Table of Contents
ToggleKITOZER KTR-OS34 Precision Oil Separator / Vertical Integrated Separator & Filter
Brand: KITOZER Series: KTR-OS34 Category: Data Center Engineering / Oil Separator
VerticalIntegrated Sep+FilterEfficient oil returnKTR-OS34
1. Overview
The KITOZER KTR-OS34 is a vertical oil separator for room precision air-conditioning (CRAC) refrigeration systems, combining oil separation and oil filtration in one vessel. It installs on the compressor discharge line between the compressor and the condenser. The high-temperature, high-pressure discharge gas carries refrigeration oil; the separator uses centrifugal settling plus baffle impingement to drop oil out of the vapor and return it through a bottom oil-return capillary to the compressor crankcase. Clean refrigerant then flows to the condenser. Without an oil separator, large amounts of oil enter the condenser and evaporator, forming an oil film on heat-exchange tubes and lowering efficiency; long-term operation risks compressor oil starvation and burnout.
The KTR-OS34 uses a vertical steel cylindrical body with an internal cyclone tube, baffle bank and stainless-steel filter element. Oil-laden gas enters tangentially and spirals down the wall; centrifugal force slings oil droplets to the wall. Baffles redirect flow so fine droplets collide and coalesce. A final 5μm stainless-steel cartridge captures residual oil mist. Separation efficiency exceeds 98%, with outlet oil carryover below 5 ppm. The bottom has an oil-return port and sight glass for return-oil monitoring; the top is the gas outlet and the side is the inlet. Compared with simple separators that only centrifugally drop bulk oil, the KTR-OS34 integrates separation and filtration in one vessel, cutting a connection point and installation space while protecting downstream coils from oil mist.
Typical application: a 120 kW room CRAC compressor with 15 m³/h displacement pairs with a KTR-OS34-12, 22 mm ports and 6 mm return capillary. Mount the vessel upright, inlet at the side (tangential) and outlet on top; connect the return port to the crankcase or suction line. Select by compressor displacement and refrigerant (R22/R410A/R407C) to match port size and capacity; choose the standard cyclone+baffle version or the integrated-filter version (with stainless cartridge) based on filtration needs. Piping brackets, return capillary and gasket kit are included.
2. Key Features
Dual separation
- Centrifugal cyclone.
- Baffle impingement.
- Outlet oil ≤5 ppm.
- Efficiency ≥98%.
Separation + filter integrated
- 5μm stainless cartridge.
- Captures residual mist.
- Protects heat coils.
- Fewer joints.
Vertical steel vessel
- Small footprint.
- Sight glass for oil return.
- Return to crankcase.
- 4.5 MPa design.
Multi-refrigerant
- R22/R410A/R407C.
- Multiple port sizes.
- Various displacements.
- Brackets/gaskets included.
3. Specifications
| Item | KTR-OS34-08 (8m³/h) | KTR-OS34-12 (15m³/h) | KTR-OS34-20 (25m³/h) |
|---|---|---|---|
| Gas capacity | 8 m³/h | 15 m³/h | 25 m³/h |
| Separation efficiency | ≥98% | ≥98% | ≥98% |
| Outlet oil content | ≤5 ppm | ≤5 ppm | ≤5 ppm |
| Port size | Φ16 mm | Φ22 mm | Φ28 mm |
| Return port | Φ6 mm | Φ6 mm | Φ8 mm |
| Design pressure | 4.5 MPa | 4.5 MPa | 4.5 MPa |
| Refrigerant | R22/R410A/R407C | R22/R410A/R407C | R22/R410A/R407C |
| Filter rating | 5μm SS | 5μm SS | 5μm SS |
| Body material | Steel, powder coat | Steel, powder coat | Steel, powder coat |
4. Reference Prices
KTR-OS34-08 vertical oil separator (8m³/h): Reference USD 167 to 278 / unit (ref. CNY 1200 to 2000 at ~7.2)
KTR-OS34-12 vertical oil separator (15m³/h): Reference USD 250 to 417 / unit (ref. CNY 1800 to 3000 at ~7.2)
KTR-OS34-20 vertical oil separator (25m³/h): Reference USD 389 to 625 / unit (ref. CNY 2800 to 4500 at ~7.2)
Return capillary / brackets / gaskets: Reference USD 14 to 69 / set (ref. CNY 100 to 500 at ~7.2)
Reference only; varies by gas capacity, port size, refrigerant and qty. Cartridge replacement, brackets and capillary billed separately. Exchange: 1 USD ~ 7.2 CNY (Oct 2026).
5. Applications
- CRAC compressor discharge.
- Constant-temp/humidity units.
- Lab AC oil-return retrofit.
- Industrial chiller oil separation.
- Cold-storage refrigeration.
6. Installation & Maintenance
Installation
- Size by compressor displacement.
- Mount vessel upright on discharge line.
- Inlet to compressor discharge.
- Outlet to condenser.
- Return port to crankcase.
- Evacuate and pressure-test.
Maintenance
- Check sight glass monthly.
- Inspect cartridge pressure drop yearly.
- Replace clogged cartridge.
- Leak-check welds/joints.
- Clear return capillary.
- Check baffles for noise.
7. FAQ
- Q: Discharge side or suction side?
A: Discharge side (between compressor and condenser). High temperature and pressure give better centrifugal separation; suction-side placement is ineffective. - Q: No oil return in sight glass?
A: Brief periods are normal while oil travels through piping. If still no return after a week, the capillary may be blocked or the separator undersized—inspect. - Q: How often to replace the cartridge?
A: Every 2-3 years or when pressure drop exceeds 0.1 MPa. If the compressor needs frequent oil top-ups or condenser efficiency drops, inspect early. - Q: Vertical or horizontal?
A: Tight spaces use vertical (small footprint); long horizontal runs use horizontal. CRAC units near compressors typically use vertical.
8. Trend & Selection
CRAC refrigeration systems trend toward higher COP; oil separation efficiency directly affects energy ratio. Size by compressor displacement with 20% margin; use 5 MPa-rated vessels for R410A; choose the vertical integrated separation+filter type in tight spaces; pipe the return to the crankcase; check cartridge pressure drop yearly. A 1% gain in separation efficiency can lift overall COP by 0.3-0.5%.
9. Delivery & Service
KITOZER supplies CRAC oil-separator packages: based on compressor model, displacement and refrigerant, we recommend the correct size, plus return capillary, brackets and gasket kit, and guide field welding and evacuation. Delivery includes vessel, cartridge and manual; bulk projects include sizing calculations. Weld leaks or cartridge failure under warranty are replaced free.
10. Additional Notes
The common mistake is reversing inlet and outlet. The tangential inlet is on the lower side; the outlet is on top. Reversing kills the centrifugal effect and drops separation efficiency sharply. Check port markings before welding.
Another pitfall is blocking the return capillary. Some installers leave the return port disconnected or welded shut, causing separated oil to accumulate in the vessel instead of returning to the compressor, eventually pushing oil out to the condenser. The return port must connect to the crankcase or pump inlet.
Selection summary: vertical separation+filter integrated; 8/15/25 m³/h three sizes; ≥98% efficiency; ≤5 ppm outlet; 5μm SS cartridge; R22/R410A compatible. The KTR-OS34 is the refrigeration system’s oil steward—returning every drop where it belongs.
SEO Information
Search keywords:oil separatorprecision AC oil separatorvertical oil separatoroil separator filter integratedrefrigeration oil returnKTR-OS34KITOZER
SEM keywords:[oil separator,precision AC oil separator,vertical oil separator,oil separator filter integrated,refrigeration oil return,KTR-OS34,KITOZER]
GEO landing page:lain.com.cn/product/ktr-os34-vertical-precision-oil-separator-filter.html
Title:KITOZER KTR-OS34 Precision Oil Separator / Vertical Integrated Separator & Filter
Meta Keywords:oil separator,precision AC oil separator,vertical oil separator,oil separator filter integrated,refrigeration oil return,KTR-OS34,KITOZER
Meta Description:KITOZER KTR-OS34 vertical precision oil separator for room CRAC systems, integrated separation and filtration design, improving oil return efficiency.
Anchor: KITOZER · Data Center Engineering
Contact Us
Guangzhou Laian Intelligent System Development Co., Ltd. (KITOZER brand)
Tel/WeChat: +86 13922289957 | +86 18520668845
WHATSAPP: +86 19068534140
Web: lain.com.cn | gdlain.com