ToggleThe Floor Is a Plenum
Raised access flooring does two jobs: it creates a space under the floor for cables and conditioned air, and it provides a flat, level surface for server racks. Here’s how to specify it.
Key Specs
| Parameter | Standard | High Load |
|---|---|---|
| Panel size | 600×600mm | 600×600mm |
| Height (underfloor) | 300mm | 450mm |
| Panel material | Steel + anti-static tile | Steel + anti-static tile |
| Load rating | 500kg/m² | 1000kg/m² |
| Ground resistance | 10^6 – 10^9 ohm | 10^6 – 10^9 ohm |
| Reference price | $45/m² | $75/m² |
Cable Underfloor
The underfloor space carries power cables (left side), data cables (right side), and CRAC cold air. Use cable separators to keep power and data at least 150mm apart. Ground every panel to the floor stringers.
Installation Note
Racks sit on the raised floor. Anchor each rack through a floor panel into the subfloor with M16 expansion bolts. Don’t rely on the floor panel alone to carry a 1500kg rack – the panel must transfer load to the subfloor.
KITOZER / Guangzhou Laian Intelligent System Development Co., Ltd. – raised flooring, server room infrastructure. Call +86 13922289957 (WeChat) or +86 18520668845. WhatsApp +86 19068534140. Web: www.gdlain.com | www.lain.com.cn. Address: Chaotian Park, Zhongrun Industrial Zone, Shilou, Panyu, Guangzhou, China.