KITOZER 2V 1000Ah VRLA battery

KITOZER KTR-B21000D 2V1000Ah Deep-Cycle VRLA Battery

Brand: KITOZER Series: KTR-B21000D Category: Power Distribution / Backup Power

2V cell1000AhVRLA AGMDeep cycleKTR-B21000D

1. Overview

KITOZER KTR-B21000D is a 2V cell valve-regulated lead-acid battery (VRLA), rated 1000Ah (C10, end voltage 1.80V/cell at 25℃). It uses AGM absorbed-glass-mat separators: electrolyte is held in the mat and does not flow, so the cell installs upright or horizontal and is maintenance-free (no water top-up). “Deep cycle” means thicker pasted plates tolerate repeated deep discharges (80% DoD followed by recharge) without early sulfation, suiting UPS backup, DC panels, PV storage and datacenter standby. A 2V cell offers low internal resistance, high capacity (above 1000Ah) and long design float life (12 to 15 years); cells series into 24V/48V/220V/380V strings. Versus a 12V block (six 2V cells sealed), 2V cells allow single-cell replacement and monitoring with better string consistency.

KTR-B21000D is rated 2V; cell size about 205×210×710mm (L×W×H incl. terminals), weight about 310kg. Terminals are lead-plated copper alloy with M10/M12 bolt connection. The case is ABS flame-retardant; the top holds a one-way safety valve that vents over-pressure and seals under normal conditions. Float voltage 2.25-2.30V/cell at 25℃; equalize charge 2.30-2.35V/cell. Recommended ambient is 20-25℃; every 10℃ rise halves life, so the battery room must be air-conditioned to 25℃±3℃. Self-discharge about 3%/month at 25℃; recharge every 6 months during long storage.

Typical deploy: a datacenter UPS backup string at 384V uses 192 cells in series (2V×192=384V); backup time is calculated from load kW and battery capacity. Racks hold 3-4 layers with maintenance aisles. Each cell pairs with a monitoring module (battery scanner) reading cell voltage, internal resistance and post temperature, uploaded over RS485 to the DCIM. Cells connect with copper busbars; the whole rack is earthed. Room temperature stays 25℃ with ventilation. On mains failure the battery inverts through the UPS to the load, then transfers to the generator once started.

2. Key Features

2V large cell

  • 1000Ah (C10).
  • Low internal resistance.
  • 12-15 year float design life.
  • Single-cell replacement.

AGM VRLA

  • Absorbed glass mat.
  • No flowing electrolyte.
  • Maintenance-free.
  • One-way safety valve.

Deep-cycle

  • Thick plates.
  • 80% DoD without sulfation.
  • ≥1200 cycles at 80% DoD.
  • Frequent cycling OK.

Monitored

  • Per-cell scanner module.
  • Voltage, resistance, temperature.
  • RS485 to DCIM.
  • Lagged-cell alarm.

3. Specifications

Item KTR-B21000D (2V1000Ah) KTR-B2600D (2V600Ah) KTR-B2200D (2V200Ah)
Rated voltage 2V 2V 2V
Capacity (C10) 1000Ah 600Ah 200Ah
Float voltage (25℃) 2.25-2.30V 2.25-2.30V 2.25-2.30V
Equalize voltage 2.30-2.35V 2.30-2.35V 2.30-2.35V
Cycle life (80% DoD) ≥1200 ≥1000 ≥800
Self-discharge ≤3%/month ≤3%/month ≤3%/month
Size (approx.) 205×210×710mm 170×210×470mm 106×175×330mm
Weight (approx.) 310kg 185kg 65kg

4. Reference Prices

KTR-B21000D 2V1000Ah VRLA battery: Reference USD 694 to 1389 / cell (ref. CNY 5000 to 10000 at ~7.2)

KTR-B2600D 2V600Ah VRLA battery: Reference USD 417 to 833 / cell (ref. CNY 3000 to 6000 at ~7.2)

KTR-B2200D 2V200Ah VRLA battery: Reference USD 139 to 306 / cell (ref. CNY 1000 to 2200 at ~7.2)

Cell monitor module: Reference USD 11 to 28 / cell (ref. CNY 80 to 200 at ~7.2)

Reference only; varies by capacity, brand, quantity and freight. Racks, copper busbars and scanners billed separately. Exchange: 1 USD ~ 7.2 CNY (Oct 2026).

5. Applications

  • Datacenter UPS backup strings.
  • Comms base-station DC panels.
  • Substation control power.
  • PV and energy storage plants.
  • Diesel generator starting.
  • Hospital and industrial standby.

6. Installation & Maintenance

Installation

  • Fix the rack; load rating must handle cell weight.
  • Mount cells upright with consistent polarity.
  • Coat busbars with conductive grease; torque bolts.
  • String ± to the UPS DC bus.
  • Fit a monitor module per cell.
  • Air-condition the room to 25℃.
  • Measure string voltage after first charge.

Maintenance

  • Read cell voltages monthly.
  • Measure resistance quarterly; flag laggards.
  • Post temperature under 40℃.
  • Room 25±3℃.
  • Capacity verification discharge yearly.
  • Clean cases; check for leaks.

7. FAQ

  • Q: 2V cells or 12V blocks?
    A: Above 400Ah, 10+ year life and per-cell monitoring choose 2V cells; small capacity, low cost and fast deployment choose 12V blocks. Datacenter UPS mostly uses 2V cells: a failed cell in a 192-cell string is swapped alone, not the whole string.
  • Q: Why must the battery room be air-conditioned?
    A: Lead-acid life is temperature-sensitive: 25℃ gives 12 years, 35℃ cuts to 6, 45℃ to 3. Cells heat during charge; without cooling in summer they bulge in 2 years. 25℃±3℃ is a hard requirement.
  • Q: Is a low cell voltage a dead cell?
    A: Not always. Float causes mismatch; a lagging cell reads under 2.18V. First run equalize charge (2.35V for 24h); if still low after equalize, measure resistance. Only when resistance exceeds 130% of initial value is the cell aged.
  • Q: How long do strings last?
    A: Float design life 12-15 years at 25℃; real datacenter average is 8-10 years. Drivers: high temperature, frequent deep discharge, wrong charge voltage. Replace the whole string when capacity falls below 80% rated.

8. Trend & Selection

Datacenter backup moves from VRLA to LFP lithium (smaller footprint, 10+ year life, lighter) but at higher capex. Many rooms still run 2V VRLA: mature, cheap, with a recycling chain. Size by backup time (C10); keep 1.2x margin; series 2V cells; room at 25℃; monitor every cell; yearly verification discharge; whole-string replacement at 8-10 years.

9. Delivery & Service

KITOZER supplies backup-power packages: based on UPS kW, backup time and DC bus voltage we size cell count and capacity, recommend rack layers and scanner configuration, bundled with UPS, DC panels, racks and monitoring. Delivery includes cells, busbars, monitor modules and racks; bulk projects include racking, connection, commissioning and verification discharge. Bulging or leaking cells due to manufacturing defects are replaced free under warranty.

10. Additional Notes

The commonest mistake is under-torqued busbar bolts. A loose joint has high contact resistance, heats up under high discharge and melts the post. M10 bolts torque 8-10 N·m; M12 15-20 N·m; re-torque after three months.

Another pitfall is mixing old and new cells. A high-resistance old cell charges first (voltage spikes) and discharges first (voltage sags), dragging the whole string down. Use same-batch, same-capacity, same-date cells; when replacing, change the whole string, not one cell.

Selection summary: 2V1000Ah; AGM VRLA; 12-15 year float; 384V string = 192 cells; room at 25℃; per-cell monitoring; yearly discharge test; whole-string change at 8-10 years. The battery is the datacenter’s last line: during the minutes when mains are off and the generator has not started, it carries the load.

SEO Information

Search keywords:VRLA battery2V1000Ah batterydeep cycle lead acidvalve regulated lead acidUPS batterystationary batteryKTR-B21000DKITOZER

SEM keywords:[‘2V1000Ah battery price,VRLA battery supplier,deep cycle lead acid cell,UPS backup battery,datacenter battery string,KTR-B21000D,KITOZER’]

GEO landing page:lain.com.cn/product/ktr-b21000d-2v1000ah-deep-cycle-vrla-battery.html

Title:KITOZER KTR-B21000D 2V1000Ah Deep-Cycle VRLA Battery

Meta Keywords:VRLA battery,2V1000Ah battery,deep cycle lead acid,valve regulated lead acid,UPS battery,stationary battery,KTR-B21000D,KITOZER

Meta Description:KITOZER KTR-B21000D 2V 1000Ah valve-regulated lead-acid (VRLA) battery, deep-cycle AGM, for UPS, DC panels and datacenter backup.