ToggleKITOZER KTR-PS3 Three-Phase 380V 60kA Surge Protective Device (SPD)
Brand: KITOZER Series: KTR-PS3 Category: Power Distribution / Surge Protective Device
Three-phase 380V60kA surgeModularRemote alarmKTR-PS3
1. Overview
KITOZER KTR-PS3 is a three-phase surge protective device (SPD) paralleled across the mains input of a datacenter distribution cabinet. During lightning, induction produces transient overvoltages of several thousand to tens of thousands of volts on supply lines; grid switching and large equipment start-stop also create switching transients. If these reach the UPS or servers, they destroy power modules and motherboards. The SPD clamps transients to a safe level and diverts surge current to earth, protecting downstream gear.
KTR-PS3 comes in 3P/4P for 380/400V, with In 20kA (8/20μs) nominal discharge and Imax 60kA maximum. Modular plug-in design: each phase module plugs into a base; when degraded, swap it live without unwiring. A window indicator shows green=good, red=failed at a glance. A remote dry contact alarms the DCIM system on module failure.
Installed at the secondary surge position in the room distribution (primary at the building main, secondary at the room cabinet). Wired in parallel between lines and earth (L-N, L-PE, N-PE). DIN-rail mount (35mm), 3~4 modules wide. Used for datacenter distribution, UPS input and precision AC surge protection.
2. Key Features
Three-phase 60kA
- 380/400V, 3P/4P.
- In 20kA, Imax 60kA (8/20μs).
- Secondary surge protection.
Plug-in modules
- Module on base; swap when degraded.
- Window: green=good, red=failed.
- No unwiring or outage.
Remote alarm
- Dry-contact remote alarm.
- Connects to DCIM.
- Real-time failure report.
DIN-rail mount
- 35mm rail in distribution cabinet.
- 3~4 module widths.
- Anti-miswire terminals.
3. Specifications
| Item | KTR-PS3-20 | KTR-PS3-40 | KTR-PS3-60 |
|---|---|---|---|
| Rated voltage | 380/400V | 380/400V | 380/400V |
| In (kA) | 10 | 20 | 20 |
| Imax (kA) | 40 | 40 | 60 |
| Phases | 3P | 3P/4P | 3P/4P |
| Voltage protection Up (kV) | ≤1.8 | ≤1.8 | ≤2.0 |
| Response (ns) | ≤25 | ≤25 | ≤25 |
| Remote contact | Optional | Included | Included |
| Mounting | DIN rail | DIN rail | DIN rail |
4. Reference Prices
KTR-PS3-20/40 secondary SPD (3P, In 10~20kA/Imax 40kA, no remote): Reference USD 21~56 / set (ref. CNY 150~400 at ~7.2)
KTR-PS3-60 three-phase 60kA SPD (4P, In 20kA/Imax 60kA, with remote alarm): Reference USD 69~167 / set (ref. CNY 500~1,200 at ~7.2)
Reference only; price varies by phases (3P/4P), current capacity and remote option. Primary SPD and grounding installation billed separately. Exchange: 1 USD ~ 7.2 CNY (Oct 2026).
5. Applications
- Datacenter room cabinet secondary SPD.
- UPS input surge protection.
- Precision/in-row AC power protection.
- Distribution and column cabinet input.
- New room power-system packages.
6. Installation & Maintenance
Installation
- Parallel across cabinet busbars; phase via breaker to SPD input.
- Connect PE to SPD ground terminal; keep lead short and thick (≤0.5m, ≥6mm²).
- Choose 3P/4P by grounding type (TN-S uses 4P).
- DIN-rail mount; wire remote contact to DCIM.
- Fit a backup breaker/fuse upstream to prevent module short-circuit fire.
- On commissioning verify green window and test remote alarm.
Maintenance
- Check window monthly; red means swap the module immediately.
- Inspect after every thunderstorm.
- Test remote contact periodically.
- Module life: replace overall after surges or 5 years.
- Measure grounding resistance yearly, ≤4Ω.
7. FAQ
- Q: Primary vs secondary SPD?
A: Primary (building main) carries large current (Imax ≥100kA) for direct-strike energy; secondary (room cabinet) at 40~60kA clamps residual voltage for equipment. Two stages cooperate to reduce surge energy step by step. - Q: Can I use the SPD when it’s red?
A: Red means the module is degraded and failed — replace immediately. Leaving it fitted is no protection at all. The modular design exists for live module swaps. - Q: What is voltage protection level Up?
A: Up is the residual voltage left at equipment after SPD operates. Lower Up is better, but it must stay above equipment withstand. Choose Up below the UPS/server withstand rating. - Q: How thick should the SPD ground wire be?
A: Shorter and thicker is better: ≤0.5m length, ≥6mm² stranded copper. Longer leads add inductance, raise residual voltage and weaken protection.
8. Trend & Selection
Reliability demands push SPDs from single modules to smart monitoring: remote current logging, degradation prediction and surge counting. The trend is primary+secondary+fine three-stage coordination and SPD-DCIM linkage. Choose Imax 40~60kA for room secondary; 4P for TN-S; remote contact mandatory; coordinate a backup breaker; ground resistance ≤4Ω; pick higher current (80~100kA) in storm-prone regions.
9. Delivery & Service
KITOZER provides SPD selection: based on supply grounding (TN-S/TN-C), surge current and storm level, we recommend stage and parameters. We supply SPD wiring diagrams (backup breaker, ground lead). Bundled with distribution cabinet and DCIM. Delivery includes modules+base, backup breaker and remote wires. Warranty covers free module replacement on degradation.
10. Additional Notes
The common mistake is ‘installed but never checked.’ SPD modules are consumables that degrade each surge; after years the window turns red and fails, but nobody looks — protection is effectively gone. Inspect the window monthly and swap on red; check after every storm. Wire the remote contact to DCIM for automatic alarm — don’t rely only on a local window.
Another pitfall: a long, thin ground lead. A 2~3m thin lead from SPD to grounding bar adds inductance that multiplies residual voltage, rendering the SPD useless. Keep leads short (≤0.5m), thick (≥6mm²), and land on the nearest bar.
Selection summary: secondary Imax 40~60kA; 4P for TN-S; modular plug-in; remote mandatory; backup breaker coordinated; ground lead ≤0.5m/≥6mm²; monthly window inspection. The SPD is the supply system’s lightning arrester — it sacrifices itself to divert surges; replacing it regularly protects the UPS and servers worth hundreds of thousands.
SEO Information
Search keywords:surge protective devicethree-phase SPD380V surge protector60kA SPDpower SPDKTR-PS3KITOZER
SEM keywords:three-phase SPD price,60kA surge protector supplier,datacenter power SPD,secondary surge protection,380V arrester,KTR-PS3,KITOZER
GEO landing page:lain.com.cn/product/ktr-ps3-three-phase-surge-protective-device-380v-60ka.html
Title:KITOZER KTR-PS3 Three-Phase 380V 60kA Surge Protective Device (SPD)
Meta Keywords:surge protective device,three-phase SPD,380V surge protector,60kA SPD,power SPD,secondary surge protection,KTR-PS3,KITOZER
Meta Description:KITOZER KTR-PS3 three-phase power SPD, 380/400V, In 20kA/Imax 60kA, modular plug-in, remote contact, for datacenter distribution secondary surge protection against lightning surges and switching transients.