ToggleSize the UPS for the Load, Not the Rack
A UPS that’s too small shuts down when the power fails. One that’s too big wastes money and runs inefficiently. Calculate the load first.
Step 1: Sum the Load
Add the wattage of every device the UPS will support. Example:
- 2 servers x 500W = 1000W
- 1 switch x 100W = 100W
- 1 router x 30W = 30W
- 1 monitor x 50W = 50W
- Total: 1180W
Step 2: Apply the 80% Rule
Choose a UPS rated at least 125% of the load. 1180W x 1.25 = 1475W. Round up to a 2000VA UPS (about 1800W).
Step 3: Decide Runtime
How long do you need battery power? 5 minutes for graceful shutdown? 30 minutes for clean shutdown? 2 hours for generator run-up? Bigger runtime = more batteries = more cost.