Table of Contents
ToggleCommon Grounding Errors
A ground wire that looks connected might not be. Here are the five most common mistakes we see on rack grounding installations.
1. Grounding to a Painted Surface
The rack is powder-coated. A screw through a painted hole contacts paint, not metal. Resistance reads 10+ ohms. Fix: use the designated grounding stud (bare metal), or scrape paint to bare metal at the connection point.
2. Too Thin a Wire
Using a 1.5mm² wire because that’s what’s in the toolbox. The standard is 6mm² minimum for a single rack. Thin wire burns open during a surge, leaving equipment unprotected.
3. No Row Bonding
Each rack grounded independently to the building earth. But racks in a row aren’t bonded to each other. Different ground potentials between racks cause ground loops and equipment damage. Fix: install a grounding busbar and bond each rack to it.
4. Loose Ring Terminal
The ring terminal isn’t crimped properly. Wiggles on the wire. Under vibration, it falls off. Fix: crimp with the correct tool, tug test before install.
5. No Continuity Test
The ground wire is installed, but nobody measured the resistance. It “looks right.” Fix: test with a multimeter. Should read under 1 ohm from rack frame to earth bar.
KITOZER / Guangzhou Laian Intelligent System Development Co., Ltd. – grounding, power safety. Call +86 13922289957 (WeChat) or +86 18520668845. WhatsApp +86 19068534140. Web: www.gdlain.com | www.lain.com.cn. Address: Chaotian Park, Zhongrun Industrial Zone, Shilou, Panyu, Guangzhou, China.