Data Center Smart Lighting System | LED Strip Luminaire, Microwave Sensor, SNMP Gateway | KITOZER

Data Center Smart Lighting System: LED Strip, Microwave Sensor, SNMP Gateway

KITOZER data center smart lighting solution replaces conventional fluorescent fixtures with 1200mm LED strip luminaires, DC24V quick-connect harness, custom control box, microwave occupancy sensors, 4.0″ touch panels, and an SNMP gateway that integrates with the BMS/DCIM platform. Scene control, occupancy linkage, and daylight harvesting cut lighting energy use by 40–60% in large data centers.

1200mm LED strip linear luminaire for data center aisle

1. Why Smart Lighting in Data Centers?

Data center lighting runs 7×24 in server aisles, corridors, and electrical rooms. Conventional 36W T8 tubes waste energy during unmanned periods and offer no integration with DCIM. KITOZER’s smart system uses 24–36W LED strips, dimmable 0/1–10V or DALI, and occupancy sensors to drop aisle light to 20% when no personnel are present, restoring 100% on approach.

2. Key Components

Component Spec
LED strip luminaire 1200mm, 30W, 4000K, CRI>80, IP40 aisle / IP54 electrical room
Quick-connect harness DC24V busbar with plug-in tees, no field wiring
Control box Custom DIN-rail box, 8 zones, 0/1–10V dimming, relay outputs
Microwave occupancy sensor 5.8GHz, 360° detection, 8m range, time/lux threshold adjustable
Touch panel 4.0″ color, wall-mount, scene selection
SNMP gateway RS485/Ethernet, MIB for BMS/DCIM, alarm on lamp failure

DC24V LED tube with quick-connect leads

3. Lighting Control Scenes

  • Normal operation: aisle 100%, corridor 60%, electrical room 100%.
  • Occupancy standby: aisle drops to 20% when no personnel detected for 5 minutes.
  • Maintenance / maintenance mode: all zones 100% via touch panel or BMS command.
  • Emergency: linked to fire alarm — emergency lighting circuits energize, normal lights off.
  • Daylight harvesting: perimeter zones dim based on ambient lux sensor.

Linear LED channel luminaire with aluminum extrusion

4. Integration with BMS/DCIM

The SNMP gateway exposes lamp status, dimming level, sensor events, and alarm logs to the BMS over Modbus-TCP or SNMP v2c. Operators can create scenes from the DCIM dashboard, schedule lighting by shift, and receive e-mail/SNMP traps on lamp or driver failure. No extra software license required for basic scenes.

5. Typical Project Configuration

For a 500-rack data center with 10 aisles, corridor, and 4 electrical rooms: ~240 LED strips, 25 microwave sensors, 1 control box, 4 touch panels, 1 SNMP gateway, DC24V harness. Reference price ~RMB 1,675,328 (~USD 232,684) per project-level configuration. Final pricing depends on rack count, ceiling height, and BMS protocol.

42U server rack in cold aisle with LED strip lighting

6. About KITOZER

KITOZER engineers data center lighting, DCIM, and electrical room monitoring packages — from luminaires and sensors to control boxes, touch panels, and BMS integration. Contact us for a site survey and scene design.