Table of Contents
ToggleKITOZER KTR-OS33 Vertical Dual-in Dual-out Oil Separator
Brand: KITOZER Series: KTR-OS33 Category: Data Center Engineering / Refrigeration
Dual in/outCyclone96% eff.KTR-OS33
1. Overview
The KITOZER KTR-OS33 is a vertical dual-inlet dual-outlet precision oil separator built for refrigeration systems with two parallel compressors or two discharge loops. The vertical shell is mounted upright; two discharge inlets on top receive gas from two parallel compressors. Inside, cyclone guide vanes spin the high-pressure gas tangentially along the wall; oil droplets are flung outward by centrifugal force, slide down the wall and collect in the bottom sump. Two symmetric clean-gas outlets at the upper shell feed the two condensers (or a common header). Dual inlets keep each compressor’s oil return independent, preventing one oil-heavy compressor from flooding or starving the other.
Compared with a plain single-inlet vertical separator, the dual-inlet KTR-OS33 suits the common datacenter precision-AC architecture of ‘two parallel compressors + inverter’. The two machines run at different loads—one fixed-speed at full load, the other inverter at light load—so discharge pulsing differs widely. Dual inlets guide each stream independently for steady 96%+ separation; the bottom sump returns oil through one shared 6mm capillary to the crankcases by pressure difference. The shell is powder-coated, with an internal mist eliminator that catches fine oil droplets; a sight glass on the lower shell lets staff check oil color and level.
Typical install: a 120kW dual-compressor precision AC uses one KTR-OS33 in the vertical discharge run—two inlets to compressor A and B (Φ35/Φ42), two outlets to condensers A and B. Anchor the shell upright with clamps within 5° of plumb; run a 6mm return capillary from the bottom port to the crankcase. It fits R22, R410A, R407C, R134a and some R32 systems across 10-30 HP dual-compressor sets. Size the shell by total displacement of both machines, ports by pipe diameter, and seals by refrigerant.
2. Key Features
Dual in/out
- Two discharge inlets.
- Two clean outlets.
- No cross-over.
- For parallel sets.
Cyclone separation
- Cyclone vanes.
- Tangential inlet.
- Centrifugal+gravity.
- 96%+ separation.
Mist eliminator
- Catches fine mist.
- Cuts oil carryover.
- Washable.
- Longer system life.
Sight glass return
- Lower sight glass.
- 6mm return capillary.
- Shared return.
- Coated shell.
3. Specifications
| 项目 | KTR-OS33(双进双出) | KTR-OS20(单进单出) | KTR-OS10(经济型) |
|---|---|---|---|
| 进出口 | 双进双出 | 单进单出 | 单进单出 |
| 适用制冷量 | 10至30匹双机 | 2至10匹 | 1至5匹 |
| 进口管径 | Φ35/Φ42 | Φ18/Φ22 | Φ12/Φ16 |
| 出口管径 | Φ35/Φ42 | Φ18/Φ22 | Φ12/Φ16 |
| 除油雾网 | 有(可拆洗) | 无 | 无 |
| 视油镜 | 有(下部) | 有 | 无 |
| 适用冷媒 | R22/410A/407C/134a | R22/410A/134a | R22/134a |
| 安装方式 | 竖直抱箍 | 竖直抱箍 | 竖直 |
4. Reference Prices
KTR-OS33 vertical dual-in dual-out separator (10-30 HP set):Reference USD 125 to 306 / unit (ref. CNY 900 to 2200 at ~7.2)
KTR-OS20 single-in single-out standard (2-10 HP):Reference USD 35 to 83 / unit (ref. CNY 250 to 600 at ~7.2)
KTR-OS10 economy (no mist net, 1-5 HP):Reference USD 17 to 49 / unit (ref. CNY 120 to 350 at ~7.2)
Spare mist net / capillary / check valve:Reference USD 4 to 21 / set (ref. CNY 30 to 150 at ~7.2)
Reference only; varies by port size, refrigerant, connection type and qty. Spare mist nets, capillary and check valves billed separately. Exchange: 1 USD ~ 7.2 CNY (Oct 2026).
5. Applications
- Dual-compressor precision AC.
- Inverter+fixed-speed loops.
- Rooftop close-control units.
- Parallel VRF return.
- Chillers/process cooling.
6. Installation & Maintenance
Installation
- Anchor upright within 5°.
- Connect inlets to A/B discharge.
- Connect outlets to A/B condensers.
- Run return capillary to crankcase.
- Nitrogen-purge while brazing.
- Evacuate, pressure-test, charge.
Maintenance
- Watch oil via sight glass.
- Clean mist net if oil darkens.
- Keep return capillary clear.
- Check shell for leaks.
- Log oil temp/level.
- Inspect vanes every 2yr.
7. FAQ
- Q: Dual or single inlet?
A: Two parallel compressors with independent discharge lines—choose dual-in dual-out (KTR-OS33) to avoid pulsing cross-talk. A single machine uses single-in. Using single-in on a dual loop mixes the two streams. - Q: Can two outlets share a header?
A: Yes, but keep two outlets and join them after a short run per side to reduce cross-flow. Merging straight into one pipe unbalances the two condensers. - Q: Is a full sight glass normal?
A: A small pool is normal. If it stays full while the crankcase starves, the return capillary is blocked—clear or replace it. - Q: How often to clean the mist net?
A: Typically every 1-2 years at service. Clean earlier if oil blackens or carryover rises; air-dry before refitting.
8. Trend & Selection
Precision AC increasingly uses dual-compressor parallel with inverter; at part load the inverter runs low and returns little oil but carries lots of it. A dual-in dual-out separator lets each stream separate and exit independently. Choose dual-in for parallel sets; size the shell with 20% headroom over total displacement; use a mist net to cut carryover; add a check valve on the return capillary; rely on the sight glass for inspection.
9. Delivery & Service
KITOZER supplies oil-return kits: based on dual-compressor model, refrigerant and pipe size we recommend the KTR-OS33 plus spare mist nets, capillary and check valves, bundled with precision-AC refrigeration accessories. Delivery includes body, mist net, fittings and manual; bulk projects get brazing and install guidance. Shell leaks or failed vanes under warranty are replaced free.
10. Additional Notes
The common mistake is swapping the two inlets. The shell marks A/B; reversing them makes the two streams collide inside and cuts separation. Check drawings against marks.
Another pitfall is tilting the shell beyond 5°. Oil droplets then slide straight toward the outlet instead of settling into the sump, raising carryover. Anchor upright and verify with a level.
Selection summary: vertical dual-in dual-out, cyclone 96%+ separation, built-in mist net, 10-30 HP dual sets, lower sight glass, check valve on return. The KTR-OS33 keeps each compressor’s oil on its own side.
Contact Us
Guangzhou Laian Intelligent System Development Co., Ltd. (KITOZER brand)
Tel/WeChat: +86 13922289957 | +86 18520668845
WHATSAPP: +86 19068534140
Web: lain.com.cn | gdlain.com