ToggleKITOZER Temperature Humidity Sensor: Data Center Environment Monitoring Complete Guide
Comprehensive technical guide covering wall-mount, DIN-rail, duct-mount and probe-type temperature humidity sensors, RS485 Modbus RTU, 4-20mA output, ±0.3°C temperature accuracy, ±2%RH humidity accuracy, installation, calibration, 90+ FAQ, pricing and applications.
By KITOZER | Guangzhou Lian Intelligent System Development Co., Ltd. | October 2026
1. Product Definition and Overview
A temperature humidity sensor for data centers is an electronic device that measures ambient air temperature and relative humidity, and transmits these measurements to a central monitoring system (BMS, DCIM, or SCADA). KITOZER temperature humidity sensors are engineered specifically for the rigorous environmental monitoring requirements of data centers, server rooms, telecommunications switching centers, and equipment shelters. They provide accurate, reliable, and continuous measurement of two critical environmental parameters that directly affect equipment reliability and uptime.
The KITOZER sensor line includes four form factors: wall-mount with LCD display, DIN-rail mount for electrical cabinets, duct-mount for HVAC air ducts, and remote probe types. All models feature RS485 Modbus RTU communication as standard, with optional 4-20mA analog output, 0-10V output, and Ethernet Modbus TCP. Temperature accuracy is ±0.3°C (optional ±0.1°C), humidity accuracy is ±2%RH (optional ±1.5%RH). The sensors operate from 9-30VDC supply, draw less than 100mA, and support up to 1200m RS485 bus length.

2. Why Temperature and Humidity Monitoring Matters
Data center equipment is sensitive to environmental conditions. Servers, storage arrays, and network switches operate within specified temperature and humidity envelopes. ASHRAE recommends 18-27°C and 40-60%RH. Deviations cause equipment failures, shortened lifespan, and safety hazards. Continuous monitoring with accurate sensors is the first line of defense against environmental incidents.
Temperature monitoring detects hot spots before they become overheating incidents. Humidity monitoring prevents both corrosion (high humidity) and electrostatic discharge (low humidity). Modern DCIM systems aggregate sensor data to visualize heat maps, optimize cooling, and trigger alarms. KITOZER sensors provide the reliable data foundation for these systems.
Without accurate sensors, operators are blind to environmental conditions. A failed sensor can mask a real hot spot, leading to equipment overheating. KITOZER sensors include built-in diagnostic functions: sensor drift detection, broken wire detection, and bus communication quality monitoring.
3. Working Principle
3.1 Temperature Measurement
KITOZER uses the digital temperature sensor chip (SHT35 or SHT45 by Sensirion, or equivalent) as the primary temperature sensing element. These MEMS-based sensors contain a bandgap temperature reference and a sigma-delta ADC. Temperature is measured to ±0.3°C accuracy over -40 to +125°C range. The sensor outputs calibrated digital data via I2C or SPI to the main microcontroller.
Alternative sensing elements include NTC thermistors (for cost-sensitive models) and Pt100/Pt1000 RTDs (for high-precision models). NTC thermistors offer ±0.5°C accuracy at lower cost. Pt1000 RTDs offer ±0.1°C accuracy but require signal conditioning circuitry.
3.2 Humidity Measurement
Humidity is measured using a capacitive polymer sensor. The sensor consists of a thin polymer film between two electrodes. As water vapor is absorbed by the polymer, the dielectric constant changes, altering the capacitance. The microcontroller measures this capacitance and converts it to relative humidity percentage. KITOZER uses Sensirion SHT35/SHT45 sensors which offer ±2%RH accuracy over 0-100%RH range, with excellent long-term stability (less than 0.25%RH drift per year).
3.3 Signal Processing
The microcontroller (ARM Cortex-M0 or equivalent) reads the sensor data every 2 seconds, applies calibration corrections, and formats the data for transmission. The RS485 transceiver converts the TTL serial signal to differential RS485 levels. An optional 4-20mA DAC converts the digital measurement to analog current output. The LCD driver updates the display every second.
4. Technical Parameters
| Parameter | Standard Model | High-Precision Model |
|---|---|---|
| Temperature Range | -40 to +125°C | -20 to +80°C |
| Temperature Accuracy | ±0.3°C | ±0.1°C |
| Humidity Range | 0-100%RH | 0-100%RH |
| Humidity Accuracy | ±2%RH | ±1.5%RH |
| Measurement Interval | 2 seconds | 1 second |
| Supply Voltage | 9-30VDC | 9-30VDC |
| Current Consumption | <80mA | <100mA |
| Communication | RS485 Modbus RTU | RS485 Modbus RTU + BACnet MS/TP |
| Baud Rate | 1200-115200 bps | 1200-115200 bps |
| Data Bits / Parity / Stop | 8N1 / 8E1 / 8O1 | 8N1 / 8E1 / 8O1 |
| Analog Output (optional) | 4-20mA (2 channels) | 4-20mA (2 channels) + 0-10V |
| Bus Length | up to 1200m | up to 1200m |
| Max Devices per Bus | 32 | 32 |
| Display | LCD 128×64 (wall-mount models) | LCD 128×64 with backlight |
| Operating Temp (electronics) | -40 to +85°C | -40 to +85°C |
| Operating Humidity | 0-100%RH non-condensing | 0-100%RH non-condensing |
| IP Rating | IP20 (DIN-rail), IP54 (wall-mount) | IP54 (wall-mount), IP65 (duct-mount) |
| Dimensions (wall-mount) | 86×86×28mm | 86×86×28mm |
| Dimensions (DIN-rail) | 70×60×43mm | 70×60×43mm |
| Weight | 100-150g | 120-180g |
5. Product Models and Form Factors
5.1 KH-TH1 Wall-Mount with LCD
The KH-TH1 is a wall-mount sensor with an integrated LCD display. It is designed for direct mounting on office walls or server room walls, at 1.5m height (breathing zone). The LCD displays current temperature, humidity, dew point, and sensor address. The sensor element is protected by a perforated plastic cap that allows air flow while blocking direct contact. Cable entry is via bottom conduit gland.
5.2 KH-TH2 DIN-Rail Mount
The KH-TH2 is a compact DIN-rail mount sensor designed for installation inside electrical cabinets, server racks, or network cabinets. It mounts on standard 35mm DIN rail. The sensor element protrudes through a slot in the cabinet door or side panel to measure room air. Terminal blocks provide screw connections for power, RS485 A/B, and optional analog output.

5.3 KH-TH3 Duct-Mount
The KH-TH3 is designed for installation in HVAC air ducts. The sensor probe (150mm or 250mm length) inserts through a 25mm hole in the duct wall, secured by a flange fitting. The electronics enclosure sits outside the duct. The probe has a perforated stainless steel or PTFE cover that allows air sampling while protecting the sensor element.

5.4 KH-TH4 Remote Probe
The KH-TH4 features a remote probe connected by 0.5-10m cable. The electronics enclosure can be mounted in an accessible location, while the probe is placed in the measurement zone. This is ideal for measuring in hard-to-reach locations such as inside server racks, cable trays, or cold aisles. The probe is available in plastic, stainless steel, or Teflon-coated versions for harsh environments.
5.5 KH-TH5 LCD Wall-Mount Premium
The KH-TH5 is a premium wall-mount sensor with a larger LCD display, backlight, and optional touch buttons. It supports local configuration (set alarm thresholds, change address, baud rate) without requiring a USB converter. The display shows temperature, humidity, dew point, heat index, and alarm status. It is the preferred model for data center command centers and operations offices.

6. Modbus RTU Communication Protocol
KITOZER sensors use the Modbus RTU protocol over RS485, the most widely used industrial communication protocol. Understanding Modbus is essential for system integration.
6.1 Modbus Frame Structure
A Modbus RTU frame consists of: slave address (1 byte), function code (1 byte), data (N bytes), CRC check (2 bytes). The frame is delimited by silent intervals of 3.5 character times. Common function codes: 03 (read holding registers), 04 (read input registers), 06 (write single register), 16 (write multiple registers).
6.2 Register Map
| Register | Description | Data Type | Scale |
|---|---|---|---|
| 0x0000 | Temperature (°C) | INT16 | ÷100 |
| 0x0001 | Humidity (%RH) | UINT16 | ÷100 |
| 0x0002 | Dew Point (°C) | INT16 | ÷100 |
| 0x0003 | Supply Voltage (V) | UINT16 | ÷100 |
| 0x0010 | Slave Address | UINT16 | 1 |
| 0x0011 | Baud Rate Code | UINT16 | 1 |
| 0x0012 | Parity Code | UINT16 | 1 |
| 0x0020 | Temp High Alarm Threshold | INT16 | ÷100 |
| 0x0021 | Temp Low Alarm Threshold | INT16 | ÷100 |
| 0x0022 | Humidity High Alarm Threshold | UINT16 | ÷100 |
| 0x0023 | Humidity Low Alarm Threshold | UINT16 | ÷100 |
| 0x0030 | Alarm Status (bitmask) | UINT16 | 1 |
| 0x0100 | Serial Number (1-4) | UINT32 | 1 |
| 0x0110 | Firmware Version | UINT16 | ÷100 |
6.3 Configuration
Sensor configuration (address, baud rate, alarm thresholds) can be done via: (1) Modbus write commands from the BMS; (2) USB configuration cable connected to a PC running KITOZER configuration software; (3) Local buttons on premium LCD models. The factory default is address 1, baud 9600, 8N1.
7. Installation Guide
7.1 Location Selection
Proper sensor placement is critical for accurate environmental monitoring. Follow these guidelines:
- Mount at 1.5m above floor (breathing zone), away from direct sunlight and heat sources.
- Avoid placing near CRAC supply air diffusers (reading will be artificially low) or return air grilles (reading artificially high).
- Space sensors every 100-200m² in open data center floors, or one per server row in contained aisles.
- Place sensors at the front of server racks (cold aisle intake) to measure the air entering equipment.
- Do not mount on exterior walls (temperature affected by outdoor conditions).
- Avoid locations with direct airflow from doors, windows, or ventilation openings.
7.2 Wiring
KITOZER sensors use a 4-wire connection: V+ (9-30VDC), GND, A (RS485+), B (RS485-). Use twisted pair shielded cable (Belden 3105A or equivalent) for RS485. Maximum bus length is 1200m at 9600bps, reducing to 100m at 115200bps. Daisy-chain all sensors on the bus, not star topology. Terminate the far end with 120Ω resistor. Ground the shield at one end only (the BMS end).
7.3 Mounting
Wall-mount sensors: use two screws through the keyhole slots on the back. Level the sensor. Do not over-tighten. DIN-rail sensors: clip onto 35mm DIN rail. Duct sensors: drill 25mm hole in duct wall, insert probe, secure with flange fitting.
7.4 Power Supply
KITOZER sensors can be powered from: (1) BMS/DCIM controller power output (12VDC or 24VDC); (2) separate 24VDC power supply; (3) PoE injector for Ethernet models. Total current per sensor is less than 100mA. A 24VDC 2A supply can power up to 20 sensors.
8. Commissioning and Configuration
After installation, each sensor must be configured with a unique Modbus address and verified for accurate readings. KITOZER provides free configuration software for Windows.
8.1 Address Assignment
Each sensor on the bus must have a unique address (1-247). KITOZER recommends sequential numbering by location: sensor 1 at the main entrance, sensor 2 in the first row, etc. Use the configuration software to set addresses one at a time (connect each sensor individually to the USB converter).
8.2 Baud Rate and Parity
Set all sensors on the same bus to the same baud rate and parity. Default: 9600 baud, 8N1. For large networks (more than 16 sensors), increase to 19200 or 38400 baud for faster polling.
8.3 Alarm Thresholds
Configure alarm thresholds appropriate to the installation: temperature high alarm at 28°C, low alarm at 18°C; humidity high alarm at 60%RH, low alarm at 40%RH. The sensor can trigger local relay output (optional) and report alarm status via Modbus.
8.4 Verification
Verify each sensor reading against a reference instrument. Allow 30 minutes for stabilization. Compare readings: temperature within ±0.5°C, humidity within ±3%RH. If deviations exceed these tolerances, check for sensor placement issues or calibration drift.
9. Calibration and Maintenance
9.1 Calibration Schedule
KITOZER recommends annual calibration. Calibration can be done: (1) at the factory (send back to KITOZER Guangzhou); (2) on-site using a reference instrument and the configuration software (two-point calibration: at 25°C/50%RH and at 0°C/0%RH or 100°C/100%RH); (3) using a portable humidity calibrator (salt chamber method).
9.2 Sensor Element Replacement
The sensing element (SHT35/SHT45) is field-replaceable. In high-dust or high-vibration environments, replace every 2-3 years. In normal office environments, the sensor lasts 5-8 years. Replacement requires opening the enclosure and unplugging the sensor module. The new module is automatically recognized by the main controller.
9.3 Cleaning
Wipe the enclosure with a dry or slightly damp cloth. Do not use solvents. Do not touch the sensor element directly. The protective cap can be removed and rinsed with clean water, then dried completely before reinstallation.
10. Common Faults and Troubleshooting (FAQ Part 1: Questions 1-20)
Q1: BMS cannot read the sensor.
A: Check: power LED on sensor? RS485 A/B wiring correct? Address unique? Baud rate matches? 120Ω termination installed? Cable damaged? Use a Modbus scanner to test.
Q2: Temperature reading is too high.
A: Sensor near heat source (CRAC, sunlight, server exhaust). Relocate. Check if the sensor is in direct airflow. Calibrate against reference thermometer.
Q3: Humidity reading is stuck at 0% or 100%.
A: Sensor element failure. Replace the sensor module. Check if the protective cap is blocked by dust or water.
Q4: Intermittent communication loss.
A: Check cable connections, especially at terminal blocks. Check for loose wires. Check bus termination. Reduce baud rate. Add a repeater for long cables.
Q5: Multiple sensors show same address.
A: Two sensors configured with the same address. Disconnect all but one, reconfigure addresses sequentially. Never power up two sensors with the default address at the same time.
Q6: Display is blank.
A: Check power supply voltage at the sensor terminals. Check wiring. Check if the backlight setting is off. Replace the LCD module if power is present but display is blank.
Q7: Readings drift over time.
A: Sensor aging. Calibrate annually. In dusty environments, clean the protective cap monthly. Replace sensor element every 3 years in harsh environments.
Q8: 4-20mA output is inaccurate.
A: Check load resistance (should be 250-500Ω). Check wiring. Recalibrate the analog output via configuration software. Verify supply voltage (must be 12-30VDC).
Q9: Sensor reports error code.
A: Error code 0x01: sensor element not detected. Check sensor cable connection. Error code 0x02: CRC error on sensor bus. Replace sensor module. Error code 0x04: supply voltage low. Check power supply.
Q10: How far can RS485 cable run?
A: Up to 1200m at 9600bps with Belden 3105A cable. At higher baud rates, distance decreases. Use RS485 repeaters for distances beyond 1200m.
Q11: How many sensors can be on one bus?
A: Up to 32 sensors on a standard RS485 bus. Use a repeater or RS485 hub for more than 32. Each segment must have its own termination.
Q12: Can I use Cat5e cable for RS485?
A: Yes, but use only one twisted pair for A/B. The other pairs can be used for power (V+/GND). Do not use unshielded cable for long runs or industrial environments.
Q13: What is the response time?
A: The sensor takes 2 seconds per measurement. The BMS typically polls every 10-60 seconds. Total response time from environmental change to BMS display is 10-60 seconds.
Q14: Can the sensor be used outdoors?
A: Only the IP65 duct-mount model can be used outdoors, in a sun-shielded and weather-protected location. Standard wall-mount (IP54) is for indoor use only.
Q15: How do I reset the sensor to factory defaults?
A: Use the configuration software: connect the sensor, click “Restore Defaults”, or press and hold the configuration button for 5 seconds (on models with a button). Default: address 1, baud 9600, 8N1.
Q16: What is the difference between Modbus RTU and Modbus TCP?
A: Modbus RTU runs on RS485 serial (cable). Modbus TCP runs on Ethernet (network). KITOZER RTU models use RS485; the Ethernet model supports Modbus TCP.
Q17: Can the sensor trigger an alarm relay?
A: Yes. The optional relay output (SPDT, 30VDC/1A) triggers when temperature or humidity exceeds configured thresholds. Wire the relay to the BMS digital input or to an audible/visual alarm.
Q18: What is the power consumption?
A: Less than 80mA at 24VDC (1.9W). With LCD backlight on, up to 100mA. Energy-efficient design allows bus-powered operation for short buses.
Q19: How do I update the firmware?
A: KITOZER provides free firmware updates. Download the latest firmware from gdlain.com, connect the sensor via USB, and use the configuration software to upload. Firmware updates add features and improve accuracy.
Q20: What certifications do the sensors have?
A: CE, RoHS, FCC, ISO 9001. Test reports available on request.
11. FAQ Part 2: Questions 21-45
Q21: Can I mix KITOZER sensors with other Modbus devices on the same bus?
A: Yes, as long as all devices use the same baud rate and parity. Each device must have a unique address. KITOZER sensors are standard Modbus RTU slaves and work with any Modbus master.
Q22: How do I know the sensor address if I forgot it?
A: Use the configuration software with “Auto Scan” function. Connect one sensor at a time, the software will discover its address. Or press the configuration button for 3 seconds, the sensor will broadcast its address on the bus.
Q23: What if the humidity reading is always high?
A: Check if the sensor is near a water source, humidifier, or open window. Check if the protective cap is wet. Allow 30 minutes to stabilize after relocation. If still high, the sensor element may be water-damaged and needs replacement.
Q24: Can I use the sensor with a PLC?
A: Yes. KITOZER sensors support standard Modbus RTU, which is supported by Siemens S7, Mitsubishi, Omron, Allen-Bradley, and most PLCs. Use the PLC’s Modbus library to read registers 0x0000 and 0x0001.
Q25: What is the difference between relative humidity and absolute humidity?
A: Relative humidity (%RH) is the percentage of water vapor in air compared to the maximum at that temperature. Absolute humidity is the actual mass of water vapor per volume of air. KITOZER sensors measure %RH.
Q26: What is dew point?
A: Dew point is the temperature at which air becomes saturated (100%RH) and water condenses. KITOZER sensors calculate dew point from temperature and humidity readings. Dew point above 15°C indicates condensation risk.
Q27: Can the sensor measure CO2 or VOC?
A: No. The KITOZER temperature humidity sensor measures only temperature and humidity. For CO2, see KITOZER CO2 sensor (separate product). For multi-parameter monitoring, use the KITOZER environmental monitoring station.
Q28: What cable should I use for long runs?
A: Belden 3105A (twisted pair, shielded) or equivalent. For runs over 500m, use 22AWG or thicker. Avoid parallel runs with power cables. Maintain at least 20cm separation from 220V power lines.
Q29: The BMS shows garbage data.
A: Check baud rate and parity settings. Check register addressing (some systems use 0-based vs 1-based). Check byte order (big-endian vs little-endian). KITOZER uses big-endian (standard Modbus).
Q30: Can I power the sensor from the BMS USB port?
A: No. USB provides 5V, but the sensor requires 9-30VDC. Use a 24VDC power supply. Some BMS controllers provide 24VDC output terminals – use those.
Q31: What happens if the RS485 cable is reversed?
A: The sensor will not communicate. Reverse the A and B wires. The sensor has reverse polarity protection on power, but NOT on RS485 – reversing RS485 will not damage the sensor but communication will fail.
Q32: Can the sensor be daisy-chained?
A: Yes. RS485 is designed for daisy-chain topology. Connect A to A, B to B through each sensor. Do NOT use star topology (branches cause signal reflection). Use terminal blocks on the sensor to pass through the bus.
Q33: How do I know if the sensor needs calibration?
A: Compare reading with a calibrated reference instrument. If temperature deviation exceeds ±0.5°C or humidity exceeds ±3%RH, recalibrate. KITOZER recommends annual calibration as preventive maintenance.
Q34: What is the response time T63?
A: T63 (time constant) is the time for the sensor to reach 63% of a step change. For KITOZER wall-mount sensors, T63 is 8-12 seconds. For duct-mount with airflow, T63 is 4-6 seconds.
Q35: Can I paint the enclosure?
A: No. Painting blocks the air vents on the sensor cap, preventing air from reaching the sensing element. This will cause slow and inaccurate readings.
Q36: What is the expected lifespan?
A: 5-8 years in normal office environments. 3-5 years in industrial environments with dust, vibration, or temperature extremes. The sensor element drifts approximately 0.25%RH per year.
Q37: Can I use the sensor in a freezer?
A: The standard model operates down to -40°C, but condensation will form inside the enclosure when moving from cold to warm. For freezer applications, use the heater model (optional internal heater prevents condensation).
Q38: What is the BACnet version?
A: The high-precision model supports BACnet MS/TP on RS485. BACnet objects: Analog Input 1 (temperature), Analog Input 2 (humidity), Analog Input 3 (dew point). Device name, instance number configurable via BACnet.
Q39: How do I backup sensor configuration?
A: Use the configuration software to read the sensor and save the configuration file (.kcf format). If a sensor is replaced, load the saved configuration to the new sensor. This ensures consistent settings.
Q40: Can multiple sensors share the same power supply?
A: Yes. Calculate total current: 20 sensors × 100mA = 2A. Use a 24VDC 5A power supply for 50 sensors. Run power in parallel from the supply to each sensor. Do not power-chain sensors (voltage drop on long runs).
Q41: The sensor LED is red.
A: Red LED indicates alarm condition. Check temperature and humidity readings against configured thresholds. Check BMS alarm log. Press the configuration button to acknowledge. If no alarm condition, check alarm threshold settings.
Q42: The sensor LED is blinking.
A: Slow blink (1Hz): normal operation, communicating. Fast blink (5Hz): no bus communication, check wiring. Double blink: sensor self-test failed, contact KITOZER support.
Q43: Can I use the sensor with LoRa or NB-IoT?
A: The standard model uses RS485. For wireless monitoring, connect the RS485 output to a KITOZER LoRa/NB-IoT gateway, which transmits data to the cloud platform.
Q44: What is the MTBF?
A: Mean Time Between Failures is 500,000 hours (about 57 years) per Bellcore specifications. Actual field lifespan is limited by environmental factors, typically 5-8 years.
Q45: Does the sensor have local data logging?
A: The standard model does not. The data logging model (KH-TH5L) has 16MB flash memory and stores 1 million readings. Log interval is configurable from 1 second to 1 hour. Data can be downloaded via USB or Modbus.
12. FAQ Part 3: Questions 46-70
Q46: What is the difference between IP20 and IP54?
A: IP20: protected against fingers and solid objects >12mm, no water protection. For installation inside cabinets only. IP54: dust-protected (limited ingress, no harmful deposit) and splash-proof from any direction. For wall-mount in normal rooms.
Q47: Can I extend the sensor cable?
A: For RS485 bus: yes, up to 1200m total. For the remote probe cable: yes, up to 10m (the I2C bus for the sensor element is limited to 10m). Use shielded cable for the probe extension.
Q48: What is the Modbus CRC calculation?
A: Modbus RTU uses CRC-16 (polyomial 0xA001, initial value 0xFFFF). The BMS calculates CRC automatically. If you are writing a custom master, use a standard Modbus library.
Q49: The reading updates only once per minute.
A: This is the BMS polling interval, not the sensor. The sensor measures every 2 seconds. Configure the BMS to poll more frequently (every 5-10 seconds) for faster updates.
Q50: Can the sensor measure outside the rated range?
A: The sensor will continue to report values beyond -40 to +125°C, but accuracy is not guaranteed outside the rated range. Extended-range sensors are available on request (up to +150°C).
Q51: How do I clean a dirty sensor cap?
A: Remove the perforated plastic cap (twist counterclockwise). Rinse with clean water or mild detergent. Do not use compressed air (may damage the sensor element). Dry completely before reinstalling.
Q52: What is the difference between NTC and PT1000?
A: NTC: negative temperature coefficient thermistor, nonlinear, low cost, ±0.5°C accuracy. PT1000: platinum RTD, linear, more expensive, ±0.1°C accuracy. KITOZER uses SHT-series digital sensors which combine both in one chip.
Q53: Can the sensor be mounted upside down?
A: The wall-mount sensor can be mounted in any orientation, but the protective cap must face downward or horizontally (not upward) to prevent water accumulation. The LCD will be upside down – use the configuration software to rotate the display 180°.
Q54: What is the recommended sensor density?
A: For data centers: 1 sensor per 100-200m², or 1 per server row. For server racks: 1 sensor per rack row at the cold aisle. For offices: 1 per 500m². For warehouses: 1 per 1000m².
Q55: Can I use the sensor with a Raspberry Pi?
A: Yes. Connect a USB-to-RS485 adapter to the Raspberry Pi, use Python’s minimalmodbus library to read registers. Example: instrument.read_register(0, functioncode=4) returns temperature×100.
Q56: What happens if power is interrupted?
A: The sensor stops measuring. When power returns, it automatically restarts and resumes normal operation. Configuration is stored in non-volatile flash memory. No data is lost (the sensor does not log data internally).
Q57: Can the sensor be used in explosive atmospheres?
A: The standard model is NOT intrinsically safe. For hazardous areas, use the intrinsically safe model (KITOZER KH-TH-EX) with ATEX/IECEx certification, installed with a safety barrier.
Q58: What is the difference between 4-20mA and 0-10V output?
A: 4-20mA: current loop, immune to noise, long distance, 2-wire. 0-10V: voltage output, shorter distance, affected by noise, 3-wire. 4-20mA is preferred for industrial environments.
Q59: The sensor shows a different temperature than the wall thermostat.
A: Wall thermostats are calibrated for HVAC control, not for measurement. They may have ±1-2°C tolerance. KITOZER sensors are calibrated to ±0.3°C. Compare against a reference instrument, not a thermostat.
Q60: Can I daisy-chain power and data on the same cable?
A: Yes. Use a 4-conductor shielded cable: pair 1 for V+/GND, pair 2 for RS485 A/B. This is common practice for wall-mount sensors. Do not use Cat5e for power over long distances (voltage drop).
Q61: What is the warranty?
A: 2 years from date of shipment. Warranty covers manufacturing defects. Not covered: water damage, physical damage, incorrect installation, unauthorized modification. Extended warranty (5 years) available on request.
Q62: Can I get a custom sensor range?
A: Yes. KITOZER can customize temperature range, humidity range, output type, enclosure material, and display. Minimum order quantity 50 units. Contact sales@gdlain.com.
Q63: How do I test the sensor before installation?
A: Connect the sensor to a USB-RS485 adapter on a PC, run the configuration software, verify readings. Breathe on the sensor – humidity should rise. Touch the sensor – temperature should rise. This confirms both sensing elements work.
Q64: What is the difference between SHT35 and SHT45?
A: SHT35: ±0.3°C, ±2%RH, older generation. SHT45: ±0.1°C, ±1.5%RH, newer generation, lower power, faster response. KITOZER standard models use SHT35; high-precision models use SHT45.
Q65: Can the sensor be integrated with BACnet/IP?
A: The RS485 model uses BACnet MS/TP. To integrate with BACnet/IP, use a BACnet router (MS/TP to IP). Or use the Ethernet model which supports Modbus TCP (convert to BACnet/IP via a gateway).
Q66: What is the maximum cable length for 4-20mA?
A: Up to 1000m with 24AWG cable. The 4-20mA current loop is immune to voltage drop. Use a 250Ω resistor at the receiver to convert to 1-5V.
Q67: The sensor display shows “Err”.
A: Sensor element failure. Check the sensor cable connection. If the sensor module is plugged in correctly, replace the sensor module. If the error persists after replacement, the main controller is faulty – return for service.
Q68: Can I use the sensor outdoors in direct sunlight?
A: No. Direct sunlight heats the sensor enclosure, causing artificially high temperature readings. Use a sun shield (KITOZER accessory) or install in a shaded location. The humidity reading is unaffected by sunlight.
Q69: What is the difference between Modbus function 03 and 04?
A: Function 03 reads holding registers (read-write, used for configuration). Function 04 reads input registers (read-only, used for measurements). KITOZER sensors: measurements at 0x0000-0x0003 are readable by both 03 and 04.
Q70: Can I use a generic USB-to-RS485 adapter?
A: Yes, any FTDI or CH340 based adapter works. KITOZER provides a certified adapter (KITOZER USB-RS485-KIT) with isolation and terminal blocks for reliable configuration.
13. FAQ Part 4: Questions 71-90
Q71: How do I know which sensor is which in a large deployment?
A: Label each sensor with its location on the enclosure. Record the mapping: address 1 = Row A Rack 1, address 2 = Row A Rack 2, etc. The configuration software can read the sensor serial number for inventory.
Q72: Can the sensor trigger email alarms?
A: The sensor itself cannot. The BMS/DCIM system polls the sensor and triggers email/SMS/WeChat alarms when thresholds are exceeded. KITOZER sensors provide the data; the alarm logic is in the central system.
Q73: What is the response time for alarm activation?
A: Sensor measurement: 2 seconds. BMS polling: 10-60 seconds. BMS alarm logic: 1-5 seconds. Total: 13-67 seconds from environmental change to alarm notification. For faster alarms, configure BMS to poll critical sensors every 5 seconds.
Q74: Can I use the sensor with a LoRaWAN gateway?
A: Yes. Connect the KITOZER RS485 sensor to a KITOZER LoRaWAN converter, which converts Modbus RTU to LoRaWAN. Data appears in the LoRaWAN network server (ChirpStack, The Things Network).
Q75: What is the current draw during alarm?
A: The sensor current does not change during alarm. The optional relay output consumes up to 1A at 30VDC separately. The sensor itself draws constant 80mA.
Q76: Can I use the sensor in a clean room?
A: Yes. The IP54 wall-mount model is suitable for clean rooms up to ISO 7. For ISO 5 or higher, use the flush-mount model with smooth surfaces and no crevices.
Q77: What is the difference between T63 and T90?
A: T63: time to reach 63% of step change. T90: time to reach 90% of step change. KITOZER T63 is 8-12 seconds, T90 is 25-35 seconds. For faster response, use a forced-air probe.
Q78: Can the sensor be recalibrated on-site?
A: Yes. Use the configuration software: place the sensor in a known environment (e.g., a salt chamber for 75%RH, or a reference thermometer for temperature), enter the reference value, and the software adjusts the calibration coefficients. Two-point calibration recommended annually.
Q79: What is the lifetime of the sensor element?
A: The SHT35/SHT45 sensor element has a rated lifetime of 8 years. Drift increases after 5 years. KITOZER recommends element replacement every 3-5 years for critical applications, or annual calibration for non-critical.
Q80: Can I use shielded cable with both ends grounded?
A: No. Grounding both ends creates a ground loop, which induces noise on the RS485 bus. Ground the shield at ONE end only (the BMS end). If noise is present, add an isolation module.
Q81: What is the difference between RS485 and RS232?
A: RS485: differential signaling, multi-drop (up to 32 devices), up to 1200m, industrial standard. RS232: single-ended, point-to-point, up to 15m, legacy. KITOZER uses RS485 exclusively.
Q82: Can the sensor measure temperature in a liquid?
A: No. The humidity sensor element is for air measurement only. For liquid temperature, use a Pt100 RTD probe (KITOZER TH-PT100 series). The humidity reading will be invalid if the sensor is submerged.
Q83: What is the mounting hole pattern?
A: Wall-mount: two keyhole slots, 60mm spacing, for M4 screws. DIN-rail: standard 35mm DIN rail clip. Duct: 25mm diameter hole for probe, 4 screws on flange.
Q84: Can I use the sensor with Modbus ASCII?
A: The KITOZER sensor supports Modbus RTU only. Modbus ASCII is not supported. ASCII is rarely used in modern systems; RTU is the standard.
Q85: What is the power supply ripple tolerance?
A: The sensor accepts 9-30VDC with up to 10% ripple. Use a regulated power supply. Unregulated supplies may cause display flicker or communication errors.
Q86: Can the sensor be mounted on a metal wall?
A: Yes. The enclosure is plastic (ABS/PC), so no interference. The RS485 signal is differential and immune to EMI. For best results, maintain 5mm gap between sensor and wall for air circulation.
Q87: What is the spare parts list?
A: Recommended spares: 10% of sensors (failures), 1 spare sensor module per 20 sensors, 1 USB-RS485 adapter, 1 roll of Belden 3105A cable, 50 terminal blocks, 10 termination resistors.
Q88: Can I get a sensor with 0-5V output?
A: The standard analog output is 4-20mA and 0-10V. 0-5V is available on request (custom order, MOQ 20). Alternatively, use a 2:1 resistor divider on the 0-10V output.
Q89: What is the shipping weight and package?
A: Each sensor is packaged in an anti-static bag with foam, inside a color box (120×100×60mm). Gross weight 200g per unit. Carton: 50 units, 45×35×30cm, 12kg.
Q90: How do I order KITOZER sensors?
A: Contact KITOZER sales: email sales@gdlain.com, Tel +86 18520668845, WeChat +86 13922289957, WhatsApp +1 906-853-4140. Provide: quantity, model (wall-mount/DIN/duct/probe), output type (RS485/4-20mA/Ethernet), and delivery address. Lead time: 3-5 days for standard models, 2-3 weeks for custom.
14. Application Scenarios
14.1 Data Center Cold Aisle Monitoring
In contained cold aisle systems, temperature and humidity at the rack intake is the critical parameter. KITOZER wall-mount sensors are mounted at the front of each rack row, measuring the air entering the servers. BMS systems use this data to adjust CRAC output and detect hot spots. Typical deployment: 1 sensor per rack row, at 1.5m height, 30cm from the rack intake.
14.2 Server Rack Internal Monitoring
For high-density racks (10kW+), internal temperature stratification is a concern. KITOZER DIN-rail or remote probe sensors are mounted inside the rack at the top, middle, and bottom to measure vertical temperature gradient. If the top is more than 5°C hotter than the bottom, airflow is insufficient.

14.3 Electrical Cabinet Monitoring
Low-voltage switchgear, UPS batteries, and PDUs require temperature monitoring to detect overheating connections. KITOZER DIN-rail sensors are mounted inside the cabinet, measuring internal air temperature. High temperature alarm triggers maintenance before a connection failure causes an outage.
14.4 HVAC Duct Monitoring
Supply and return air temperature/humidity in CRAC units and AHUs are measured with KITOZER duct-mount sensors. The BMS uses this data for demand-controlled ventilation, enthalpy calculation, and economizer control. Duct sensors are installed in both supply and return ducts, 1m from the AHU.
14.5 Warehouse and Storage Monitoring
Warehouses storing sensitive goods (electronics, pharmaceuticals, food) require continuous temperature/humidity monitoring. KITOZER wall-mount sensors are mounted every 1000m², with data logged to a cloud platform. Alarm thresholds: 15-25°C, 40-60%RH for electronics.
14.6 Clean Room Monitoring
Clean rooms in semiconductor and pharmaceutical manufacturing require tight environmental control. KITOZER high-precision sensors (±0.1°C, ±1.5%RH) are mounted at 1.2m height (working plane). Data feeds into the clean room monitoring system for compliance reporting.
14.7 Telecommunication Base Station Monitoring
Outdoor telecom cabinets house power systems, batteries, and transmission equipment. KITOZER DIN-rail sensors monitor internal temperature and humidity. Over-temperature triggers cooling fan or air-conditioner activation. Low temperature triggers battery heater.
14.8 Museum and Archive Monitoring
Museums and archives require stable temperature (18-20°C) and humidity (45-55%RH) for preservation. KITOZER high-precision sensors with data logging provide compliance documentation. The sensor’s low drift (0.25%RH/year) ensures long-term accuracy without frequent calibration.
15. Reference Pricing
| Model | Description | Unit Price (¥) | USD Reference (×2) |
|---|---|---|---|
| KH-TH1-S | Wall-mount, RS485, no display, ±0.3°C/±2%RH | ¥150 | ~$21 |
| KH-TH1-L | Wall-mount, LCD display, RS485 | ¥280 | ~$39 |
| KH-TH2-D | DIN-rail mount, RS485, Modbus RTU | ¥180 | ~$25 |
| KH-TH3-D | Duct-mount, 150mm probe, RS485 | ¥450 | ~$63 |
| KH-TH3-L | Duct-mount, 250mm probe, LCD display | ¥680 | ~$95 |
| KH-TH4-R | Remote probe, 2m cable, RS485 | ¥380 | ~$53 |
| KH-TH5-P | Premium wall-mount, LCD+buttons, 4-20mA | ¥850 | ~$119 |
| KH-TH5-H | High-precision, ±0.1°C/±1.5%RH, BACnet | ¥1,200 | ~$168 |
| KH-TH5-E | Ethernet model, Modbus TCP, PoE | ¥1,500 | ~$210 |
| KH-TH-EX | Intrinsically safe, ATEX certified | ¥3,500 | ~$490 |
| KH-USB-KIT | USB-RS485 configuration kit | ¥250 | ~$35 |
| KH-CAL | On-site calibration service | ¥500/sensor | ~$70 |
Note: Prices are reference prices (参考价) for volume orders (100+ units). Smaller quantities may be higher. USD prices are converted at current exchange rate and include export packaging. Contact sales for exact quotation.
16. KITOZER Brand Advantages
16.1 Engineering Expertise
KITOZER is the industrial product line of Guangzhou Lian Intelligent System Development Co., Ltd. With over 20 years of experience in environmental monitoring and data center infrastructure, KITOZER sensors are designed by engineers who have deployed thousands of sensors in real data centers. Our sensors are field-proven in Chinese data centers, telecom networks, and industrial facilities.
16.2 Quality Control
Every KITOZER sensor undergoes: (1) 100% functional test before shipment; (2) 24-hour burn-in test on a production line sample; (3) calibration against NIST-traceable reference instruments. Production follows ISO 9001 quality management system. CE, RoHS, FCC certified.
16.3 Local Support
Based in Guangzhou Panyu, KITOZER provides: (1) 24-hour response for technical support; (2) 2-year warranty with advance replacement; (3) free configuration software and documentation; (4) on-site commissioning support for large projects; (5) English-language support for overseas customers.
16.4 Competitive Pricing
KITOZER sensors are priced 40-60% lower than European brands (Siemens, Siemens, Vaisala, Testo) while meeting the same accuracy and reliability standards. For data center operators running hundreds of sensors, the cost savings are significant. Direct factory sales, no middlemen.
16.5 Customization
KITOZER can customize: sensor range, output protocol, enclosure material, display language, cable length, and labeling. Minimum order 50 units. Custom firmware features available for large projects.
17. Installation Diagram Walkthrough
Step 1: Plan Sensor Locations
Draw a floor plan. Mark rack rows, CRAC units, doors, windows. Place sensors at 1.5m height, 50cm from racks, away from direct airflow. Count sensors for each location type.
Step 2: Run Cable
Run Belden 3105A cable from the BMS location to each sensor, daisy-chain style. Use cable trays or conduit. Label both ends of each cable run.
Step 3: Mount Sensors
Drill screw holes for wall-mount. Clip DIN-rail sensors. Install duct sensors through duct holes. Ensure the sensor element faces the measurement zone.
Step 4: Wire Connections
Connect V+, GND, A, B to terminal blocks. Torque screws to 0.5 Nm. Do not leave loose strands. Add 120Ω termination at the last sensor on the bus.
Step 5: Power Up and Configure
Apply power. Verify LED lights. Connect USB-RS485 adapter. Set addresses sequentially. Set baud rate and parity. Configure alarm thresholds.
Step 6: Verify Readings
Read each sensor via BMS. Compare against reference. Allow 30 minutes stabilization. Check for communication errors in the BMS log.
Step 7: Document and Label
Label each sensor with its address and location. Update the as-built drawing. Provide documentation to the customer.
18. Development History of Temperature Humidity Sensors
18.1 Early Era (19th Century to 1960s)
The first hygrometers used human hair (hair hygrometer) or wet-and-dry bulb psychrometers. Temperature was measured by mercury thermometers. These analog devices required manual reading and recording. Accuracy was poor (±5%RH, ±1°C) and response time was slow (minutes).
18.2 Electronic Era (1970s-1990s)
The invention of the capacitance-based humidity sensor in the 1970s revolutionized the field. Electronic humidity sensors (Vaisala HMP series, Rotronic Hygroclip) offered ±2%RH accuracy and fast response. Temperature was measured by thermistors and RTDs. Analog output (0-1V, 4-20mA) allowed connection to strip chart recorders and early PLCs.
18.3 Digital Era (2000s-2010s)
The introduction of digital sensor chips (Sensirion SHT1x, SHT7x) integrated temperature and humidity sensing into a single package with digital output (I2C). RS485 Modbus communication became the standard for building automation. Low-cost sensors enabled widespread deployment in commercial buildings, data centers, and industrial facilities.
18.4 IoT Era (2010s-Present)
Modern sensors add: wireless communication (LoRa, NB-IoT, BLE), cloud connectivity, edge computing, and AI-based anomaly detection. KITOZER bridges traditional industrial RS485 with modern IoT: standard Modbus RTU sensor, connected via a gateway to cloud platforms. This protects customer investment while enabling smart building features.
19. Technical Deep Dive: Capacitive Humidity Sensor
19.1 Sensor Construction
The capacitive humidity sensor consists of: (1) a substrate (glass or silicon); (2) a bottom electrode (gold or platinum); (3) a humidity-sensitive polymer layer (acetate polymer); (4) a top porous electrode (gold or chromium). The polymer absorbs water vapor, changing its dielectric constant. The change in capacitance is proportional to relative humidity.
19.2 Measurement Circuit
The sensor capacitance is measured by an oscillator circuit. The SHT35 chip contains a capacitance-to-digital converter (CDC) that measures the sensor capacitance and converts it to a digital value. Internal calibration coefficients are applied to output temperature-compensated humidity.
19.3 Advantages and Limitations
Advantages: wide range (0-100%RH), good accuracy (±2%RH), low cost, fast response, temperature-compensated. Limitations: susceptible to condensation (water on the sensor causes saturation), chemical contamination (silicone vapors, corrosive gases damage the polymer), long-term drift (0.25%RH/year).
19.4 Protection Strategies
KITOZER protects the sensor element with: (1) a perforated plastic cap that blocks direct contact; (2) optional PTFE membrane that allows water vapor but blocks liquid water and chemicals; (3) a condensation heater (optional) that evaporates moisture when condensation is detected.
20. BMS and DCIM Integration
20.1 BMS Integration Protocol
KITOZER sensors integrate with major BMS platforms: Siemens Desigo, Schneider EcoStruxure, Honeywell EBI, Johnson Controls Metasys, Delta Controls, Trane Tracer. All support Modbus RTU natively. KITOZER provides pre-built BMS point lists and graphics templates.
20.2 DCIM Integration
DCIM platforms (Schneider EcoStruxure IT, Nlyte, Sunbird, PowerIQ) read sensor data via Modbus gateway or API. Sensor data is displayed on rack-level heat maps. Threshold alarms trigger DCIM tickets for maintenance.
20.3 Point List Example
| BMS Point Name | Source | Unit | Alarm High | Alarm Low |
|---|---|---|---|---|
| Temp-RowA-Rack1 | Sensor addr 1, reg 0x0000 | °C | 28 | 18 |
| Hum-RowA-Rack1 | Sensor addr 1, reg 0x0001 | %RH | 60 | 40 |
| DewP-RowA-Rack1 | Sensor addr 1, reg 0x0002 | °C | 15 | – |
| Temp-RowB-Rack1 | Sensor addr 2, reg 0x0000 | °C | 28 | 18 |
| Hum-RowB-Rack1 | Sensor addr 2, reg 0x0001 | %RH | 60 | 40 |
21. Maintenance Schedule
| Task | Frequency | Method |
|---|---|---|
| Visual inspection | Monthly | Check enclosure, wiring, LED status |
| Clean sensor cap | Quarterly | Remove cap, rinse, dry, reinstall |
| Verify readings vs reference | Quarterly | Compare with portable reference meter |
| Check bus communication | Quarterly | Review BMS comm error log |
| Full calibration | Annually | Two-point calibration at factory or on-site |
| Replace sensor element | Every 3-5 years | Swap SHT35 module |
| Check power supply | Annually | Measure voltage at sensor terminal |
| Update firmware | As needed | Download from gdlain.com, update via USB |
22. Cable Specification
For RS485 bus wiring, KITOZER recommends Belden 3105A or equivalent: 2 twisted pairs, 22AWG, shielded, PVC jacket. Color code: pair 1 (white/blue) = V+/GND, pair 2 (white/orange) = RS485 A/B. Maximum total cable length: 1200m at 9600bps, 400m at 38400bps, 100m at 115200bps. Use conduit for cable runs through power rooms. Maintain 20cm separation from 220V power cables.
23. Frequently Asked Questions: Additional Questions 91-100
Q91: Can I use a KITOZER sensor in a silent or vibration-sensitive environment?
A: Yes. The sensor has no moving parts (except the optional relay), so it operates silently. Vibration does not affect the MEMS sensor. DIN-rail mounting provides mechanical stability.
Q92: What is the difference between Modbus and BACnet?
A: Modbus is a simple register-based protocol, common in industrial and power applications. BACnet is a building automation protocol with rich object models, common in HVAC and BMS. KITOZER supports both (model-dependent).
Q93: Can the sensor be used in a marine environment?
A: Standard sensors are not rated for salt spray. For marine environments, use the conformal-coated version (PCB coated against corrosion), with stainless steel enclosure. Contact KITOZER for marine-grade options.
Q94: What is the recommended torque for terminal screws?
A: 0.4-0.6 Nm. Over-tightening strips the screw; under-tightening causes loose connections. Use a small Phillips screwdriver. Strip wire 7mm, insert fully, tighten.
Q95: Can I use the sensor with a 5V supply?
A: No. The minimum supply is 9VDC. Using 5V will cause unstable operation. Use a 12VDC or 24VDC supply. The 9-30VDC range allows flexible power options.
Q96: What is the difference between NEMA and IP ratings?
A: NEMA (National Electrical Manufacturers Association) is a US standard. IP (Ingress Protection) is an international standard. IP54 ≈ NEMA 12. IP65 ≈ NEMA 4. KITOZER uses IP ratings.
Q97: Can I paint the sensor cap?
A: No. The perforated cap must remain open for air flow. Painting blocks the holes and prevents accurate humidity measurement.
Q98: What is the expected lead time?
A: Standard models (KH-TH1, KH-TH2): 3-5 days from Guangzhou warehouse. Custom models: 2-3 weeks. Export shipping: 5-7 days by DHL/FedEx for samples, 25-30 days by sea for bulk.
Q99: Do you provide OEM/ODM service?
A: Yes. KITOZER provides OEM branding (your logo on the enclosure and packaging), custom firmware, and custom enclosure design. MOQ 100 units. Contact sales@gdlain.com for OEM program details.
Q100: Where can I download the datasheet and manual?
A: Visit gdlain.com, search for “temperature humidity sensor”, and download the PDF datasheet, user manual, Modbus register map, and configuration software. All documents are free.
24. Contact Us
KITOZER Industrial Product Line
Guangzhou Lian Intelligent System Development Co., Ltd.
Address: Chaotian Park, Zhongrun Industrial Zone, No.5 Huashan Road, Shilou, Panyu, Guangzhou, China
Tel: +86 18520668845 (WeChat same number)
WeChat: +86 13922289957
WhatsApp: +1 906-853-4140
Email: sales@gdlain.com
Web: gdlain.com (English international) | lain.com.cn (Chinese domestic)
For technical support, project inquiries, distribution partnership, or OEM requests, contact us. Our engineers respond within 24 hours.
Disclaimer: Specifications are subject to change without notice. Prices are reference prices for volume orders. KITOZER is a registered product line of Guangzhou Lian Intelligent System Development Co., Ltd.
25. Sensor Placement Best Practices
25.1 Height Considerations
The ideal sensor height for data center monitoring is 1.5 meters above the finished floor, corresponding to the breathing zone and the typical server rack intake height (1.2-1.5m). Placing sensors too low (below 0.5m) reads the cold air pool under raised floors. Placing too high (above 2m) reads the hot exhaust air at the ceiling. For rack-level monitoring, mount at the middle of the rack (1.2m) and at the top (2m) to measure vertical temperature gradient.
25.2 Distance from Heat Sources
Maintain at least 1 meter from: CRAC units, server exhaust grilles, UPS batteries, power distribution units, light fixtures, and direct sunlight. Heat sources create local temperature gradients that do not represent the overall room environment. A sensor placed next to a CRAC supply diffuser will read artificially low (18-20°C) while the actual rack intake is 24-26°C.
25.3 Airflow Considerations
The sensor needs free airflow to measure representative conditions. Do not mount inside closed cabinets (unless measuring cabinet interior), behind doors, under desks, or inside cable trays. The perforated sensor cap should face the room, not the wall. Allow 5cm clearance behind the wall-mount sensor for air circulation.
25.4 Redundancy
For critical data centers, use redundant sensors: two sensors per monitoring zone, on separate buses, from different manufacturers. If one sensor fails or drifts, the other provides backup. The BMS compares readings and alarms on discrepancy (more than 2°C or 5%RH difference).
25.5 Mapping with Floor Plans
Create a sensor layout map showing each sensor’s address, location, and coverage area. Use this map for: (1) installation verification; (2) troubleshooting when alarms trigger; (3) expansion planning. Update the map when sensors are moved or added.
26. RS485 Bus Design Principles
26.1 Daisy-Chain Topology
RS485 requires daisy-chain (linear) topology: the cable runs from the BMS to sensor 1, then to sensor 2, then to sensor 3, etc. Star topology (cable branches to each sensor) causes signal reflection and communication errors. If star topology is unavoidable, use an RS485 hub/repeater.
26.2 Termination
The RS485 bus requires a 120Ω termination resistor at the TWO ENDS of the bus: at the BMS end and at the last sensor. KITOZER sensors have a built-in termination switch (on DIN-rail models) or require an external 120Ω resistor at the last sensor. Do NOT add termination at intermediate sensors.
26.3 Bias Resistors
When no sensor is transmitting, the RS485 lines float, causing the BMS to read garbage. Bias resistors (560Ω pull-up on A, 560Ω pull-down on B) set the idle state. KITOZER sensors have optional bias resistor jumpers. Enable bias at ONE location on the bus (typically the BMS end).
26.4 Grounding
The cable shield must be grounded at ONE end only (BMS end). Grounding both ends creates a ground loop. If the shield must be grounded at both ends for EMC reasons, use a shield grounding block with a capacitor (100nF/1000V) to allow high-frequency grounding while blocking DC ground loops.
26.5 Isolation
For noisy environments (near VFDs, inverters, large motors), use isolated RS485 repeaters between segments. KITOZER optional isolated RS485 (2500V isolation) prevents ground loop currents and surge damage.
27. Alarm Configuration
27.1 Threshold Levels
Set alarm thresholds based on ASHRAE guidelines and equipment manufacturer specs. Typical data center thresholds: temperature high alarm at 27°C (warning), 32°C (critical); temperature low alarm at 18°C (warning); humidity high alarm at 60%RH (warning), 70%RH (critical); humidity low alarm at 40%RH (warning), 30%RH (critical). Set hysteresis of 1-2°C or 3-5%RH to prevent alarm chatter.
27.2 Alarm Priority
Differentiate alarm levels: (1) Warning – email to maintenance, no immediate action; (2) Critical – SMS + phone call to on-site engineer; (3) Emergency – automatic failover, generator start, customer notification. KITOZER sensors report digital alarm status via Modbus register 0x0030; the BMS implements the priority logic.
27.3 Alarm Delay
Configure a 60-300 second alarm delay to avoid false alarms from transient events (door opening, CRAC cycling). If the condition persists beyond the delay, trigger the alarm. This prevents nuisance alarms that operators learn to ignore.
27.4 Local Alarm Output
Optional relay output on KITOZER sensors triggers a local audible/visual alarm (beacon, buzzer) in the equipment room. This alerts on-site staff even when the BMS is unreachable. The relay is SPDT 30VDC/1A, wired to a local alarm horn.
28. Data Logging and Trend Analysis
28.1 Local Data Logger
The KH-TH5L model has 16MB internal flash, storing 1 million readings at configurable intervals (1 second to 1 hour). Data is timestamped (RTC battery-backed). Download via USB or Modbus. Useful for commissioning verification and temporary monitoring when the BMS is not yet operational.
28.2 BMS Trend Log
The BMS logs sensor data to a historical database. Typical logging interval: 1 minute for critical sensors, 5 minutes for general. Trend data is used for: (1) capacity planning; (2) identifying seasonal patterns; (3) correlating environmental conditions with equipment failures; (4) compliance reporting.
28.3 Trend Analysis
Analyze trends monthly: Is temperature drifting upward? Is humidity increasing (indicating a leak)? Are there periodic fluctuations (diurnal cycle)? Gradual changes indicate developing problems. KITOZER sensors’ long-term stability ensures trend data is meaningful.
29. Comparison with Competitors
| Feature | KITOZER KH-TH | Vaisala HMT120 | Siemens QFA3160 | Generic Chinese |
|---|---|---|---|---|
| Temp accuracy | ±0.3°C | ±0.3°C | ±0.4°C | ±0.5°C |
| Humidity accuracy | ±2%RH | ±2%RH | ±3%RH | ±5%RH |
| Communication | RS485 Modbus | RS485 Modbus | KNX/Modbus | RS485 Modbus |
| Display | LCD (optional) | No | No | LCD (optional) |
| Price (USD) | $25-200 | $300-500 | $150-250 | $10-50 |
| Warranty | 2 years | 2 years | 5 years | 1 year |
| Support | Chinese/English | English | English/German | Chinese |
| Availability | 3-5 days | 4-6 weeks | 2-4 weeks | 1-2 days |
KITOZER offers the best balance of accuracy, price, and availability. European brands offer longer warranty but at 3-5x the price. Generic sensors are cheap but accuracy and support are questionable.
30. Sensor Element Technology Comparison
30.1 Capacitive Polymer (SHT35/SHT45)
Pros: ±2%RH accuracy, digital output, temperature-compensated, low cost. Cons: susceptible to condensation and chemicals. Best for: normal indoor environments, data centers, offices.
30.2 Chilled Mirror Dew Point
Pros: highest accuracy (±0.1%RH), reference standard. Cons: expensive ($5000+), requires maintenance, slow response. Best for: calibration laboratories.
30.3 Wet/Dry Bulb Psychrometer
Pros: simple, no electronics. Cons: requires water supply, slow, requires manual reading. Best for: historical reference, not for modern monitoring.
30.4 Aluminum Oxide (Al2O3)
Pros: wide range, rugged, for high-temperature applications. Cons: drift requires frequent calibration, more expensive. Best for: industrial process monitoring.
31. Power Supply Design
31.1 Power Budget Calculation
Each KITOZER sensor draws up to 100mA at 24VDC. For a bus with 20 sensors: total current = 20 × 100mA = 2A. Add 50% margin: use a 24VDC 3A power supply. For 50 sensors: 5A supply. Mount the power supply in the BMS panel, not near the sensors.
31.2 Voltage Drop
On long power runs, voltage drop reduces the voltage at the sensor. For 22AWG cable, resistance is 54Ω/km. At 1A over 100m: voltage drop = 54 × 0.1 = 5.4V. Too much! Use thicker cable (18AWG) for long runs, or use local power supplies every 50 sensors.
31.3 Redundant Power
For critical installations, use redundant power supplies (N+1). Each supply can power the entire bus. A diode OR circuit combines the two supplies. If one fails, the other takes over without interruption.
31.4 Surge Protection
Add a TVS (transient voltage suppressor) on the power input at each sensor. KITOZER sensors have built-in TVS for 6kV surge protection. For outdoor or long cable runs, add external gas discharge tubes.
32. Enclosure and Mechanical Design
32.1 Wall-Mount Enclosure
The wall-mount enclosure is ABS plastic, 86×86×28mm, with IP54 rating. Four screw holes (M4) at the corners for wall mounting. Bottom cable entry via M16 conduit gland. The front cover snaps on, secured by one screw at the bottom. The LCD window is on the front (display models).
32.2 DIN-Rail Enclosure
The DIN-rail enclosure is 70×60×43mm, designed for 35mm DIN rail. A red metal clip at the bottom releases the sensor from the rail. Terminal blocks (5-pin, 3.5mm pitch) on the side for wiring. Ventilation slots on the side for air flow to the sensor element.
32.3 Duct-Mount Enclosure
The duct-mount has a 25mm diameter probe (150mm or 250mm length) with a stainless steel flange. The probe tip has a perforated PTFE cap protecting the sensor. The electronics enclosure is 100×80×40mm, mounted outside the duct. Cable entry via bottom gland.
32.4 Materials
Standard: ABS/PC plastic (UL94-V0 flame retardant). Optional: stainless steel 304/316 for washdown or corrosive environments. Optional: copper-free aluminum for aerospace clean rooms.
33. Configuration Software
33.1 Features
KITOZER provides free Windows configuration software (KITOZER Sensor Configurator). Features: (1) Auto-scan bus for connected sensors; (2) Read and display current measurements; (3) Configure address, baud rate, parity; (4) Set alarm thresholds; (5) Two-point calibration; (6) Firmware update; (7) Save/load configuration files; (8) Real-time trend graph.
33.2 System Requirements
Windows 7/10/11, 100MB disk space, one USB port. No installation required (portable application). .NET Framework 4.8 included. Chinese and English interface.
33.3 Download
Download from gdlain.com under “Support > Software”. The latest version is always free. Registration not required.
34. Quality Assurance and Testing
34.1 Production Testing
Every sensor undergoes: (1) Power-up test: verify LED and LCD; (2) Communication test: connect via RS485, verify response; (3) Measurement test: compare against reference instrument, within ±0.5°C/±3%RH; (4) Enclosure test: verify IP rating; (5) Label test: verify serial number and label.
34.2 Burn-In Test
Sample sensors (2% of production) undergo 24-hour burn-in at 40°C and 80%RH. Sensors that fail burn-in are rejected. This catches early failures.
34.3 Calibration Certificate
Each sensor ships with a calibration certificate showing the as-tested accuracy. The certificate is traceable to NIST via our reference standards. Calibration interval: 1 year.
35. Sensor Network Architecture
35.1 Single-Bus Small Network
For small installations (up to 32 sensors), a single RS485 bus connects all sensors to one BMS/DCIM controller. The BMS has an integrated RS485 port (or USB-RS485 adapter). Total bus length up to 1200m. This is the simplest and most cost-effective architecture.
35.2 Multi-Bus Large Network
For larger installations (32-256 sensors), use multiple RS485 buses, each with its own 32 sensors, connected to a BMS with multiple RS485 ports or an RS485-to-Ethernet gateway. Each bus is a separate segment with its own termination and power supply. This isolates failures and allows expansion.
35.3 Distributed IoT Network
For very large or geographically distributed sites, use RS485-to-LoRa/NB-IoT gateways. Sensors on RS485 buses connect to local gateways, which transmit data to a cloud platform over wireless. No cable between buildings. Ideal for multi-building campuses and remote sites.
35.4 Redundant Architecture
For mission-critical data centers, use dual-bus redundant architecture: every sensor connects to two independent RS485 buses, each with its own power supply and BMS. If one bus fails, the other continues. The BMS compares readings from both buses and alarms on discrepancy.
36. Modbus Register Deep Dive
36.1 Reading Temperature
To read temperature: send Modbus request: address (1 byte), function 04, register address 0x0000, quantity 2 registers (temperature and humidity), CRC. Response: address, function 04, byte count 4, temperature (INT16, ÷100), humidity (UINT16, ÷100), CRC. Example response: 01 04 04 09 C0 0F A0 CRC = 24.96°C, 40.00%RH.
36.2 Writing Alarm Threshold
To set temperature high alarm at 28°C: write register 0x0020 with value 2800 (28.00 × 100). Modbus request: address, function 06, register 0x0020, value 2800 (0x0AF0), CRC. The sensor stores the new threshold and uses it for alarm comparison.
36.3 Reading Alarm Status
Register 0x0030 is a bitmask: bit 0 = temp high alarm, bit 1 = temp low alarm, bit 2 = humidity high alarm, bit 3 = humidity low alarm, bit 4 = sensor error, bit 5 = supply low. Read register 0x0030 and check individual bits.
36.4 Sensor Identification
Registers 0x0100-0x0103 contain the serial number (32-bit). Register 0x0110 contains firmware version (e.g., 0x0105 = v1.05). These registers are read-only and help identify sensors in the field.
37. Installation Best Practices
37.1 Pre-Installation Checklist
Before installing, verify: (1) all sensors received and undamaged; (2) configuration software installed on PC; (3) USB-RS485 adapter available; (4) cable cut to length; (5) mounting hardware (screws, wall plugs); (6) sensor layout drawing; (7) reference calibration meter.
37.2 Mounting Sequence
Install from the BMS outward: mount the first sensor closest to the BMS, then the next, etc. This allows testing as you go. After each sensor, verify communication before moving to the next. This catches wiring errors early.
37.3 Labeling
Label each sensor with: (1) Modbus address; (2) location name (e.g., “Row A Rack 1”); (3) installation date. Use heat-shrink labels or engraved plastic tags. Label both ends of each cable. This makes future maintenance much easier.
37.4 Documentation
After installation, provide: (1) as-built sensor layout map; (2) Modbus address list; (3) alarm threshold table; (4) configuration file backup; (5) calibration certificates; (6) test report showing readings vs reference.
38. Troubleshooting Workflow
38.1 No Communication
Step 1: Check power LED on sensor. If off: check power supply, wiring, voltage at sensor. Step 2: Check RS485 wiring (A to A, B to B). Step 3: Verify baud rate and parity match BMS. Step 4: Check address uniqueness. Step 5: Check termination resistor. Step 6: Try a known-good sensor at the same location to isolate sensor vs cable.
38.2 Incorrect Readings
Step 1: Compare with reference instrument. Step 2: Check sensor placement (near heat source?). Step 3: Check if sensor cap is blocked. Step 4: Recalibrate. Step 5: If still off, replace sensor element.
38.3 Intermittent Communication
Step 1: Check cable connections (loose terminals). Step 2: Check for cable damage. Step 3: Add repeaters for long runs. Step 4: Reduce baud rate. Step 5: Check for EMI sources near cable.
38.4 Drifting Readings
Step 1: Compare with reference over 24 hours. Step 2: If drift exceeds 0.5°C/year, calibrate. Step 3: If drift continues, replace sensor element. Step 4: Check for chemical exposure.
39. Industry Standards
39.1 ASHRAE Guidelines
ASHRAE TC 9.9 recommends data center environmental envelope: A1 (18-27°C, 40-60%RH), A2 (10-35°C, 20-80%RH), A3 (5-40°C, 20-80%RH), A4 (5-45°C, 8-80%RH). KITOZER sensors support all classes.
39.2 ISO Standards
ISO 9001: quality management. ISO 14644: clean room classification. ISO 17251: hygrometer performance. KITOZER sensors comply with applicable standards.
39.3 CE and FCC
CE marking: EU EMC directive (EN 61000-6-2 industrial immunity, EN 61000-6-4 emissions). FCC: US Part 15 Class A. RoHS: lead-free, no restricted substances.
40. Data Center Case Study Example
A 500-server data center in Guangzhou deployed 60 KITOZER KH-TH1-L wall-mount sensors across 6 server rows. Sensors connected via 3 RS485 buses to a Schneider BMS. Installation took 3 days (2 technicians). After 6 months of operation, no sensor failures. The BMS detected 2 hot spots (at the top of rack rows 3 and 5), allowing targeted CRAC adjustment. Average PUE improved by 0.05. Sensor accuracy verified quarterly against a Fluke reference meter, average deviation 0.2°C/1.5%RH.
41. Environmental Monitoring Ecosystem
KITOZER temperature humidity sensors are part of a larger environmental monitoring ecosystem: (1) Temperature humidity sensor (this product); (2) Water leak detector; (3) Smoke detector; (4) Door contact; (5) Vibration sensor; (6) Power meter; (7) UPS monitor. All connect to the same BMS/DCIM platform. KITOZER provides the complete ecosystem for integrated data center monitoring.
42. Future Trends
42.1 AI-Powered Monitoring
Future sensors will include edge computing: on-sensor AI algorithms detect anomalies without BMS involvement. KITOZER is developing AI-ready sensors with local processing.
42.2 Energy Harvesting
Battery-free sensors powered by thermal energy harvesting or ambient light. Eliminates battery replacement. KITOZER is evaluating energy-harvesting options for wireless models.
42.3 Self-Calibrating Sensors
Future sensors will auto-calibrate against reference conditions (e.g., night-time stable temperature). Reduces maintenance. KITOZER is researching this technology.
43. Shipping and Packaging
Each sensor: anti-static bag + foam + color box (120×100×60mm). 50 units per carton (45×35×30cm, 12kg). Carton marked with product name, quantity, serial number range, and handling symbols. Export packaging includes: moisture barrier bag with desiccant, foam protection, carton with shipping marks. Sea freight: 20GP container holds ~5000 units.
44. After-Sales Support
Warranty: 2 years from shipment. Within warranty: free repair/replacement for manufacturing defects. Out of warranty: paid repair service. Technical support: email support@gdlain.com, response within 24 hours. Phone support: +86 18520668845 (Mon-Sat 9:00-18:00 China time). Spare parts: available for 7 years after product discontinuation.
45. Distributor Program
KITOZER offers a distributor program for system integrators and distributors. Benefits: (1) Discounted pricing (30-50% off list); (2) Marketing support (product images, datasheets, samples); (3) Technical training; (4) Lead sharing; (5) Regional exclusivity for qualified distributors. Contact sales@gdlain.com for distributor application.
46. Conclusion
The KITOZER temperature humidity sensor is a reliable, accurate, and cost-effective solution for data center environmental monitoring. With RS485 Modbus communication, ±0.3°C/±2%RH accuracy, multiple form factors, and 2-year warranty, KITOZER sensors meet the requirements of modern data centers, telecom facilities, and industrial environments. Contact KITOZER today for quotation and technical consultation.
47. Detailed Product Datasheet
47.1 KH-TH1 Wall-Mount Sensor
The KH-TH1 is the standard wall-mount temperature humidity sensor. It features a white ABS plastic enclosure (86×86×28mm), IP54 rating, and a perforated sensor cap. The LCD display (optional) shows temperature, humidity, and dew point. Power: 9-30VDC, 80mA. Communication: RS485 Modbus RTU. Cable entry: M16 bottom gland. Weight: 120g. Operating temperature: -40 to +85°C. Operating humidity: 0-100%RH non-condensing.
47.2 KH-TH2 DIN-Rail Transmitter
The KH-TH2 is a compact DIN-rail mount transmitter (70×60×43mm) designed for installation inside electrical cabinets and server racks. It clips onto standard 35mm DIN rail. Terminal block: 5-pin (V+, GND, A, B, optional analog out). The sensor element protrudes through a slot in the enclosure side. LED indicates power and communication. Weight: 100g.
47.3 KH-TH3 Duct-Mount Sensor
The KH-TH3 is designed for HVAC duct installation. The probe (25mm diameter, 150mm or 250mm length) inserts through a duct wall hole. The probe tip has a PTFE protective cap. The electronics enclosure (100×80×40mm) mounts outside the duct. LCD display (optional) on the enclosure face. Weight: 200g. IP65 rated.
47.4 KH-TH4 Remote Probe Sensor
The KH-TH4 features a remote probe connected by 2m shielded cable (extendable to 10m). The electronics enclosure (86×86×28mm) mounts in an accessible location. The probe (20mm diameter, 50mm length) with perforated cap is placed in the measurement zone. Available in plastic, stainless steel, or PTFE-coated versions. Weight: 150g.
47.5 KH-TH5 Premium LCD Sensor
The KH-TH5 is the premium wall-mount sensor with a larger LCD (128×64) with backlight, three configuration buttons, and optional 4-20mA analog output. The display cycles through: temperature, humidity, dew point, heat index. Buttons allow local configuration (address, alarm thresholds, display backlight). Weight: 150g.
48. Wiring Diagram Description
The wiring is straightforward: four wires from the BMS panel to each sensor. Wire 1 (red): V+ (24VDC). Wire 2 (black): GND. Wire 3 (yellow): RS485 A. Wire 4 (blue): RS485 B. Daisy-chain: from BMS V+/GND/A/B to sensor 1 terminal block, then continue from sensor 1 to sensor 2, etc. At the last sensor, install a 120Ω resistor between A and B. At the BMS, install a 120Ω termination and bias resistors.
49. Calibration Procedure
49.1 Two-Point Temperature Calibration
Step 1: Place the sensor in a temperature chamber at 0°C (ice water slurry). Wait 30 minutes for stabilization. Step 2: Read the reference thermometer. Enter the reference value in the configuration software. Step 3: Set the chamber to 50°C. Wait 30 minutes. Step 4: Enter the reference value. The software calculates the calibration offset and gain. Step 5: Save the calibration to the sensor.
49.2 Two-Point Humidity Calibration
Step 1: Place the sensor in a humidity chamber with saturated salt solution at 33%RH (MgCl2). Wait 2 hours. Step 2: Enter the reference value. Step 3: Change to 75%RH (NaCl). Wait 2 hours. Step 4: Enter the reference value. Step 5: Save. For field calibration, use a portable humidity calibrator.
49.3 Verification
After calibration, place the sensor in a normal room. Compare with a reference meter. Temperature should be within ±0.3°C, humidity within ±2%RH. If not, repeat the calibration or contact KITOZER support.
50. Alarm Notification Examples
When temperature exceeds 28°C at sensor address 5 (Row C Rack 2): BMS sends: (1) Email to maintenance team: “ALARM: Temperature 28.5°C at Row C Rack 2 (sensor 5). Threshold 28°C.” (2) SMS to on-site engineer: “Data center temp alarm Row C Rack 2, 28.5°C. Please investigate.” (3) WeChat message to the operations group. (4) Dashboard indicator turns red. When the temperature returns to normal, BMS sends a recovery notification.
51. Installation Tools Required
Basic tools: Phillips screwdriver (PH1), flathead screwdriver, wire stripper, crimping tool, drill with 6mm bit, level, measuring tape, label printer, USB-RS485 adapter, laptop with configuration software. Optional: cable tester, multimeter, reference calibration meter.
52. Common Installation Mistakes
(1) Star topology instead of daisy-chain: causes communication errors. (2) Missing termination resistor: causes signal reflection. (3) Reversed A/B wiring: no communication. (4) Sensor near heat source: inaccurate readings. (5) Over-tightened terminal screws: stripped screws. (6) No labels: impossible to troubleshoot. (7) No as-built documentation: future expansions difficult. (8) Power and data in same unshielded cable: EMI errors. (9) Sensor cap blocked by paint or tape: slow response. (10) No power supply margin: voltage drop at end of bus.
53. Sensor Lifecycle Management
Phase 1: Procurement (order, delivery, inspection). Phase 2: Installation (mount, wire, configure). Phase 3: Commissioning (verify readings, test alarms). Phase 4: Operation (monitor, trend, alarm). Phase 5: Maintenance (clean, calibrate, replace element). Phase 6: Decommissioning (remove, recycle, update documentation). KITOZER supports all phases.
54. Environmental Compliance
KITOZER sensors comply with: RoHS 2011/65/EU (lead-free), REACH (no SVHC), WEEE (recycling), CE (EMC), FCC (US emissions). The product packaging is 100% recyclable. Batteries (in data-logger models) are lithium coin cells, recyclable.
55. Comparison of Sensor Types by Installation Method
| Type | Best For | Pros | Cons |
|---|---|---|---|
| Wall-mount LCD | Room monitoring | Local display, easy to read | Visible on wall |
| DIN-rail | Inside cabinets | Compact, DIN rail | Not visible, needs cabinet slot |
| Duct-mount | HVAC ducts | Air measurement, IP65 | Requires duct hole |
| Remote probe | Hard-to-reach locations | Flexible placement | Probe cable limited to 10m |
| Premium LCD | Command centers | Local configuration, large display | Higher cost |
56. Data Center Environmental Requirements Detail
ASHRAE A1: 18-27°C, 40-60%RH, dew point 5-15°C. This is the recommended envelope for new data centers. A2: 10-35°C, 20-80%RH, for less critical facilities. KITOZER sensors measure all three parameters (temperature, humidity, dew point) and can alarm on any of them.
Equipment manufacturers specify operating ranges. Servers: typically 5-40°C, 8-80%RH. Storage: 10-35°C, 20-80%RH. Network switches: 0-40°C, 10-85%RH. KITOZER sensors should be configured to alarm before equipment limits are reached.
57. Networking: RS485 vs Ethernet vs Wireless
| Feature | RS485 Modbus | Ethernet TCP/IP | Wireless (LoRa) |
|---|---|---|---|
| Cable | Shielded twisted pair | Cat5e/Cat6 | None |
| Distance | 1200m | 100m (Ethernet) | 2-5km |
| Devices per bus | 32 | Unlimited | Unlimited |
| Cost per node | Low | Medium | Medium |
| Reliability | High | High | Medium |
| Power | 24VDC separate | PoE optional | Battery or solar |
| Best for | Wired data centers | Modern DCIM | Retrofit, multi-building |
58. Response to Common Customer Questions
Can I use KITOZER sensors with my existing BMS? Yes. KITOZER uses standard Modbus RTU, which all major BMS systems support. We provide point lists and integration support.
What is the minimum order quantity? 1 unit for standard models. 50 units for custom/OEM. Samples available for evaluation.
How long is the warranty? 2 years from shipment. Extended warranty (5 years) available.
Do you provide English documentation? Yes. All datasheets, manuals, and software are in English.
Can you ship internationally? Yes. We ship worldwide via DHL/FedEx (express) or sea freight (bulk). Export documentation provided.
59. Sensor Maintenance Checklist (Printable)
Monthly: (1) Check LED status on all sensors. (2) Review BMS alarm log for sensor errors. (3) Verify readings are reasonable (no stuck values).
Quarterly: (1) Clean sensor caps. (2) Compare readings with reference meter. (3) Check cable connections. (4) Review trend data for anomalies.
Annually: (1) Full calibration. (2) Check power supply voltage. (3) Update firmware. (4) Inspect enclosures for damage.
Every 3-5 years: (1) Replace sensor elements. (2) Check cable condition. (3) Plan for sensor replacement.
60. Final Remarks
KITOZER temperature humidity sensors are engineered for the rigors of data center environmental monitoring. With proven accuracy, robust design, and comprehensive support, KITOZER sensors provide the data foundation for reliable, efficient data center operation. Contact us today for your sensor requirements.
61. Extended FAQ: Questions 101-120
Q101: Can KITOZER sensors be used in 19-inch server racks directly?
A: Yes. The DIN-rail model clips onto a DIN rail mounted inside the rack. For rack-mounted monitoring, also consider KITOZER’s rack-mount sensor panel (1U) with multiple probe inputs.
Q102: What is the difference between a sensor and a transmitter?
A: A sensor measures the physical quantity. A transmitter converts the sensor signal to a standardized output (4-20mA, RS485, 0-10V). KITOZER products are transmitters (sensor + signal conditioning in one enclosure).
Q103: Can the sensor measure air velocity?
A: No. KITOZER temperature humidity sensors measure only temperature and humidity. For air velocity, use KITOZER’s anemometer (separate product).
Q104: What is the response time of the display?
A: The LCD updates every 1 second. The actual measurement is every 2 seconds. The display is not a real-time graph; it shows the current value.
Q105: Can I set the display to show only temperature?
A: Yes. Use the configuration software to select display mode: temperature only, humidity only, or alternating. The premium model’s buttons allow on-site selection.
Q106: What is the backlight lifetime?
A: LED backlight lifetime is 50,000 hours (about 5.7 years continuous). The backlight can be set to turn off after 60 seconds of inactivity to extend life.
Q107: Can the sensor be used in a low-oxygen environment?
A: Yes. The sensor measures humidity and temperature regardless of oxygen level. However, the electronics may be affected by corrosive gases. For oxygen-depleted or corrosive environments, use the stainless steel enclosure model.
Q108: What is the effect of altitude?
A: Altitude does not affect temperature measurement. Humidity measurement (relative humidity) is slightly affected by barometric pressure, but the effect is less than 0.5%RH at 3000m. Negligible for most applications.
Q109: Can I use the sensor with a solar-powered system?
A: Yes. The sensor draws only 80mA at 24VDC (1.9W). A small solar panel (10W) with battery can power it. For solar installations, use the low-power model with adjustable measurement interval (10 seconds to 1 minute).
Q110: What happens if the sensor is exposed to ESD?
A: KITOZER sensors have 8kV ESD protection on the RS485 and power inputs. ESD beyond this may damage the sensor. For ESD-prone environments, add external TVS diodes.
Q111: Can I change the sensor address by rotating a dial?
A: No. KITOZER uses software configuration (no DIP switches). This prevents accidental address changes. Use the USB configuration cable to set addresses.
Q112: What is the difference between accuracy and precision?
A: Accuracy: how close to the true value (±0.3°C). Precision: how repeatable the measurement (±0.05°C). KITOZER sensors are both accurate and precise.
Q113: Can I use the sensor in a sound-sensitive room?
A: Yes. The sensor has no moving parts and operates silently. The optional relay clicks when switching, but this is inside the enclosure and barely audible.
Q114: What is the MTBF calculation basis?
A: MTBF = 500,000 hours calculated per Bellcore TR-332, considering component derating, temperature, and environment. This is a theoretical value; actual field life is 5-8 years.
Q115: Can I paint the wall-mount enclosure to match the wall?
A: No. Painting blocks the ventilation slots and may damage the LCD window. Use the white or beige enclosure as-is. KITOZER offers custom colors for orders of 100+ units.
Q116: What is the sensor’s memory retention after power loss?
A: Configuration parameters (address, baud rate, alarm thresholds) are stored in non-volatile flash memory and retained for 100 years without power. The RTC (real-time clock) in data-logger models is battery-backed for 10 years.
Q117: Can the sensor be mounted on a ceiling?
A: Yes. The wall-mount sensor can be ceiling-mounted using the same screw holes. The sensor cap faces downward. Note: ceiling-mounted sensors measure the air at ceiling level, which may be hotter than breathing zone.
Q118: What is the maximum cable length for the 4-20mA output?
A: Up to 1000m with 24AWG. The 4-20mA loop is immune to voltage drop. Use a 250Ω resistor at the receiver to convert to 1-5V if needed.
Q119: Can I use shielded cable for the power wires?
A: Yes. Shielded cable is recommended. Ground the shield at the BMS end. Do not use the shield as a power conductor.
Q120: How do I dispose of a failed sensor?
A: Electronic waste. Recycle at an e-waste facility. The PCB contains lead-free solder. The plastic enclosure is ABS/PC, recyclable. Do not dispose in regular trash.
62. Extended FAQ: Questions 121-140
Q121: Can KITOZER sensors measure dew point directly?
A: Yes. The sensor calculates dew point from temperature and humidity, available at Modbus register 0x0002. Dew point is displayed on LCD models.
Q122: What is heat index?
A: Heat index combines temperature and humidity to indicate perceived temperature. KITOZER premium models display heat index. Not a critical parameter for data centers.
Q123: Can I use the sensor in a sauna or steam room?
A: No. The operating temperature is -40 to +85°C. Sauna temperatures (80-100°C) exceed the rating. Condensation in steam rooms will damage the sensor element.
Q124: What is the difference between IP54 and IP65?
A: IP54: dust-protected (limited ingress, no harmful deposit), splash-proof. IP65: dust-tight, water-jet protected. Wall-mount: IP54. Duct-mount: IP65.
Q125: Can I submerge the sensor in water?
A: No. Even IP65 is water-jet, not submersion. Submersion will damage the electronics. The humidity sensor element is for air measurement only.
Q126: What is the recommended storage condition?
A: Store sensors at -10 to +60°C, 20-80%RH, in the original packaging. Avoid direct sunlight, dust, and corrosive atmosphere. Shelf life: 2 years.
Q127: Can the sensor be used outdoors in a protective enclosure?
A: Yes. Place the sensor in a weatherproof enclosure with a sun shield and vent. The sensor measures the internal enclosure environment, which should approximate the outdoor air. Use the IP65 duct-mount model for outdoor installations.
Q128: What is the difference between a 2-wire and 4-wire sensor?
A: 2-wire: power and communication share the same wires (loop-powered). 4-wire: separate power and communication. KITOZER uses 4-wire (V+, GND, A, B) for reliable operation.
Q129: Can I use the sensor with a PLC’s analog input?
A: Yes. The 4-20mA output connects to a PLC analog input module. Temperature maps to 4-12mA, humidity to 12-20mA (or configurable). The PLC converts current to engineering units.
Q130: What is the scan time of the BMS?
A: Typical BMS scan: 1-5 seconds per sensor. For 60 sensors, one full scan takes 60-300 seconds. For faster updates, use multiple buses or high-speed polling.
Q131: Can I use the sensor with a wireless gateway?
A: Yes. Connect the RS485 output to a KITOZER wireless gateway (LoRa, NB-IoT, or Wi-Fi). The gateway transmits data to the cloud. No need to run network cable to each sensor.
Q132: What is the maximum number of sensors on one BMS?
A: Depends on the BMS capacity. Typical BMS supports 100-1000 Modbus points. With 2 points per sensor (temp + humidity), a 200-point BMS supports 100 sensors.
Q133: Can I use the sensor in a freezer warehouse?
A: Use the freezer model with internal heater (prevents condensation). Standard models may ice up. The sensor operates down to -40°C, but condensation on the sensor element when entering/leaving the freezer is the risk.
Q134: What is the power-on delay?
A: The sensor starts measuring within 1 second of power application. The first reading may be inaccurate during warm-up (allow 5 minutes for stabilization).
Q135: Can I use the sensor with a solar charge controller?
A: Yes. Connect the 24VDC output of the charge controller to the sensor. The sensor draws constant current, suitable for solar systems. Add a battery for overnight operation.
Q136: What is the difference between NTC and PTC?
A: NTC: resistance decreases with temperature. PTC: resistance increases. KITOZER uses digital sensors (SHT series) which internally use NTC elements but output calibrated digital data.
Q137: Can the sensor be used in a clean room with positive pressure?
A: Yes. Positive pressure does not affect sensor operation. The wall-mount model is suitable for clean rooms up to ISO 7.
Q138: What is the cable shield grounding recommendation?
A: Ground at the BMS end only. If the BMS panel is not grounded, ground the shield at the nearest earth point. Do not leave the shield unconnected (it acts as an antenna).
Q139: Can I use the sensor with a 12V battery backup?
A: Yes. The sensor operates from 9-30VDC, so a 12V battery works. Battery life: 12V 7Ah battery / 0.08A = 87.5 hours. Add a solar panel for extended operation.
Q140: What is the sensor’s weight in shipping package?
A: Gross weight per unit: 200g (including box and accessories). Carton of 50 units: 12kg.
63. Extended FAQ: Questions 141-150
Q141: Can I use KITOZER sensors with Building Management System software?
A: Yes. KITOZER sensors are compatible with all major BMS platforms via Modbus RTU. We provide integration support.
Q142: What is the expected delivery time for samples?
A: Samples ship within 1-2 days from Guangzhou. International delivery: 3-5 days by DHL/FedEx.
Q143: Can I get a custom logo on the sensor?
A: Yes. OEM service: your logo on the enclosure and packaging. MOQ 100 units. Lead time 2-3 weeks.
Q144: What is the sensor’s operating pressure range?
A: The sensor is designed for atmospheric pressure (80-110 kPa). It is not pressure-rated for pressurized ducts or vessels. For pressurized applications, use a pressure-sealed probe fitting.
Q145: Can I use the sensor in a kitchen or cooking area?
A: Not recommended. Oil vapors contaminate the humidity sensor element, causing drift. For kitchen monitoring, use a stainless steel enclosure with PTFE-protected probe, and replace the sensor element every 6 months.
Q146: What is the Modbus slave address range?
A: 1-247. Address 0 is broadcast (write-only, no response). KITOZER recommends 1-32 for the first bus, 33-64 for the second bus, etc.
Q147: Can the sensor be used in a laboratory fume hood?
A: Yes, but the sensor element may be damaged by chemical vapors. Use the PTFE-protected probe and inspect monthly. Replace the sensor element every 6 months in chemical environments.
Q148: What is the difference between a relative humidity sensor and a dew point sensor?
A: Relative humidity sensor measures %RH. Dew point sensor measures the dew point temperature directly (using a chilled mirror). KITOZER measures %RH and calculates dew point. A true dew point sensor is more accurate but much more expensive.
Q149: Can I use the sensor in a wine cellar?
A: Yes. Wine cellars require 12-16°C, 60-70%RH. KITOZER wall-mount sensors are suitable. The high humidity (70%RH) is within the sensor’s range.
Q150: What is the warranty on the sensor element?
A: The sensor element (SHT35/SHT45) is covered under the 2-year warranty. After 2 years, sensor element replacement is available as a spare part (¥80/piece).
64. Sensor Calibration and Uncertainty
64.1 Measurement Uncertainty Budget
The total measurement uncertainty of a KITOZER sensor includes: (1) Sensor element accuracy: ±0.3°C / ±2%RH; (2) ADC resolution: ±0.05°C / ±0.1%RH; (3) Calibration reference uncertainty: ±0.1°C / ±0.5%RH; (4) Drift since last calibration: ±0.1°C / ±0.25%RH/year; (5) Environmental effects: ±0.1°C / ±0.3%RH. Combined uncertainty (k=2): ±0.35°C / ±2.1%RH. This is the guaranteed accuracy specification.
64.2 Traceability
KITOZER calibration reference standards are calibrated annually by a national metrology institute (NIM China). The calibration chain: sensor → KITOZER reference → NIM reference → SI unit. This ensures KITOZER measurements are internationally comparable.
65. Sensor Integration with Building Automation
65.1 BACnet MS/TP Implementation
KITOZER high-precision models support BACnet MS/TP on RS485. BACnet objects: Analog Input 1 (temperature), Analog Input 2 (humidity), Analog Input 3 (dew point). Device object: vendor ID, model name, firmware version. Configuration via BACnet WriteProperty or KITOZER configuration software.
65.2 Modbus to BACnet Gateway
For BACnet/IP systems without MS/TP, use a Modbus-to-BACnet gateway (e.g., HMS Anybus, Contemporary Controls). The gateway maps Modbus registers to BACnet objects. KITOZER provides the register mapping file for common gateways.
66. Sensor Data Visualization
66.1 Trend Graphs
The BMS displays sensor data as trend graphs: X-axis = time (hour/day/week), Y-axis = temperature (°C) and humidity (%RH). Graphs help identify: daily cycles, seasonal changes, equipment correlations, and gradual drifts.
66.2 Heat Maps
Data center DCIM platforms display floor-plate heat maps: colored zones based on sensor readings. Red = hot, green = normal, blue = cold. Heat maps help identify hot spots and optimize CRAC placement.
66.3 Dashboards
Operations dashboards show: current temperature/humidity at key locations, alarm status, historical trends, and compliance status. Dashboards are displayed in the NOC (Network Operations Center) for real-time monitoring.
67. Sensor Security
67.1 Network Security
KITOZER sensors are on the BMS network, which is typically isolated from the internet. For IoT-connected models, use VPN, firewall, and strong passwords. The sensor firmware can be password-protected to prevent unauthorized configuration changes.
67.2 Physical Security
Wall-mount sensors can be secured with a tamper screw (Torx T10). DIN-rail sensors inside locked cabinets are physically secure. Duct sensors are outside the occupied space. Physical access control prevents sensor tampering.
68. Sensor Lifecycle Cost Analysis
Total cost of ownership over 5 years for a KITOZER sensor: Purchase ¥280 + Installation ¥150 + Calibration (5×¥100) ¥500 + Sensor element replacement (¥80) = ¥1,010. Per year: ¥202. Compare to a European brand: Purchase ¥2,000 + Installation ¥150 + Calibration (5×¥200) ¥1,000 = ¥3,150. Per year: ¥630. KITOZER saves 68% over 5 years.
69. Sensor Deployment Planning
69.1 Site Survey
Before deployment, conduct a site survey: measure the room, identify heat sources, plan sensor locations, plan cable routes, identify power supply location. Output: sensor layout drawing, cable schedule, bill of materials.
69.2 Bill of Materials
For a 60-sensor deployment: 60× KH-TH1-L sensors (¥16,800), 1× USB-RS485 kit (¥250), 1000m Belden 3105A cable (¥3,000), 60× terminal blocks (¥300), 10× 120Ω resistors (¥50), 3× 24VDC power supplies (¥600), mounting hardware (¥200). Total: ¥21,200.
69.3 Installation Schedule
Day 1: Cable running. Day 2: Sensor mounting and wiring. Day 3: Configuration and commissioning. Day 4: Verification and documentation. Total: 4 days for 2 technicians.
70. Sensor Performance in Extreme Conditions
70.1 High Temperature
The sensor operates up to 85°C. At 85°C, humidity accuracy degrades to ±5%RH (not guaranteed). For high-temperature environments, use the industrial model (up to 125°C).
70.2 Low Temperature
The sensor operates down to -40°C. At -40°C, humidity measurement is not meaningful (air is very dry). The sensor continues to report temperature accurately.
70.3 High Humidity
At 100%RH, condensation may form on the sensor element. The SHT35 sensor can recover from condensation (after drying). For sustained high humidity, use the condensation-heater model.
71. Sensor Comparison Table: All Models
| Model | Mount | Display | Output | Accuracy | IP | Price |
|---|---|---|---|---|---|---|
| KH-TH1-S | Wall | No | RS485 | ±0.3°C/±2%RH | IP54 | ¥150 |
| KH-TH1-L | Wall | LCD | RS485 | ±0.3°C/±2%RH | IP54 | ¥280 |
| KH-TH2-D | DIN-rail | No | RS485 | ±0.3°C/±2%RH | IP20 | ¥180 |
| KH-TH3-D | Duct | No | RS485 | ±0.3°C/±2%RH | IP65 | ¥450 |
| KH-TH3-L | Duct | LCD | RS485 | ±0.3°C/±2%RH | IP65 | ¥680 |
| KH-TH4-R | Remote | No | RS485 | ±0.3°C/±2%RH | IP54 | ¥380 |
| KH-TH5-P | Wall | LCD+buttons | RS485+4-20mA | ±0.3°C/±2%RH | IP54 | ¥850 |
| KH-TH5-H | Wall | LCD | RS485 BACnet | ±0.1°C/±1.5%RH | IP54 | ¥1,200 |
| KH-TH5-E | Wall | LCD | Ethernet TCP | ±0.3°C/±2%RH | IP54 | ¥1,500 |
72. Final Conclusion
The KITOZER temperature humidity sensor series provides comprehensive environmental monitoring solutions for data centers, industrial facilities, and commercial buildings. With accurate measurement (±0.3°C/±2%RH), reliable RS485 Modbus communication, multiple form factors, and competitive pricing (¥150-¥1,500), KITOZER sensors meet the diverse needs of modern monitoring applications. Backed by 2-year warranty, English-language support, and Guangzhou manufacturing, KITOZER is your trusted partner for environmental sensing. Contact us at sales@gdlain.com or Tel +86 18520668845 for quotation.
73. Sensor Application Notes
73.1 Mounting in Raised Floor Environments
Data centers with raised floors have cold air plenum under the floor. Do NOT mount sensors under the floor (they measure plenum air, not room air). Mount sensors at 1.5m height on the rack rows. If measuring plenum air, use a separate duct sensor installed through a floor tile.
73.2 Hot Aisle/Cold Aisle Configuration
In hot/cold aisle containment, mount sensors at the cold aisle intake (front of racks) to measure the air entering servers. Also mount sensors in the hot aisle (rear of racks) to measure exhaust temperature. The temperature difference between cold and hot aisle indicates cooling efficiency.
73.3 Server Rack Temperature Stratification
Without containment, hot exhaust from racks mixes with cold supply air. Temperature at the top of a rack can be 5-10°C higher than at the bottom. Mount sensors at multiple heights (bottom 0.5m, middle 1.2m, top 2m) to measure stratification.
73.4 CRAC Unit Monitoring
Install duct sensors on CRAC supply and return air. Monitor: supply air temperature (should be 15-18°C), return air temperature (should be 22-27°C), supply humidity (should be 40-50%RH). Deviations indicate CRAC problems.
73.5 Battery Room Monitoring
UPS battery rooms require 20-25°C for battery longevity. High temperature (above 25°C) reduces battery life by 50% for every 10°C rise. KITOZER DIN-rail sensors monitor battery room temperature with high-low alarms.
73.6 Cable and Wiring
Use proper cable management: conduit or cable trays. Do not run sensor cables parallel to power cables. Maintain 20cm separation. Use corner pulls for bends. Label both ends. This ensures reliable communication and easy troubleshooting.
74. Sensor FAQ: Quick Reference
Q: What accuracy? A: ±0.3°C, ±2%RH standard; ±0.1°C, ±1.5%RH high-precision.
Q: What output? A: RS485 Modbus RTU standard; optional 4-20mA, 0-10V, Ethernet TCP.
Q: What power? A: 9-30VDC, 80-100mA.
Q: What range? A: -40 to +125°C, 0-100%RH.
Q: How long is the warranty? A: 2 years.
Q: How much? A: ¥150-¥1,500 ($21-210) depending on model.
Q: How to configure? A: Free Windows software via USB-RS485 adapter.
Q: What is the lead time? A: 3-5 days standard, 2-3 weeks custom.
Q: Can you ship internationally? A: Yes, worldwide via DHL/FedEx.
Q: How to contact? A: sales@gdlain.com, Tel +86 18520668845, WeChat +86 13922289957.
75. Summary
KITOZER temperature humidity sensors are the foundation of data center environmental monitoring. This encyclopedia covers product definitions, working principles, technical parameters, models, installation, commissioning, calibration, maintenance, troubleshooting (150 FAQ), applications, pricing, and brand advantages. For further information, visit gdlain.com or contact KITOZER directly.
76. Sensor Technical Specifications Summary
Temperature: range -40 to +125°C, accuracy ±0.3°C (standard) / ±0.1°C (high-precision), resolution 0.01°C. Humidity: range 0-100%RH, accuracy ±2%RH (standard) / ±1.5%RH (high-precision), resolution 0.01%RH. Dew point: calculated from temperature and humidity, range -40 to +40°C. Supply: 9-30VDC, reverse polarity protected. Current: 80mA typical, 100mA max. Communication: RS485 Modbus RTU, baud 1200-115200, 8N1/8E1/8O1. Optional: 4-20mA (2 channels), 0-10V, Ethernet Modbus TCP, BACnet MS/TP. Display: LCD 128×64 (wall-mount models), optional backlight. Operating: -40 to +85°C, 0-100%RH non-condensing. IP: IP20 (DIN-rail), IP54 (wall), IP65 (duct). Dimensions: 86×86×28mm (wall), 70×60×43mm (DIN), 100×80×40mm (duct). Weight: 100-200g. Warranty: 2 years.
77. Sensor Ordering Information
To order: specify model number (e.g., KH-TH1-L), quantity, delivery address, and contact person. KITOZER accepts: T/T bank transfer, PayPal, Western Union. Proforma invoice provided. Lead time: 3-5 days for stock models, 2-3 weeks for custom. Shipping: DHL/FedEx (express, 3-5 days) or sea freight (bulk, 25-30 days). Export documentation: commercial invoice, packing list, certificate of origin.
78. Sensor Support Resources
Download from gdlain.com: (1) Product datasheet PDF; (2) User manual PDF; (3) Modbus register map; (4) Configuration software (Windows); (5) CAD drawings (DWG/DXF); (6) 3D models (STEP); (7) BACnet PICS; (8) CE/FCC certificates; (9) Calibration certificate template. All resources are free. Technical support: email support@gdlain.com, response within 24 hours. Phone: +86 18520668845 (Mon-Sat 9:00-18:00 China time).
79. Sensor Contact Information
KITOZER Industrial Products
Guangzhou Lian Intelligent System Development Co., Ltd.
Address: Chaotian Park, Zhongrun Industrial Zone, No.5 Huashan Road, Shilou, Panyu, Guangzhou, China
Tel: +86 18520668845 (WeChat same)
WeChat: +86 13922289957
WhatsApp: +1 906-853-4140
Email: sales@gdlain.com
Web: gdlain.com (English) | lain.com.cn (Chinese)
80. Sensor Installation Verification Checklist
After installation, verify: (1) All sensors powered (LED on). (2) All sensors communicating via BMS. (3) Readings within ±0.5°C/±3%RH of reference. (4) Alarm thresholds configured correctly. (5) Alarm test: simulate high temperature, verify BMS alarm. (6) All sensors labeled with address and location. (7) Cable connections tight. (8) Termination resistor installed. (9) Power supply voltage at sensor within 24VDC ±10%. (10) Documentation provided to customer. Sign off the commissioning report.
81. Sensor Maintenance Record Template
Each sensor should have a maintenance record: date, task performed, reading before/after, technician name, next maintenance date. Track: monthly visual inspection, quarterly cleaning, quarterly reading comparison, annual calibration, sensor element replacement. This record proves compliance and helps plan maintenance.
82. Sensor Spare Parts List
Recommended spares for a 60-sensor installation: 6 spare sensors (10%), 3 sensor elements (SHT35 modules), 1 USB-RS485 adapter, 1 roll of Belden 3105A cable (100m), 50 terminal blocks, 10 120Ω termination resistors, 10 M16 cable glands, 1 roll of heat-shrink labels. Total spare cost: approximately ¥3,000.
83. Sensor Warranty Policy
KITOZER warrants sensors to be free from defects in materials and workmanship for 2 years from the date of shipment. Warranty covers: repair or replacement of defective units, free of charge. Warranty does not cover: water damage, physical damage, incorrect installation, unauthorized modification, normal wear and tear. To claim warranty: contact support@gdlain.com with serial number and description. RMA number provided. Ship defective unit to KITOZER Guangzhou address. Replacement shipped within 5 days of receipt.
84. Final Disclaimer
Specifications are subject to change without notice. Prices are reference prices for volume orders and may vary. KITOZER is a product line of Guangzhou Lian Intelligent System Development Co., Ltd. All trademarks are property of their respective owners. This document is for informational purposes and does not constitute a contract. Contact KITOZER for the latest datasheet and quotation.
85. About KITOZER
KITOZER is the industrial product brand of Guangzhou Lian Intelligent System Development Co., Ltd., founded in 2004 and based in Panyu, Guangzhou. KITOZER designs and manufactures environmental monitoring sensors, data center infrastructure products, and intelligent building systems. With over 20 years of engineering experience, KITOZER serves data centers, telecom operators, industrial facilities, and commercial buildings across China and internationally. Products include: temperature humidity sensors, water leak detectors, fresh air systems, humidifiers, dehumidifiers, and integrated monitoring solutions. KITOZER is committed to quality, reliability, and customer support.