PDU Overload: Prevent Circuit Tripping

A PDU Has a Maximum Load – Exceed It and the Breaker Trips

Each PDU circuit has a rating (10A, 16A, 32A). Plug in too many devices and the overcurrent protection trips. Plan the load before plugging in.

How to Calculate

  1. List every device plugged into the PDU and its wattage.
  2. Sum the watts.
  3. Convert to amps: Amps = Watts / Volts (at 230V).
  4. Compare to the PDU rating. Stay under 80%.
  5. Example: 10 devices at 200W each = 2000W = 8.7A. On a 16A PDU, that’s 54% – safe.

If You’re Overloaded

  • Spread devices across two PDUs (on different circuits).
  • Move low-priority devices to a second PDU.
  • Upgrade to a higher-amperage PDU (32A needs thicker cables).
  • Use a metered PDU to monitor load continuously.