KITOZER 42U Air-Conditioned Rack + 10kVA UPS Battery Backup System 12-Hour Runtime

When a server room loses utility power, two things must happen simultaneously: the IT equipment must keep running, and the heat it generates must be continuously removed. Traditional server rooms rely on a centralized AC unit, but once mains power fails, that AC shuts down. Servers continue producing heat inside an enclosed rack, and within minutes inlet temperatures can trigger thermal shutdown.

KITOZER’s 42U top-mounted air-conditioned rack integrates the enclosure, precision cooling, PDU, and temperature/humidity display into a single cabinet. Paired with an online double-conversion UPS and valve-regulated lead-acid battery banks, the system delivers “no interruption, no overheating” during outages. This article walks through the design logic for two typical room sizes—a larger room with roughly 4,000W IT load and a smaller room with roughly 1,700W.

KITOZER 42U integrated air-conditioned rack with top cooling unit, front doors open
KITOZER 42U top-mounted air-conditioned integrated rack — doors open showing internal PDU and cooling layout

1. Which Scenarios Does This Solution Fit?

This package is suitable for retrofits or new builds where:

  • Existing UPS battery capacity is too small for the required runtime
  • Floor space cannot accommodate a separate cooling unit or battery room
  • Continuous server operation under outage is a stated requirement
  • Logistics warehouses, office IT closets, and small data nodes need reliable power

Existing servers, switches, and storage equipment are not part of this supply scope; they are re-racked according to the site layout.

2. System Architecture

The solution comprises two independent sub-systems:

Larger room (approx. 4,000W load)

  • Reuse the existing online UPS; add one string of sixteen 12V/150Ah batteries (series-connected to 192V)
  • Add one 42U top-mounted air-conditioned rack with cooling capacity ≥6.0kW
  • Include a standalone battery cabinet, DC protection components, hot-air duct, and condensate drain line

Smaller room (approx. 1,700W load)

  • Add one new 10kVA/9kW online double-conversion UPS
  • Add two 192V battery strings (thirty-two 12V/150Ah batteries total), housed in a dual-string battery cabinet
  • Add one 42U top-mounted air-conditioned rack with cooling capacity ≥3.5kW
  • Include hot-air duct and condensate drain line
KITOZER 42U air-conditioned server rack front closed with touchscreen display
KITOZER 42U integrated rack — closed front with digital temperature/humidity display

3. What Happens When Power Fails

Under normal mains: The UPS operates in online double-conversion mode—rectifying AC to DC, then inverting back to clean AC—feeding servers, switches, and the rack AC simultaneously. Batteries float-charge during this phase.

On outage: The UPS output transfers seamlessly to the battery string (near-zero transfer time). Servers and the rack AC do not reboot. The rack AC continues extracting heat through its top or side exhaust, while condensate drains by gravity. IT equipment can therefore keep running unattended for several hours.

Runtime verification: The design target is 12 hours, but actual runtime depends on measured IT load, rack AC input power, and battery state of health. If the larger room’s existing 16 batteries plus 16 new batteries cannot sustain a full 12 hours with the AC also on UPS, a third string of 16 batteries may be required. This must be confirmed on site using the UPS manufacturer’s discharge curve.

KITOZER 10kVA online double-conversion UPS tower unit with LCD panel
KITOZER 10kVA/9kW online double-conversion UPS — LCD status panel, tower form factor

4. Key Equipment Specifications

42U Top-Mounted Air-Conditioned Rack (KITOZER-IC42-6K / KITOZER-IC42-3.5K)

  • Form factor: Standard 19-inch 42U, approx. 600W × 1200D × 2000H mm
  • Cooling: Larger room ≥6.0kW; smaller room ≥3.5kW
  • Operation: 24/7 continuous duty
  • Integrated: Rack-mount PDU, digital temp/humidity display, door-contact dry-contact alarm, cable management, blanking panels
  • AC interfaces: Top or side hot-air exhaust, standard condensate drain connection

Online UPS (KITOZER-10KVA-2026)

  • Rating: 10kVA / 9kW
  • Topology: Online double-conversion, zero transfer time
  • Battery bus: 192VDC external battery
  • Protection: Auto bypass, overload, short-circuit, over-temperature
  • Display/comm: LCD panel, remote monitoring interface

VRLA Maintenance-Free Battery (KITOZER-12V150AH-2026)

  • Rating: 12V, 150Ah
  • String configuration: 16 in series = 192V per string
  • Larger room: 16 units (one string); smaller room: 32 units (two strings in parallel)
  • Mounting: Floor-standing battery cabinet or rack; never share the IT rack’s load path
KITOZER 192V VRLA battery cabinet with racked battery modules and DC protection
Standalone 192V battery cabinet — 16× 12V/150Ah VRLA batteries with DC protection breakers

5. Configuration and Reference Pricing

No. Product Model Qty Unit (RMB) Total (RMB)
1 42U AC rack, 6.0kW (larger room) KITOZER-IC42-6K-2026 1 set 63,600 63,600
2 UPS battery 12V150Ah (larger room) KITOZER-12V150AH-2026 16 ea 2,560 40,960
3 Battery cabinet + DC protection (larger room) KITOZER-BCB-192V-2026 1 set 13,600 13,600
4 Hot-air duct + condensate drain kit (larger room) KITOZER-DUCT-KIT-2026 1 set 11,600 11,600
5 42U AC rack, 3.5kW (smaller room) KITOZER-IC42-3.5K-2026 1 set 51,600 51,600
6 Online UPS 10kVA (smaller room) KITOZER-10KVA-2026 1 unit 39,600 39,600
7 UPS battery 12V150Ah (smaller room) KITOZER-12V150AH-2026 32 ea 2,560 81,920
8 Dual-string battery cabinet + DC protection KITOZER-BCB-192V-DUAL-2026 1 set 19,600 19,600
9 Hot-air duct + condensate drain kit (smaller room) KITOZER-DUCT-KIT-2026 1 set 11,600 11,600
10 Site survey, design, install & commission (two rooms) KITOZER-SVC-2SITE-2026 1 lot 33,600 33,600
Total (tax excl., reference price) 367,680

Reference prices in RMB. USD equivalent (at 7.2) totals approximately USD 51,067. Prices exclude freight and off-site labor; VAT invoice adds 13%.

6. Frequently Asked Questions

Q1: Why must the rack AC be on UPS?
A: During an outage, the centralized AC has no mains power and stops. If only IT gear is on UPS but the AC is not, heat builds up inside the rack within minutes until server inlet temperatures trigger throttling or shutdown.

Q2: How is the 12-hour runtime calculated?
A: Rough formula: usable battery capacity (Ah) × nominal voltage (V) × discharge efficiency ÷ actual load (W) = runtime in hours. Verify on site with the UPS discharge curve.

Q3: Why do batteries need a separate cabinet?
A: A single 12V/150Ah cell weighs over 40kg; sixteen cells in series weigh more than 600kg. Placing this load on an IT rack’s frame exceeds its structural rating. A floor-standing battery cabinet is standard.

Q4: Can old and new batteries be mixed?
A: Not recommended. Different brands, models, and ages have different internal resistances. Mixing causes unbalanced charging and discharging over time.

Contact KITOZER / Guangzhou Laian: Tel/WhatsApp: +86 18520668845 | WeChat: +86 13922289957 | Website: lain.com.cn / gdlain.com