ToggleKITOZER KTR-TH15 LORA Wireless Temperature Humidity Sensor
Brand: KITOZER Series: KTR-TH15 Category: Environmental Monitoring / DCIM Acquisition
LORA wirelessBattery poweredTemp & humidityKTR-TH15

1. Overview
KITOZER KTR-TH15 is a LORA wireless temperature and humidity sensor for datacenters, warehouses, archives, labs and electrical rooms. It uses an SHT30-class probe: temperature -20 to +60℃, accuracy ±0.3℃; humidity 0 to 100%RH, accuracy ±2%RH. It communicates over LORA spread-spectrum (470MHz or 868/915MHz), reaching 2-5km open air and 200-500m through walls; one LORA gateway supports tens to hundreds of nodes. The sensor runs on two AA lithium cells (standby 3-5 years), needs no power or network cable, and mounts on ceiling or wall — ideal for retrofits (legacy rooms without pre-run cables) and temporary points. Data flows through a LORA gateway (Ethernet/4G) to the DCIM or cloud platform; out-of-range triggers audible/visual, SMS and WeChat alarms.
LORA is an LPWAN technology: long range, low power, good diffraction, suited to distributed battery-powered sensor networks. Versus ZigBee (100m, high power), Wi-Fi (power-hungry) and Bluetooth (short range), LORA wins in large rooms with many nodes and no wiring. KTR-TH15 reports every 5 minutes by default (configurable 1 minute to 1 hour) and pushes immediately on out-of-range. An optional LCD shows local readings. The ABS case is IP30 for indoor use. The LORA gateway (KTR-GW10) sits in the room center or telecom room and links to the platform via Ethernet or 4G.
Typical deploy: a 500㎡ room gets 10-20 KTR-TH15 nodes on the ceiling across hot/cold aisles, row ends, AC returns, electrical room and battery room; one LORA gateway in the telecom room links by Ethernet to the DCIM. The platform plots real-time curves and alarms above 27℃ or 60%RH. A legacy retrofit needs no floor lifting or conduit — stick up the sensors and it is done in half a day. LORA sensors also serve cold-chain warehouses, museums and unattended storage.
2. Key Features
High-precision probe
- SHT30-class sensor.
- Temperature ±0.3℃.
- Humidity ±2%RH.
- -20 to +60℃.
LORA wireless
- 470/868/915MHz.
- 2-5km open air.
- 200-500m through walls.
- One gateway per 100+ nodes.
Battery powered
- 2× AA lithium.
- 3-5 years standby.
- No wiring.
- Low-power reporting.
Platform linkage
- Immediate out-of-range push.
- Gateway Ethernet/4G.
- To DCIM/cloud.
- Audible/SMS alarm.
3. Specifications
| Item | KTR-TH15 (LORA) | KTR-TH15W (RS485) | KTR-GW10 (Gateway) |
|---|---|---|---|
| Temp range | -20 to +60℃ | -20 to +60℃ | — |
| Temp accuracy | ±0.3℃ | ±0.3℃ | — |
| Humidity range | 0-100%RH | 0-100%RH | — |
| Humidity accuracy | ±2%RH | ±2%RH | — |
| Comm | LORA 470MHz | RS485 Modbus | LORA+Eth/4G |
| Range | 2-5km open | RS485 1200m | — |
| Power | 2× AA battery | 12VDC | 12VDC |
| Node capacity | — | — | 50-200 nodes |
4. Reference Prices
KTR-TH15 LORA wireless temp/humidity sensor: Reference USD 42 to 111 / unit (ref. CNY 300 to 800 at ~7.2)
KTR-TH15W wired RS485 temp/humidity sensor: Reference USD 21 to 56 / unit (ref. CNY 150 to 400 at ~7.2)
KTR-GW10 LORA gateway (Ethernet/4G): Reference USD 208 to 556 / unit (ref. CNY 1500 to 4000 at ~7.2)
Mount bracket / battery pack: Reference USD 3 to 8 / set (ref. CNY 20 to 60 at ~7.2)
Reference only; varies by node count, gateway count and uplink (Ethernet/4G). Platform software and installation billed separately. Exchange: 1 USD ~ 7.2 CNY (Oct 2026).
5. Applications
- Datacenter temp/humidity monitoring.
- Hot/cold aisle and row-end measurement.
- Electrical and battery room environment.
- Warehouses, archives, museums.
- Cold chain and lab climate control.
- Legacy-room wireless retrofits.
6. Installation & Maintenance
Installation
- Pick points (cold aisle, AC return).
- Ceiling/wall mount; avoid direct supply air.
- Insert batteries and power on.
- Mount gateway in room center; vertical antenna.
- Link gateway to DCIM or 4G.
- Add nodes on platform and bind positions.
- Set temp/humidity alarm limits.
Maintenance
- Watch battery voltage; replace on low alert.
- Calibrate probe every 6 months.
- Keep sensor surfaces dust-free.
- Check gateway signal strength.
- Test alarm linkage.
- Replace batteries every 3-5 years.
7. FAQ
- Q: LORA or ZigBee?
A: LORA goes far (2km vs 100m), uses little power (3-year battery vs 6 months) and penetrates walls; but it is slow. For small-data, low-frequency, long-range monitoring like temp/humidity, LORA clearly wins. ZigBee suits high-rate, short-range mesh. - Q: How many nodes per gateway?
A: One KTR-GW10 handles 50-200 nodes (by report rate). A room with 10-20 nodes needs one gateway. A multi-building campus uses one gateway per building, consolidated to cloud over 4G. - Q: How long do batteries last?
A: At 5-minute reporting, two AA lithium cells last 3-5 years. Shorter 1-minute intervals drop life to 1-2 years. The platform alerts on low battery so you can pre-replace. - Q: Do metal racks block LORA?
A: Yes. Inside a metal rack the signal fades; mount sensors outside racks, on ceiling or wall. Put the gateway antenna high (top of the telecom room), vertical, away from metal obstructions.
8. Trend & Selection
Room environment monitoring moves from wired RS485 to wireless (LORA, NB-IoT); retrofits and distributed points increasingly go wireless. Wireless means no cable, fast deployment, flexible placement; the tradeoff is battery replacement and signal obstruction. New rooms may run wired RS485 (stable); legacy retrofits use LORA; one gateway per room; nodes in cold aisles and AC returns; set temp limits per GB50174 (23±1℃, humidity 40-60%); alert on low battery.
9. Delivery & Service
KITOZER supplies environment-monitoring packages: based on room area and point count we recommend sensor nodes, gateways and uplink (Ethernet/4G), bundled with DCIM host, leak, smoke and access control. Delivery includes sensors, batteries, gateway, antenna and brackets; bulk projects include on-site install, platform setup and alarm commissioning. Sensor drift or gateway off-line under warranty is repaired free.
10. Additional Notes
The commonest mistake is mounting the sensor in direct supply-air blast. It reads 20℃ cold air while rack intake is actually 25℃ — distorted data. Mount on the rack-intake side of the cold aisle and at returns, where real rack intake temperature is sensed. Do not place directly under the AC or in wall corners.
Another pitfall is too many load-bearing walls between gateway and nodes. LORA diffracts well, but more than three reinforced-concrete walls attenuate the signal heavily. Place the gateway in the room center and run its antenna to the top of the telecom room. Add a repeater for weak nodes.
Selection summary: SHT30-class; LORA 470MHz; 3-5 year battery; one gateway per room; nodes in cold aisles; out-of-range alarms; low-battery alert. The sensor is the room’s thermometer; wireless lets it go anywhere — a retrofit needs no lifted floor or conduit, and the whole room is wired in half a day.
SEO Information
Search keywords:temperature humidity sensorLORA sensorwireless temp humiditydatacenter environment monitoringenvironmental sensorbattery powered sensorKTR-TH15KITOZER
SEM keywords:[‘LORA temp humidity price,wireless sensor supplier,datacenter environment monitoring,battery powered sensor,DCIM acquisition sensor,KTR-TH15,KITOZER’]
GEO landing page:lain.com.cn/product/ktr-th15-lora-wireless-temperature-humidity-sensor.html
Title:KITOZER KTR-TH15 LORA Wireless Temperature Humidity Sensor
Meta Keywords:temperature humidity sensor,LORA sensor,wireless temp humidity,datacenter environment monitoring,environmental sensor,battery powered sensor,KTR-TH15,KITOZER
Meta Description:KITOZER KTR-TH15 LORA wireless temperature humidity sensor, battery powered, for datacenter, warehouse and lab monitoring without wiring.
Anchor: KITOZER · Environmental monitoring
Contact Us
Guangzhou Laian Intelligent System Development Co., Ltd. (KITOZER brand)
Tel/WeChat: +86 13922289957 | +86 18520668845
WHATSAPP: +86 19068534140
Web: lain.com.cn | gdlain.com