Grounding Bar Installation: The Rack Must Be Earthed

A Rack Without Ground Is a Shock and Fire Hazard

Static electricity, fault currents, and EMI all need a path to earth. The grounding bar (copper bus bar) inside the rack connects every device’s ground lug to a single point, which then runs to the building earth.

Installation Steps

  1. Mount the copper ground bar vertically on the rear rail (1U or 2U tall, with 5-10 screw terminals).
  2. Run a thick ground wire (6-10mm2) from the bar to the rack’s ground lug.
  3. From the rack lug, run a 6-16mm2 green-yellow wire to the building earth point.
  4. Connect each device’s ground lug to the bar with a short ground wire.
  5. Tighten all connections (loose ground = no ground).
  6. Test with a multimeter: resistance from rack to earth should be under 1 ohm.