KITOZER
KITOZER

Cable Tray Installation Between Racks: Hangers, Radius and Separation

Run Cables Overhead, Not Underfoot

Overhead cable trays connect racks in a row. Cables run above the cold aisle, keeping the floor clear and the air path open. Here’s the installation method.

Installation Steps

  1. Mark the path: The tray runs above the rack row, centered. Width: 300mm for medium rows, 400mm for dense rows.
  2. Install hangers: Steel rods from the ceiling structure, every 1.5 meters. Threaded M10 rod with adjustable clamps.
  3. Assemble tray sections: Bolt tray sections together with splice plates. The tray bottom should be flat, no gaps.
  4. Add radius turns: At corners, use a 90-degree radius bend (not a sharp turn). Fiber trays need 300mm minimum radius.
  5. Separate power and data: Use a divider in the tray, or run two trays. Power on the left, data on the right, 150mm separation.
  6. Ground the tray: Bond each section to the rack ground. Use a 6mm² green-yellow wire at both ends.
  7. Drop to racks: Use a vertical drop (flexible conduit or straight section) from the tray to each rack top. Secure with a J-hook.

Cost

Tray sections: $35 per 2m length. Hangers: $12 per set. Radius bend: $25. Divider: $8 per meter. A 10-rack row typically uses 15m of tray = about $550 in materials.

KITOZER / Guangzhou Laian Intelligent System Development Co., Ltd. – cable trays, overhead routing. Call +86 13922289957 (WeChat) or +86 18520668845. WhatsApp +86 19068534140. Web: www.gdlain.com | www.lain.com.cn. Address: Chaotian Park, Zhongrun Industrial Zone, Shilou, Panyu, Guangzhou, China.

Shopping Cart