KITOZER
KITOZER

KITOZER 2V 300Ah VRLA battery

KITOZER KTR-B3300D Battery / 2V300Ah Deep-Cycle VRLA

Brand: KITOZER Series: KTR-B3300D Category: Power Distribution / UPS Battery

battery2V300Ahdeep cycleVRLAKTR-B3300D

1. Overview

KITOZER KTR-B3300D is a 2V 300Ah deep-cycle VRLA battery used as energy storage in data center UPS and DC panels. On mains failure, the battery bank feeds loads through the inverter or DC bus so servers and network devices stay up. 2V cells are series-connected to form the DC bus (e.g. 48 cells for 96V, 104 cells for 208V), offering high capacity and long life for medium-to-large UPS backup.

KTR-B3300D is a valve-regulated lead-acid (VRLA) battery with AGM absorbed-glass-mat separators; electrolyte is held in the mat, no free acid, mountable in any orientation. Deep-cycle design withstands deep discharge and recharge; design float life 12 years at 25℃, float voltage 2.27 V/cell, equalize 2.35 V. Terminals are tin-plated copper with inter-cell links supplied. Housing is flame-retardant ABS.

In data center power distribution, the battery bank is the heart of backup power. A failed battery causes the UPS to fail to transfer on outage, dropping the load. Banks need periodic charge/discharge testing, internal-resistance checks and temperature control. KTR-B3300D is a 2V high-capacity deep-cycle cell supplied in volume for medium-to-large UPS and DC panels.

2. Key Features

2V high-capacity cell

  • Rated 2V 300Ah (C10).
  • Series strings form the DC bus.
  • Tin-plated copper terminals, low resistance.

Deep-cycle design

  • AGM absorbed separator.
  • Withstands deep discharge and recharge.
  • Cycle life ≥1200 (50% DOD).

Sealed VRLA

  • Valve-regulated, no free acid.
  • Mountable any orientation.
  • Flame-retardant ABS case.

Long life

  • Design float life 12 yr (25℃).
  • Float 2.27 V/cell.
  • Equalize 2.35 V/cell.

3. Specifications

Item KTR-B3300D-2V300
Rated voltage (V) 2
Rated capacity (C10, Ah) 300
Design life (25℃, yr) 12
Float voltage (V/cell) 2.27~2.30
Equalize voltage (V/cell) 2.35
Internal resistance (mΩ) ~0.4
Cycle life (50%DOD, cycles) ≥1200
Working temp (℃) -15~50
Weight (kg) ~19

4. Reference Prices

KTR-B3300D-2V300 single 2V300Ah deep-cycle VRLA cell (AGM, 12-yr design life): Reference USD 94~128 / pc (ref. CNY 680~920 at ~7.2)

Full bank (48/104-cell DC string): Reference USD 4,583~13,333 / bank (priced by cell count and links)

Reference only; by Ah, cell count, links and rack. UPS and installation excluded. Exchange: 1 USD ~ 7.2 CNY (Oct 2026).

5. Applications

  • Medium/large UPS DC-bus storage.
  • Substation DC panel backup.
  • Data center backup banks.
  • Telecom sites and PV storage.
  • Whole-bank replacement.

6. Installation & Maintenance

Installation

  • Place rack with ventilation at 20~25℃.
  • Set cells on rack in series order.
  • Series-connect links by polarity; torque terminals.
  • Connect end cells to UPS DC bus.
  • Verify total and per-cell voltage.
  • Close battery breaker; float-charge.
  • Charge 24~48 h before commissioning.

Maintenance

  • Monthly float and per-cell voltage.
  • Quarterly internal resistance; mark laggards.
  • Yearly capacity discharge test.
  • Keep room at ~25℃.
  • Check links for looseness/corrosion.
  • Plan whole-bank replacement after 3~5 yr.

7. FAQ

  • Q: 2V vs 12V cells?
    A: 2V cells offer flexible series strings and high capacity for large long-life backup; 12V blocks suit small UPS.
  • Q: How long do they last?
    A: Design float life 12 yr at 25℃; real life starts fading after 3~5 yr; every 10℃ halves life.
  • Q: Why replace the whole bank?
    A: A series bank is limited by its weakest cell; replace the same batch together — do not mix old and new.
  • Q: Why is battery-room temperature critical?
    A: VRLA is temperature-sensitive; heat accelerates water loss and thermal runaway; hold 25℃.

8. Trend & Selection

Data center backup evolves from lead-acid to lithium, but VRLA still dominates medium/large UPS, trending toward high-rate, long-life and built-in BMS monitoring. Size cell count by DC bus voltage, capacity by backup time, choose deep-cycle for frequent discharge, control room temperature, and include internal-resistance monitoring.

9. Delivery & Service

KITOZER selects batteries by UPS DC bus voltage, backup time and discharge rate, configuring 2V cell count and capacity. We provide a bank wiring diagram and rack layout. Delivery includes cells, links and manual. Warranty covers installation guidance and laggard-cell detection.

10. Additional Notes

The common pitfall is sizing by capacity but ignoring temperature. A battery room without air conditioning at 35℃ in summer accelerates water loss and bulges cells within years. Keep the room at 25℃ — temperature is the number-one killer of battery life.

Another pitfall is replacing only the bad cell. In a series string, swapping one laggard for a mismatched new cell soon drags the new one down. Replace the whole bank from the same batch; never mix old and new.

Selection summary: cell count by DC voltage; capacity by backup time; deep-cycle for frequent discharge; control room temperature; replace whole batches. The battery is the UPS’s granary — charged up, outages stay calm.

SEO Information

Search keywords:battery2V300Ahdeep cycleVRLAKTR-B3300DKITOZER

SEM keywords:2V300Ah battery price,deep cycle VRLA supplier,UPS DC panel battery,KTR-B3300D

GEO landing page:lain.com.cn/product/ktr-b3300d-2v300ah-deep-cycle-vrla-battery.html

Title:KITOZER KTR-B3300D Battery / 2V300Ah Deep-Cycle VRLA

Meta Keywords:battery,2V300Ah battery,deep cycle VRLA,UPS battery,data center DC panel,KTR-B3300D,KITOZER

Meta Description:KITOZER KTR-B3300D 2V300Ah deep-cycle VRLA AGM battery, 12-year design life, for UPS and DC panel backup.