ToggleRun Cables Overhead, Not Underfoot
Overhead cable trays connect racks in a row. Cables run above the cold aisle, keeping the floor clear and the air path open. Here’s the installation method.
Installation Steps
- Mark the path: The tray runs above the rack row, centered. Width: 300mm for medium rows, 400mm for dense rows.
- Install hangers: Steel rods from the ceiling structure, every 1.5 meters. Threaded M10 rod with adjustable clamps.
- Assemble tray sections: Bolt tray sections together with splice plates. The tray bottom should be flat, no gaps.
- Add radius turns: At corners, use a 90-degree radius bend (not a sharp turn). Fiber trays need 300mm minimum radius.
- Separate power and data: Use a divider in the tray, or run two trays. Power on the left, data on the right, 150mm separation.
- Ground the tray: Bond each section to the rack ground. Use a 6mm² green-yellow wire at both ends.
- Drop to racks: Use a vertical drop (flexible conduit or straight section) from the tray to each rack top. Secure with a J-hook.
Cost
Tray sections: $35 per 2m length. Hangers: $12 per set. Radius bend: $25. Divider: $8 per meter. A 10-rack row typically uses 15m of tray = about $550 in materials.