Table of Contents
ToggleBad Grounding Is Worse Than No Grounding
A poor ground creates ground loops, static buildup, and unsafe fault paths. Here are the most common mistakes.
Mistake: No Dedicated Ground Wire
The rack sits on rubber casters with no metal path to earth. Fix: run a 6mm² green-yellow cable from the rack grounding bar to the building PE busbar.
Mistake: Grounding Through the PDU Cord
“The PDU is plugged in, so the rack is grounded.” Wrong – the PDU chassis isn’t bonded to the rack frame. Fix: bond the PDU chassis to the rack grounding bar.
Mistake: Daisy-Chaining Racks
“Rack A grounds to Rack B, Rack B to ground.” If the link breaks, Rack A floats. Fix: every rack has its own ground wire to the PE busbar.
Mistake: Loose Connection
A hand-tightened lug vibrates loose. Fix: torque to 1.2 Nm, add a lock washer, re-check quarterly.
KITOZER / Guangzhou Laian Intelligent System Development Co., Ltd. – grounding mistakes, safety. Call +86 13922289957 (WeChat) or +86 18520668845. WhatsApp +86 19068534140. Web: www.gdlain.com | www.lain.com.cn. Address: Chaotian Park, Zhongrun Industrial Zone, Shilou, Panyu, Guangzhou, China.