rear pull-out tray. The tray slides out for splicing and pushes back. Built-in cable manager and splice-protection holders. PC/UPC-polished end faces, insertion loss ≤0.3 dB. Rack ground lug bonds to the cabinet ground bar. Each panel is end-face cleaned and loss-tested before shipping.

2. Key Features

12-port SC SM

  • 12 SC simplex adapters pre-loaded.
  • Blue UPC, single-mode.
  • OS2 backbone ready.

1U compact

  • 19-inch 1U.
  • Cold-rolled steel powder coat.
  • Pull-out splice tray.

Splice integrated

  • Rear tray holds 12 splices.
  • Cable gland.
  • Splice protector holders.

Low loss

  • Insertion loss ≤0.3 dB.
  • UPC polish.
  • 100% tested at factory.

3. Specifications

Item KTR-SC12R2
Ports 12 × SC simplex
Fiber type OS2 SM 9/125μm
Flange Blue (UPC)
Size 19-inch 1U
Panel Cold-rolled steel powder coat
Splice tray 12 fibers, pull-out
Insertion loss ≤0.3 dB
Return loss ≥50 dB (UPC)
Wavelength 1310 / 1550 nm
Operating temp -20~70℃
Ground Rack ground lug

4. Reference Prices

[‘

KTR-SC12R2 12-port SC SM panel (adapters only, no pigtails): Reference USD 25~44 / unit (ref. CNY 180~320 at ~7.2)

‘, ‘

KTR-SC12R2 12-port SC SM panel (with 12 SC pigtails, pre-spliced): Reference USD 39~63 / unit (ref. CNY 280~450 at ~7.2)

‘, ‘

Reference only; priced by pigtails/pre-splice. Cabinet bulk on request. Exchange: 1 USD ~ 7.2 CNY (Oct 2026).

‘]

5. Applications

    [‘

  • Data hall backbone termination.
  • ‘, ‘

  • Building MDF fiber distribution.
  • ‘, ‘

  • Switch optical patch management.
  • ‘, ‘

  • Carrier fiber entry termination.
  • ‘, ‘

  • Enterprise server room ODF.
  • ‘]

6. Installation & Maintenance

Installation

    [‘

  • Mount panel to rack with M6 cage nuts.
  • ‘, ‘

  • Bring backbone cable in from rear, gland it.
  • ‘, ‘

  • Strip jacket, fan out tubes.
  • ‘, ‘

  • Splice each fiber to SC pigtail, shrink protector.
  • ‘, ‘

  • Stow splices in tray, bend radius ≥30 mm.
  • ‘, ‘

  • Plug pigtail SC into rear adapter.
  • ‘, ‘

  • Front: SC patch cord to switch.
  • ‘, ‘

  • Label each port with the far end.
  • ‘]

Maintenance

    [‘

  • Check labels monthly.
  • ‘, ‘

  • Cap unused ports.
  • ‘, ‘

  • Clean end face before every mating.
  • ‘, ‘

  • Spot-test port loss yearly.
  • ‘, ‘

  • Inspect cable gland and tray.
  • ‘]

7. FAQ

    [‘

  • Q: 12-port vs 24-port?
    A: Match cable fiber count. 12-fiber cable → 12-port, 24-fiber → 24-port. Keep 20% spare ports.
  • ‘, ‘

  • Q: Can SC SM and MM adapters mix?
    A: Physically yes, but mismatched mode-field adds loss. Use one type end-to-end.
  • ‘, ‘

  • Q: Bend radius in the tray?
    A: ≥30 mm static for SM. Tight kinks add macro-bend loss. Coil neatly, never sharp-fold.
  • ‘, ‘

  • Q: Does the panel need grounding?
    A: Bond the rack lug to the cabinet ground bar with 6 mm² green-yellow wire to discharge induced voltage on the cable armor.
  • ‘]

8. Trend & Selection

[“

Backbone moves to 40G/100G SM; ODFs trend toward higher density (1U with 24/48 ports) and pre-terminated factory-spliced kits. KTR-SC12R2 is the 12-port standard for small-to-medium halls and building IDFs. Select: ports match fiber count; SC SM UPC blue; pull-out tray; clean end faces; label every port. Inert as it is, the ODF is the cable-to-cord registry — every fiber’s route is recorded there.

“]

9. Delivery & Service

[‘

KITOZER supplies KTR-SC12R2 panels matched to backbone fiber count and rack U-space, with pre-loaded SC adapters and optional pigtails. We provide the termination drawing labeling each port, tube and far-end gear. Warranty covers adapter and tray replacement.

‘]

10. Additional Notes

[‘

A common mistake: too-tight bend radius in the tray. Folding fibers sharply into a 10 mm bend causes huge SM macro-bend loss. Coil at ≥60 mm diameter, loosely tie.

‘, ‘

Another pitfall: no labels. A tangle of cords after install; six months later nobody knows what goes where. Label both ends of every cord, matching the termination drawing.

‘, ‘

Selection summary: 12-port SC SM; 1U; pull-out tray; UPC blue; ≤0.3 dB; label every port. The ODF is the cabling hub — cable becomes patch cord here, and termination quality decides backbone performance.

‘]

SEO Information

Search keywords:fiber patch panel12-port SC panelSC SM ODFrack-mount fiber box1U ODFKTR-SC12R2KITOZER

SEM keywords:[’12-port SC panel price,SC SM ODF supplier,1U rack-mount fiber box,data center ODF,KTR-SC12R2,KITOZER’]

GEO landing page:lain.com.cn/product/ktr-sc12r2-12port-sc-sm-odf.html

Title:KITOZER KTR-SC12R2 Rack-mount 12-port SC SM Fiber Patch Panel (ODF)

Meta Keywords:fiber patch panel,12-port SC panel,SC SM ODF,rack-mount fiber box,1U ODF,KTR-SC12R2,KITOZER

Meta Description:KITOZER KTR-SC12R2 1U rack-mount 12-port SC single-mode fiber patch panel for backbone cable termination.