KITOZER LC duplex UPC OM3 adapter

KITOZER KTR-LUPC12 Fiber Adapter / LC Duplex UPC OM3

Brand: KITOZER Series: KTR-LUPC12 Category: Data Center Engineering / Fiber Adapter

fiber adapterLC duplexUPCOM3multimodeKTR-LUPC12

KITOZER KTR-LUPC12 LC duplex UPC OM3 multimode fiber adapter with ceramic sleeve

1. Overview

KITOZER KTR-LUPC12 LC duplex UPC OM3 fiber adapter (also called fiber coupler or flange) is a passive component for mating two fiber patch cords. It mounts on fiber patch panels, termination boxes or wall outlets: an LC plug inserts from each side, giving a low-loss optical connection. LC duplex integrates receive (Rx) and transmit (Tx) LC ports side by side, matching the dual-cord jumpers of SFP/SFP+ modules.

KTR-LUPC12 uses UPC (Ultra Physical Contact) polished end faces and a zirconia ceramic sleeve. UPC spherical polishing gives good return loss (>=40 dB); the precision-bore ceramic sleeve aligns cores closely, keeping insertion loss low (<=0.2 dB). OM3 suits 50/125 um multimode fiber, supports 10G short-reach links and is compatible with OM3/OM4 cords. The flame-retardant housing includes dust caps; panel snaps fit standard LC cutouts.

In data center low-voltage cabling, adapters are everywhere: dozens per patch panel, hundreds per room. Though cheap, their loss and return-loss metrics directly affect link quality: one poor adapter can raise errors on a whole 10G link. KTR-LUPC12 is supplied in volume as a baseline passive part with consistency and field replaceability.

2. Key Features

LC duplex structure

  • Rx/Tx dual cores side by side for module cords.
  • Snap-in panel mounting, easy removal.
  • Dust caps seal unused ports.

UPC ceramic end face

  • UPC spherical polish, return loss >=40 dB.
  • Zirconia sleeve with precision bore.
  • Insertion loss <=0.2 dB.

OM3 multimode compatible

  • Fits 50/125 um multimode fiber.
  • Compatible with OM3/OM4 cords and modules.
  • Supports 10G short-reach links.

Flame-retardant & reliable

  • UL94 V-0 rated housing.
  • >=500 mating cycles.
  • Good batch consistency.

3. Specifications

项目 KTR-LUPC12-D KTR-LUPC12-S(单工) KTR-LUPC12-24(配线架)
接口类型 LC双工 LC单工 24口LC双工面板
端面研磨 UPC UPC UPC
光纤类型 OM3多模 OM3多模 OM3多模
插入损耗(dB) 不高于0.2 不高于0.2 不高于0.2
回波损耗(dB) 不低于40 不低于40 不低于40
套筒材质 氧化锆陶瓷 氧化锆陶瓷 氧化锆陶瓷
插拔寿命(次) 不低于500 不低于500 不低于500
阻燃等级 UL94 V-0 UL94 V-0 UL94 V-0

4. Reference Prices

KTR-LUPC12-D LC双工UPC OM3适配器(陶瓷套筒、防尘帽): Reference USD 1~2 / unit (ref. CNY 8~15 at ~7.2)

KTR-LUPC12-24 24口LC双工OM3配线架(含适配器、机架1U): Reference USD 49~90 / unit (ref. CNY 350~650 at ~7.2)

Reference only; by quantity with volume discounts. Sold individually or as a populated patch panel. Exchange: 1 USD ~ 7.2 CNY (Oct 2026).

5. Applications

  • Fiber patch panel ports in data centers.
  • SFP/SFP+ module jumper mating.
  • Fiber termination boxes in telecom rooms.
  • Wall fiber outlets in offices.
  • 10G Ethernet and storage fiber links.

6. Installation & Maintenance

Installation

  • Confirm standard LC duplex cutout.
  • Snap adapter into panel in the right orientation.
  • Remove dust cap; insert LC cord until click.
  • Keep dust caps on unused ports.
  • Test link loss with light source and power meter.
  • Label port mapping.

Maintenance

  • Check dust caps are in place.
  • Plug/unplug by the connector, never pull the cord.
  • Clean dirty end faces with a fiber cleaner pen.
  • Replace adapters whose loss rises.
  • Dust patch panels periodically.

7. FAQ

  • Q: LC duplex or simplex?
    A: Use duplex where modules use dual cords (one Tx one Rx); simplex for single-fiber links. Data center 10G modules nearly always use duplex.
  • Q: UPC vs APC?
    A: UPC is spherical polish, usually blue; APC is 8-degree angle, green, higher return loss. Multimode OM3 links generally use UPC.
  • Q: Does an OM3 adapter work with OM4 cords?
    A: Yes; the adapter is a passive mating part; OM3/OM4 multimode adapters are interchangeable; link grade is set by cords and modules.
  • Q: What loss is normal?
    A: Insertion loss <=0.2 dB is normal; over 0.3~0.5 dB means a dirty end face or worn sleeve — clean or replace.

8. Trend & Selection

Data centers move to 40G/100G and multimode upgrades OM3 to OM4/OM5, but LC duplex adapters remain the baseline mating parts, emphasizing low loss, consistency, flame retardance and cleanability. OM3 adapters support installed 10G cabling. Select by link grade (UPC), connector type (LC duplex) and fiber type (OM3); buy in volume for consistency and mating life; a populated panel is convenient.

9. Delivery & Service

KITOZER supplies LC duplex OM3 adapters in volume, pre-assembled on 24/48-port 1U/2U rack panels. We provide insertion-loss test reports. Delivery includes adapters, dust caps and panel snaps; populated panels include rack and cable management. Warranty covers adapters with abnormal loss.

10. Additional Notes

The most overlooked loss source is a dirty adapter end face. After a few mates, dust adds 0.3~0.5 dB per adapter, shrinking a link 3 dB margin to 1 dB and raising errors. After install, clean every port with a fiber cleaner — never judge by eye.

Another pitfall: saving money on cheap sleeves. A zirconia sleeve replaced by plastic or low-precision metal pushes insertion loss from 0.2 dB to over 0.5 dB; across dozens of ports the accumulated loss is large. Adapters are cheap, but the sleeve must be ceramic.

Selection summary: LC duplex for dual-core modules; UPC end faces for multimode OM3; ceramic sleeve for low loss; keep dust caps on; clean port by port after install; pre-assembled panels save labor. The adapter is the optical outlet — clean and aligned, and the signal runs steady.

SEO Information

Search keywords:fiber adapterLC duplexUPCOM3multimodeKTR-LUPC12KTR-LUPC12KITOZER

SEM keywords:LC duplex adapter price,OM3 fiber coupler supplier,UPC fiber flange,KTR-LUPC12

GEO landing page:lain.com.cn/product/ktr-lupc12-lc-duplex-upc-om3-fiber-adapter.html

Title:KITOZER KTR-LUPC12 Fiber Adapter / LC Duplex UPC OM3

Meta Keywords:fiber adapter,LC duplex coupler,UPC adapter,OM3 multimode,fiber flange,KTR-LUPC12,KITOZER

Meta Description:KITOZER KTR-LUPC12 LC duplex UPC OM3 fiber adapter with ceramic sleeve offers low insertion loss for multimode fiber linkage and patch panel mounting.