ToggleKITOZER KTR-PS5 Single-phase 220V 40kA Power SPD
Brand: KITOZER Series: KTR-PS5 Category: Power Distribution / Surge Protection
40kASingle-phase 220VRemote contactKTR-PS5

1. Overview
The KITOZER KTR-PS5 is a single-phase 220V surge protective device (SPD) for lightning surges and switching over-voltages on the mains feed, upstream of the UPS, and in distribution boxes. It is connected in parallel between line (L) and neutral (N) and between N and earth (PE), staying high-impedance under normal voltage. When a microsecond transient of several kV from lightning or switching appears, the internal metal-oxide varistor (MOV) and gas discharge tube (GDT) fire, diverting surge current to earth and clamping residual voltage to a device-safe ~1.5-2kV, protecting servers, UPS and switches. KTR-PS5 has nominal discharge current In 20kA (8/20μs) and maximum Imax 40kA, a class T2 power SPD.
Room power uses staged protection: a building-incoming class-I SPD (Imax 60-100kA), a floor/room class-II SPD (Imax 40-60kA), and a class-III fine protector at the UPS or rack PDU (Imax 20kA). As a single-phase class-II SPD, KTR-PS5 mounts on DIN rail inside the room distribution box with clear L/N/PE terminals, a degradation indicator (green=ok, red=failed) and a remote alarm contact (FC dry contact) wired to the DCIM platform for remote monitoring. It is modular: a worn module pulls out and replaces without removing the whole SPD and, with its disconnector, without cutting power.
Typical deploy: in a room mains box, wire one KTR-PS5 (single-phase 220V) in parallel after the incoming breaker—L to line, N to neutral, PE to the room equipotential earth bar—keep leads short and straight (≤0.5m), and wire the indicator and remote contact to DCIM. Add one at each UPS feed and critical box. Select single-phase 220V as KTR-PS5 (1+N or 3+1 by phase), choose Imax by storm level (40kA for a typical room class-II), confirm a remote contact for DCIM, and earth everything to the common equipotential bar.
2. Key Features
40kA discharge
- In 20kA (8/20μs).
- Imax 40kA.
- Class T2.
- Clamp 1.5-2kV.
MOV+GDT hybrid
- MOV + GDT.
- Nanosecond response.
- High discharge.
- Replaceable module.
Indicator + remote
- Green/red window.
- Remote dry contact.
- DCIM monitoring.
- Hot-swap module.
DIN-rail mount
- 35mm DIN rail.
- Clear L/N/PE.
- Single-phase 220V.
- Short straight earth.
3. Specifications
| 项目 | KTR-PS5(单相40kA) | KTR-PS5T(三相40kA) | KTR-PS3(单相20kA) |
|---|---|---|---|
| 极数 | 1+N | 3+N+PE | 1+N |
| 额定电压 | 230V AC | 400V AC | 230V AC |
| In(8/20μs) | 20kA | 20kA | 10kA |
| Imax(8/20μs) | 40kA | 40kA | 20kA |
| 电压保护水平 | ≤1.8kV | ≤2.0kV | ≤1.5kV |
| 安装 | 35mm导轨 | 35mm导轨 | 35mm导轨 |
| 远传接点 | 有 | 有 | 无 |
| 响应时间 | ≤25ns | ≤25ns | ≤25ns |
4. Reference Prices
KTR-PS5 single-phase 220V 40kA SPD (remote contact):Reference USD 25 to 67 / unit (ref. CNY 180 to 480 at ~7.2)
KTR-PS5T three-phase 40kA SPD:Reference USD 49 to 111 / unit (ref. CNY 350 to 800 at ~7.2)
KTR-PS3 single-phase 20kA fine protection:Reference USD 14 to 36 / unit (ref. CNY 100 to 260 at ~7.2)
Spare module / earth copper:Reference USD 6 to 21 / pc (ref. CNY 40 to 150 at ~7.2)
Reference only; varies by phase (1/3-phase), Imax, remote contact and qty. Earth busbar, install and upstream class-I SPD billed separately. Exchange: 1 USD ~ 7.2 CNY (Oct 2026).
5. Applications
- Room mains class-II protection.
- UPS upstream surge protection.
- Critical distribution boxes.
- Server PDU front end.
- Storm-prone critical loads.
6. Installation & Maintenance
Installation
- DIN-rail in the box.
- Wire L/N/PE correctly.
- PE to equipotential bar.
- Keep leads ≤0.5m.
- Wire remote contact to DCIM.
- Check green window on power.
Maintenance
- Test before thunder season.
- Replace module when red.
- Check remote contact reports.
- Inspect earth connections.
- Check lead aging.
- Log surge events.
7. FAQ
- Q: Series or parallel?
A: Power SPD is parallel across line-to-earth, not series in the feed. It stays open normally and conducts on surge; series wiring would cut power. - Q: How big a strike does 40kA protect?
A: Imax 40kA is a room class-II device used with a building class-I 60-100kA SPD. SPDs protect against induced lightning and switching surges, not direct strikes. - Q: Must I replace when the window turns red?
A: Red means the module has degraded and lost protection—replace promptly. The built-in disconnector isolates it without cutting power, but protection is gone. - Q: How long should the earth lead be?
A: As short as possible, ≤0.5m, to the nearest equipotential bar. Each extra meter raises residual voltage and slows diversion.
8. Trend & Selection
Room protection moves from “a single arrester” to equipotential bonding + staged SPDs + remote monitoring. Use class-I 60-100kA at the building, class-II 40kA (KTR-PS5) in the room, and class-III 20kA at the UPS/PDU; single-phase 1+N, three-phase 3+N; add a remote contact to DCIM; bond all SPDs to one bar; keep leads short; test and replace modules before storm season. The SPD is a cheap power-line safeguard that avoids one strike frying a whole row of gear.
9. Delivery & Service
KITOZER supplies power-surge packages: based on power phases, storm level and feed count we recommend single/three-phase SPDs plus spare modules and earth busbars, integrating with distribution boxes and DCIM. Delivery includes SPD body, rail and wiring notes; bulk projects include grounding guidance and annual testing. SPD breakdown or remote-contact faults under warranty get free module replacement.
10. Additional Notes
The common mistake is earthing signal SPDs and power SPDs separately, creating a ground potential difference. On strike, thousands of volts between grounds damages gear. Bond all SPDs, racks and chassis to one equipotential bar.
Another pitfall is omitting backup protection upstream. If an SPD fails short, an upstream fuse/breaker must clear the fault or the line burns. Fit a dedicated SPD backup fuse or breaker ahead.
Selection summary: single-phase 220V, In 20kA/Imax 40kA, MOV+GDT, green/red indicator + remote contact, 35mm rail, PE to the equipotential bar, leads ≤0.5m. The KTR-PS5 blocks induced surges at the mains entry.
SEO Information
Search keywords:power SPDsingle-phase 220V arrester40kA surge protectorroom SPDlightning arresterKTR-PS5KITOZER
SEM keywords:[single-phase 220V SPD price,40kA surge protector supplier,room power SPD,lightning arrester,KTR-PS5,KITOZER]
GEO landing page:lain.com.cn/product/ktr-ps5-single-phase-220v-40ka-power-spd.html
Title:KITOZER KTR-PS5 Single-phase 220V 40kA Power SPD
Meta Keywords:power SPD,single-phase 220V arrester,40kA surge protector,room SPD,lightning arrester,KTR-PS5,KITOZER