Multi-Rack Layout: Arrange Rows for Optimal Airflow

The Row Layout Determines Cooling Efficiency

How you arrange racks in a room matters. Hot aisle/cold aisle arrangement ensures cold air goes into rack fronts and hot air exits the backs without mixing.

KITOZER data center hot cold aisle layout

Standard Layout

  1. Racks face each other in rows: front-to-front, back-to-back.
  2. The space between rack fronts = cold aisle.
  3. The space between rack backs = hot aisle.
  4. CRAC units blow cold air into the cold aisle (via underfloor or duct).
  5. Hot air rises from the hot aisle and returns to the CRAC.

Aisle Width

Aisle Minimum Width Recommended
Cold aisle 1000mm 1200-1500mm
Hot aisle 800mm 1000mm
End of row (walkway) 1000mm 1200mm

Don’t Mix Orientations

Never turn one rack 90 degrees. It disrupts the airflow pattern and creates a hot spot. All racks in a row face the same direction.