- Rack level front-to-back and side-to-side.
- Rack bolted to floor or wall.
- All cage nuts installed, no missing screws.
- Equipment at correct U positions, rails aligned.
- Screws torqued to 2.5 Nm.
- Power cables in PDU, labeled both ends.
- Network cables in correct switch ports, labeled.
- Ground wire connected to earth point.
- Ground resistance under 1 ohm.
- Blanks fill empty U-slots.
- Cable management used properly.
- Cable ties secure, not over-tight.
- Fans spinning, no unusual noise.
- Temperature/humidity sensor installed and reading.
- UPS powered on, battery charging, self-test passed.
- Door closes and seals; lock works.
- All labels applied.
- Monitoring sees all devices (SNMP ping OK).
- Alert thresholds set.
- Documentation updated.