ToggleKITOZER KTR-TH19 Environment Sensor / Wall-mount Temp & Humidity with Display
Brand: KITOZER Series: KTR-TH19 Category: Environmental Monitoring / Temp & Humidity Sensor
temp humidity sensorwall-mountwith displayRS485room environmentKTR-TH19

1. Overview
KITOZER KTR-TH19 is a wall-mount temperature/humidity sensor: the front-end environmental probe of a data center DCIM system. Mounted on walls or rack posts, it measures ambient temperature and relative humidity, shows them on a local LCD and uploads via RS485 (Modbus-RTU) to the DCIM host. On out-of-range T/H, the sensor plus platform alarms staff: high room temperature causes server throttling and overheating; too-dry air causes ESD, too-wet causes condensation.
KTR-TH19 uses a digital T/H chip with accuracy +/-0.5 C and +/-3 %RH, fast response and low drift. The wall case has an LCD for on-site reading; RS485 two-wire daisy-chains multiple sensors with DIP-switch addressing. Powered DC 12~24 V, used with the DCIM host or a POE splitter. It holds T/H thresholds for local beep or upload alarms.
In data center environment monitoring, T/H sensors are the most basic and numerous probes: every cold aisle, rack side, UPS room and battery room needs one. Though cheap, point density and accuracy determine monitoring effectiveness. KTR-TH19 is a standard wall T/H sensor supplied in volume for DCIM systems.
2. Key Features
T/H acquisition
- +/-0.5 C, +/-3 %RH.
- Digital chip, fast, low drift.
- Real-time ambient T/H.
Local display
- Wall LCD for on-site reading.
- Temperature and humidity on one screen.
- Wall-mount case, neat install.
RS485 network
- RS485 Modbus-RTU output.
- Two-wire daisy-chain, multi-drop.
- DIP-switch addressing.
Over-limit alarm
- Adjustable T/H thresholds.
- Local beep + upload alarm.
- DC 12~24 V power.
3. Specifications
| 项目 | KTR-TH19-D(带屏) | KTR-TH19-N(无屏) | KTR-TH19-P(POE款) |
|---|---|---|---|
| 温度范围 | -20~60℃ | -20~60℃ | -20~60℃ |
| 湿度范围 | 0~100%RH | 0~100%RH | 0~100%RH |
| 温度精度 | ±0.5℃ | ±0.5℃ | ±0.5℃ |
| 湿度精度 | ±3%RH | ±3%RH | ±3%RH |
| 显示 | LCD屏 | 无 | LCD屏 |
| 通信 | RS485 | RS485 | RS485+POE |
| 供电 | DC12~24V | DC12~24V | POE/DC |
4. Reference Prices
KTR-TH19-D 壁挂温湿度传感器(LCD屏、RS485、超限报警): Reference USD 25~53 / unit (ref. CNY 180~380 at ~7.2)
KTR-TH19-N/P 无屏/POE款温湿度传感器(批量配套动环): Reference USD 17~44 / unit (ref. CNY 120~320 at ~7.2)
Reference only; by display, comm and quantity; DCIM host and wiring excluded. Exchange: 1 USD ~ 7.2 CNY (Oct 2026).
5. Applications
- Cold aisle and rack-side T/H monitoring.
- UPS and battery room environment.
- Warehouse and archive T/H logging.
- Lab and cleanroom T/H acquisition.
- DCIM system front-end points.
6. Installation & Maintenance
Installation
- Mount away from outlets and direct heat.
- Choose representative spots (middle of cold aisle).
- Daisy-chain RS485; match A/B polarity.
- Set DIP address to the point table.
- Power DC 12~24 V or POE.
- Verify platform value against on-site temperature.
Maintenance
- Periodically compare with a standard thermometer.
- Wipe probe dust with soft cloth, no solvents.
- On RS485 drop, check wiring.
- Protect battery-room sensors from acid mist.
- Calibrate accuracy yearly.
7. FAQ
- Q: How many T/H points per room?
A: By aisle area and rack density: generally one mid-aisle and one at return air; densify on high-density rack sides. - Q: How many sensors on one RS485?
A: Up to ~32 per RS485 bus (more with repeaters), planned by DCIM host ports and addressing. - Q: Sensor reads wrong?
A: First check mounting away from direct AC airflow; then compare with a standard thermometer; calibrate or replace if off. - Q: What thresholds?
A: Rooms generally alarm at 18~27 C and 40~60 %RH per the room design standard.
8. Trend & Selection
DCIM evolves from single-point to dense, visual monitoring; T/H sensors with displays, RS485 networking and threshold alarms are standard, linked to CRAH for temperature control. Select count by point density; choose display models where staff read locally; RS485 lowers cost; thresholds link to AC; calibrate regularly.
9. Delivery & Service
KITOZER supplies wall T/H sensors in volume, configured by site map (count and address). We provide a Modbus point table. Delivery includes sensor, wall bracket and terminals. Warranty covers abnormal accuracy calibration/replacement.
10. Additional Notes
The most common wrong mounting is directly in front of an AC outlet. The probe reads the chilled airflow, not the real rack intake, so the platform shows 22 C while racks run at 30 C. Mount mid-aisle at rack intake height.
Another pitfall: reversed RS485 A/B polarity. The sensor drops offline and wastes half a day; daisy-chain polarity must be uniform, with a 120 ohm terminator at the end.
Selection summary: place points by cold aisle; avoid outlets and heat; display models for local reading; uniform RS485 polarity; thresholds link to AC; yearly calibration. The T/H sensor is the room thermometer: accurate temperature lets the AC tune correctly.
SEO Information
Search keywords:temp humidity sensorwall-mountwith displayRS485room environmentKTR-TH19KTR-TH19KITOZER
SEM keywords:temp humidity sensor price,wall-mount TH transmitter supplier,room environment monitoring,KTR-TH19
GEO landing page:lain.com.cn/product/ktr-th19-wall-mount-temp-humidity-sensor-display.html
Title:KITOZER KTR-TH19 Environment Sensor / Wall-mount Temp & Humidity with Display
Meta Keywords:temperature humidity sensor,wall-mount TH,room environment monitoring,RS485 TH transmitter,KTR-TH19,KITOZER
Meta Description:KITOZER KTR-TH19 wall-mount temperature/humidity sensor with LCD and RS485 output for room and warehouse monitoring and over-limit alarms.
Anchor: KITOZER official · Data center & low-voltage equipment
Contact Us
KITOZER brand (professional data center & low-voltage equipment supplier)
Tel/WeChat: +86 13922289957 | +86 18520668845
WHATSAPP: +86 19068534140
Web: lain.com.cn | gdlain.com