Table of Contents
ToggleKITOZER KTR-PS11 Power Surge Protector / Three-phase 380V 60kA Class C
Brand: KITOZER Series: KTR-PS11 Category: Power Distribution / Power Surge Protector
power SPDthree-phase 380V60kAClass Csurge protectorKTR-PS11
1. Overview
KITOZER KTR-PS11 is a three-phase 380V 60kA Class C power surge protective device (SPD) paralleled at the distribution panel, UPS input or critical load front-end, diverting lightning surges and switching overvoltage riding the power line. Mains enters the room from the transformer; induced lightning or large load switching produces transient high voltage (up to several kV) that travels along the line into UPS, servers and switches and burns power supplies. KTR-PS11 parallels between the three phases (L1/L2/L3), neutral (N) and PE (4-pole): normally high-impedance without affecting supply; during a surge it conducts instantly, diverts current to ground and clamps residual voltage within equipment tolerance.
60kA is the nominal/max discharge current (8/20 us waveform); Class C (level 3) is the final fine-protection stage installed at the sub-distribution or load front-end, with lower residual voltage close to the protected gear. Three-phase 380V means it serves three-phase five-wire AC loops (L1-L2-L3-N-PE). Rail-mount modular, failed cartridges swap live, with a status window (green OK/red failed) and a remote-contact to the panel monitor.
In data center power, surge protection is staged: Class B (level 1) at the main, Class C (level 3) at sub-distribution, shaving the surge step by step. KTR-PS11 is the three-phase Class C final stage close to UPS and precision power distribution, a common room-power accessory.
2. Key Features
Three-phase 380V
- L1-L2-L3-N-PE 4-pole protection.
- For three-phase 5-wire AC.
- Clamps residual voltage for downstream gear.
60kA discharge
- 60kA (8/20 us) discharge.
- Class C final fine protection.
- Close to 3-phase UPS/loads.
Rail modular
- 35mm rail-mount.
- Hot-swap failed cartridges.
- Green/red status window.
Remote contact
- Remote contact output.
- Uploads to panel DCIM.
- Short thick ground.
3. Specifications
| 项目 | KTR-PS11 | KTR-PS11-40(40kA) | KTR-PS11-100(100kA) |
|---|---|---|---|
| 相制 | 三相380V | 三相380V | 三相380V |
| 极数 | 4P(3+N+PE) | 4P(3+N+PE) | 4P(3+N+PE) |
| 通流容量 | 60kA(8/20) | 40kA(8/20) | 100kA(8/20) |
| 保护级别 | C级(三级) | C级(三级) | B/C级 |
| 电压保护水平 | 低 | 低 | 中 |
| 安装 | 导轨35mm | 导轨35mm | 导轨35mm |
| 状态指示 | 绿/红+遥信 | 绿/红 | 绿/红+遥信 |
| 应用 | 分配电/UPS前 | 末端设备 | 总/分配电 |
4. Reference Prices
KTR-PS11 三相60kA C级防雷器(4极、导轨、状态窗、遥信): Reference USD 58~108 / unit (ref. CNY 420~780 at ~7.2)
KTR-PS11-40 三相40kA C级防雷器(末端设备): Reference USD 44~81 / unit (ref. CNY 320~580 at ~7.2)
KTR-PS11-100 三相100kA防雷器(B/C级): Reference USD 94~178 / unit (ref. CNY 680~1,280 at ~7.2)
Reference only; by discharge rating, stage and quantity; panel mounting and grounding excluded. Exchange: 1 USD ~ 7.2 CNY (Oct 2026).
5. Applications
- Class C at 3-phase UPS input.
- Precision distribution and row cabinet front-end.
- Three-phase critical load front-end.
- Row cabinets and distribution panel SPD.
- Staged with main-panel Class B SPD.
6. Installation & Maintenance
Installation
- Parallel SPD at the protected loop input.
- Wire L1/L2/L3/N/PE per labels.
- Add upstream backup (fuse/MCB).
- Short thick ground to earth bar.
- Rail-mount; confirm green window.
- Wire remote contact to DCIM.
Maintenance
- Check status window quarterly.
- Replace cartridge on red window.
- Check SPD action after storms.
- Test remote-contact upload.
- Keep ground tight, corrosion-free.
7. FAQ
- Q: How many poles for 3-phase SPD?
A: A 3-phase 5-wire system uses 4P (3+N+PE): three phases plus N and PE; a 3-phase 3-wire system uses 3P. Choose by distribution system. - Q: Is 60kA enough?
A: Class C 60kA is generally enough at 3-phase UPS input and row cabinets; choose Class B high discharge at the main service entry. Select by position and lightning zone. - Q: Need a fuse ahead of SPD?
A: Yes: a failed SPD can short and catch fire; add a dedicated backup fuse/MCB upstream to isolate it without cutting supply. - Q: Grounding requirement?
A: Ground wire short and thick (per specified cross-section), to the room equipotential bar with proper resistance; long leads add inductance and residual voltage stays high.
8. Trend & Selection
Room power moves from single-stage to staged fine protection; Class C final SPDs add remote contacts and hot-swap cartridges for online monitoring. Select stage by lightning zone (B at main, C at end); choose single/three-phase by system; 60kA is common at the end; add upstream backup; ground short and thick; upload contacts to DCIM.
9. Delivery & Service
KITOZER supplies three/single-phase power SPDs in volume, configuring stage and discharge by the distribution system and lightning zones. We advise wiring and backup protection. Delivery includes SPD modules, rail, backup fuse and terminals. Warranty covers non-strike module failures.
10. Additional Notes
The common power-SPD pitfall is no upstream backup protection. An aged SPD fails short; without a fuse ahead, it catches fire and burns the whole box. SPDs must have a dedicated backup fuse/MCB upstream.
Another pitfall: over-long ground leads. An SPD grounded by a long run to the earth bar has high lead inductance, so residual voltage does not drop during a surge — the SPD is wasted. Ground leads must be short, thick and local to equipotential bonding.
Selection summary: stage B at main, C at end; 4-pole for 3-phase 380V; 60kA common at the end; add upstream backup fuse; ground short and thick; upload contacts. Power SPD is the distribution fuse — unseen until a surge proves its worth.
SEO Information
Search keywords:power SPDthree-phase 380V60kAClass Csurge protectorKTR-PS11KTR-PS11KITOZER
SEM keywords:three-phase power SPD price,60kA surge protector supplier,Class C SPD,KTR-PS11
GEO landing page:lain.com.cn/product/ktr-ps11-three-phase-380v-60ka-class-c-spd.html
Title:KITOZER KTR-PS11 Power Surge Protector / Three-phase 380V 60kA Class C
Meta Keywords:[‘power surge protector,three-phase SPD,380V surge protector,60kA SPD,Class C SPD,KTR-PS11,KITOZER’]
Meta Description:KITOZER KTR-PS11 three-phase 380V 60kA Class C power SPD parallels at the distribution panel input to divert lightning and switching surges and protect downstream three-phase loads.
Anchor: KITOZER official · Data center & low-voltage equipment