1. Overview
KITOZER KTR-B5500D is a 2V500Ah deep-cycle VRLA cell used as the energy storage unit for large UPS systems, DC operating panels and telecom/data center backup. When mains fail, the battery bank inverts DC to AC via the UPS to power the room, buying time for generator start or safe shutdown. KTR-B5500D is a 2V cell (not a 12V block): many cells in series form a high-voltage bank (e.g. DC384V, DC480V) at 500 Ah, suiting medium-to-large backup. It is valve-regulated sealed (VRLA) with electrolyte absorbed in AGM glass-matter: leak-free, maintenance-free, deep-cycle rated for repeated charge/discharge.
Compared with 12V blocks, 2V cells build high-voltage large-capacity banks in series: large per-cell capacity and flexible grouping, the mainstream for data center large UPS. Each cell is 2V, 500 Ah, with copper terminals carrying connector bars, a flame-retardant ABS case and a relief valve. Design float life can reach 10~15 years at 25 C (long-life type). Deep-cycle means it tolerates deeper discharge for frequent backup.
In data center power, the battery bank is the UPS pantry: a great UPS with bad batteries still drops the room on an outage. Battery life depends strongly on temperature, depth of discharge and charging regime; life is long at 25 C and shortens in heat. KTR-B5500D is the key large backup storage paired with UPS systems.
2. Key Features
2V500Ah large capacity
- 2V cell, 500 Ah.
- Series strings form high-voltage banks.
- Suits medium/large UPS backup.
Deep-cycle design
- Tolerates repeated charge/discharge.
- Good recovery after deep discharge.
- Suits frequent backup.
VRLA sealed
- Valve-regulated sealed, leak-free.
- AGM absorbs electrolyte, no acid mist.
- Maintenance-free, no topping.
Safe long life
- Flame-retardant ABS case.
- Relief valve vents overpressure.
- 10~15 year float life at 25 C.
3. Specifications
| 项目 | KTR-B5500D | KTR-B5300D(300Ah) | KTR-B5200D(200Ah) |
|---|---|---|---|
| 额定电压 | 2V | 2V | 2V |
| 额定容量 | 500Ah | 300Ah | 200Ah |
| 设计浮充寿命 | 10~15年 | 10~12年 | 8~10年 |
| 充电电压 | 2.25~2.30V | 2.25~2.30V | 2.25~2.30V |
| 端子 | 铜芯M10 | 铜芯M8 | 铜芯M8 |
| 重量(kg) | 约31 | 约18 | 约12 |
| 应用 | 大容量UPS/直流屏 | 中容量UPS | 小容量/直流屏 |
4. Reference Prices
KTR-B5500D 2V500Ah深循环VRLA单体(长寿命、阀控密封、阻燃壳): Reference USD 136~229 / unit (ref. CNY 980~1,650 at ~7.2)
KTR-B5300D 2V300Ah VRLA单体(中容量配套): Reference USD 86~146 / unit (ref. CNY 620~1,050 at ~7.2)
Reference only; by capacity and quantity; battery cabinet, connector bars and installation excluded. Exchange: 1 USD ~ 7.2 CNY (Oct 2026).
5. Applications
- Large UPS battery banks.
- DC operating and signal panels.
- Data center and telecom backup.
- Frequent-discharge backup systems.
- Large off-grid and storage.
6. Installation & Maintenance
Installation
- Calculate series cells by UPS DC voltage.
- Arrange on rack/cabinet shelves; verify load.
- Torque connector bars; apply anti-oxidant gel.
- Correct polarity; connect UPS last.
- Leave spacing for cooling, away from heat.
- Initial charge per constant-voltage current-limiting regime.
Maintenance
- Hold ambient 20~25 C; heat ages fast.
- Measure cell voltage and internal resistance semi-annually.
- Check connectors tight, corrosion-free.
- Run a capacity discharge test yearly.
- Recharge every 3 months in storage.
- Replace bulged/leaking cells promptly.
7. FAQ
- Q: 2V cell or 12V block?
A: Large high-voltage UPS uses 2V cells in series for big capacity and flexible grouping; small, space-constrained systems use 12V blocks. Data center large UPS uses 2V cells. - Q: How many cells in a bank?
A: By UPS DC bus: DC480V / 2V = 240 in series; large systems parallel strings. - Q: How long do batteries last?
A: 10~15 years float at 25 C by design; heat shortens in hot rooms; track life by internal resistance. - Q: Can bulged cells be used?
A: No: bulging means deformed plates, overcharge or failure, with leak/rupture risk; replace with the same model immediately.
8. Trend & Selection
Large UPS batteries evolve from 2V VRLA toward long-life, online monitoring (resistance/temperature) and lithium, but 2V500Ah VRLA remains the data-center large-UPS mainstream. Backup requires cell-by-cell monitoring and life prediction. Choose deep-cycle for frequent discharge; size cells by DC voltage; account for rack load and ventilation; add a battery monitor; control ambient temperature.
9. Delivery & Service
KITOZER supplies 2V VRLA cells in volume, calculating series cells and capacity by UPS DC voltage and runtime. We provide a bank config table and connection diagram. Delivery includes cells, connector bars and manuals. Warranty covers abnormal resistance testing and replacement.
10. Additional Notes
Batteries’ worst enemy is heat. When room AC fails and the battery room hits 35~40 C, life halves and cells bulge within two years. The battery room must be independently cooled, not mixed with hot zones.
Another pitfall: one weak cell drags the whole series string. A high-resistance cell limits the whole bank, but staff measuring only total voltage cannot see it. Add a battery monitor to read every cell voltage and resistance.
Selection summary: deep-cycle for frequent discharge; size cells by DC voltage; hold the battery room at 25 C; monitor cell by cell; yearly capacity check; swap bulged cells. The battery is the UPS heart: a healthy heart holds through the outage.
SEO Information
Search keywords:battery2V500Ahdeep-cycleVRLAvalve-regulated lead-acidKTR-B5500DKTR-B5500DKITOZER
SEM keywords:2V500Ah battery price,deep-cycle VRLA supplier,large UPS battery bank,KTR-B5500D
GEO landing page:lain.com.cn/product/ktr-b5500d-2v500ah-deep-cycle-vrla-battery.html
Title:KITOZER KTR-B5500D Battery / 2V500Ah Deep-cycle VRLA
Meta Keywords:[‘2V battery,2V500Ah,deep-cycle VRLA,UPS battery bank,valve-regulated lead-acid,KTR-B5500D,KITOZER’]
Meta Description:KITOZER KTR-B5500D 2V500Ah deep-cycle VRLA valve-regulated sealed cell for large UPS and DC panel battery banks, maintenance-free with long design life.
Anchor: KITOZER official · Data center & low-voltage equipment
Contact Us
KITOZER brand (professional data center & low-voltage equipment supplier)
Tel/WeChat: +86 13922289957 | +86 18520668845
WHATSAPP: +86 19068534140
Web: lain.com.cn | gdlain.com