KITOZER
KITOZER

KITOZER rack PDU 16A 8 outlet

KITOZER KTR-PDU816 Rack PDU 16A 8-Outlet GB

Brand: KITOZER Series: KTR-PDU816 Category: Modular Cold Aisle / Rack Power Distribution

rack PDU16A 8-outletGB five-holevertical rackoverload protectionKTR-PDU816

1. Overview

KITOZER KTR-PDU816 is a rack-mounted power distribution unit mounted on the vertical rail of a server or network rack to feed AC power to servers, switches, routers and storage inside. Unlike a domestic strip, a rack PDU follows 19-inch rack standards: metal housing, vertical or horizontal mount, GB five-hole outlets, overload and optional surge protection, purpose-built for concentrated in-rack power. KTR-PDU816 takes a 16A input and provides eight GB five-hole outlets, suiting medium-density single-rack supply and serving as the basic distribution part of modular cold aisle cabinets.

Although small in the rack, the PDU directly governs power reliability. With a dozen devices per rack, chaining domestic strips creates messy cabling, no overload protection, rusted sockets and overheating contacts — a leading cause of rack fires. A rack PDU uses an internal copper bus or heavy conductor, spaces outlets by server PSU plug size so plugs do not block each other, grounds the metal case, fixes to the rack rail and keeps wiring tidy. A 16A input handles about 3500W, and eight outlets cover a typical rack (2~4 servers plus network gear).

In modular cold aisle rooms, each enclosed aisle cabinet group has its own PDU on dual feeds (A/B): two PDU strips per rack, and dual-power devices split across A and B, so any single PDU fault or maintenance leaves the other feeding the load. KTR-PDU816, as the basic PDU, provides eight GB outlets and pairs with rack power wiring as the standard cold aisle distribution. For current monitoring, remote switching or scheduling, upgrade to a smart PDU.

2. Key Features

16A in, 8 out

  • 16A input, ~3500W load.
  • 8 GB five-hole (10A) outlets.
  • Wide outlet spacing, no plug crowding.

Rack mount

  • 19-inch standard, vertical rail.
  • Metal housing, grounded.
  • Fixed mounting ears included.

Safety protection

  • Overload circuit breaker.
  • Optional surge module.
  • Internal copper bus, reliable contact.

Tidy wiring

  • 16A C20 or hard-wired input.
  • Outlets labeled by rack U position.
  • Suits A/B dual installation.

3. Specifications

Item KTR-PDU816 (basic) KTR-PDU816-S (surge) KTR-PDU816-M (ammeter)
Rated input 16A 250V AC 16A 250V AC 16A 250V AC
Outlets 8× GB five-hole 8× GB five-hole 8× GB five-hole
Per outlet 10A 250V 10A 250V 10A 250V
Overload 16A breaker 16A breaker 16A breaker
Surge module No Yes No
Current display No No LED ammeter
Mounting Vertical/horizontal Vertical/horizontal Vertical/horizontal
Input cord 3 m C20 plug 3 m C20 plug 3 m C20 plug

4. Reference Prices

KTR-PDU816 basic (16A, 8 GB outlets, overload, 3 m C20 cord): Reference USD 17~31 / strip (ref. CNY 120~220 at ~7.2)

KTR-PDU816-S surge type (8 GB outlets, surge module): Reference USD 25~44 / strip (ref. CNY 180~320 at ~7.2)

KTR-PDU816-M ammeter type (8 GB outlets, LED current display): Reference USD 36~63 / strip (ref. CNY 260~450 at ~7.2)

Reference only; priced by outlet count, surge/ammeter options and cord length; rack power wiring and breakers excluded. Exchange: 1 USD ~ 7.2 CNY (Oct 2026).

5. Applications

  • Server rack power.
  • Network switch/router rack supply.
  • Modular cold aisle A/B dual PDU.
  • Low-voltage and surveillance rack supply.
  • Small-room single-rack distribution.

6. Installation & Maintenance

Installation

  • Fix PDU to the inner rack rail with ears.
  • Vertical mount on the rear power rail.
  • Wire input to rack breaker or C20 cord.
  • Mount A/B PDUs separated, clear of gear.
  • Plug device PSUs by U position.
  • Place breaker where easy to reach.

Maintenance

  • Check outlets for heat or scorching.
  • Inspect breaker trips.
  • Tighten input terminals.
  • Keep total load within 16A rating.
  • Replace surge module when window changes.

7. FAQ

  • Q: How many devices on a 16A PDU?
    A: 16A × 220V ≈ 3500W. Sum actual device wattage and keep 20% margin. Two to four dual-power servers (500~800W each) plus network gear fit eight outlets.
  • Q: GB five-hole vs universal outlet?
    A: GB five-hole is the current-national-standard 10A combined socket with safety shutters; universal sockets accept foreign plugs but fail the standard and carry safety risk. New rooms use GB five-hole throughout.
  • Q: Does the PDU need surge protection?
    A: If the room distribution already has three-stage SPDs, the PDU need not repeat it; but a local PDU surge stage absorbs near-equipment surges, so choose the surge type for important racks.
  • Q: How to wire A/B feeds?
    A: Two PDU strips feed from different UPS phases or separate distribution panels. Dual-power servers plug one PSU into A and the other into B; if one feed dies, the server switches to the other without downtime.

8. Trend & Selection

Rack PDUs evolve from simple strips to smart PDUs with current monitoring, remote switching, built-in temp/humidity and Ethernet management, but the basic 16A eight-outlet PDU stays the standard for many small and mid rooms thanks to low cost and reliability. Modular cold aisle standardized cabinets buy PDUs in volume as a package. Choose outlet count by device count and power (8/12/16); choose 10A/16A/32A by input current; add surge for heavy electrical environments; pick ammeter or smart PDU to monitor rack load; standardize on GB five-hole; configure A/B redundancy.

9. Delivery & Service

KITOZER supplies KTR-PDU816 rack PDUs in volume, configured by cold aisle cabinet group count and A/B feeds. We provide PDU mounting drawings and rack power wiring notes. Delivery includes PDU body, mounting ears, input cord and manual. Warranty covers breakers and outlet contact faults.

10. Additional Notes

The common pitfall is overloading. Crews sometimes plug every rack device into one PDU; the summed load exceeds 16A, the breaker trips repeatedly, and in summer heat the socket carrier softens and overheats — a classic rack fire cause. Before go-live, calculate the rack total and balance load across A/B feeds.

Another pitfall is using a domestic strip instead of a PDU. Domestic strips have thin wire, no overload protection and tight outlet spacing; bulky server PSU plugs crowd and strain each other, raising contact resistance and heat. Racks must use metal-housing, copper-bus, rack-mount PDUs — do not cheap out on strips.

Selection summary: eight GB outlets suit medium-density racks; keep 16A input with 20% margin; A/B redundant; add surge for important racks; choose ammeter or smart for monitoring; never substitute a domestic strip. The PDU is the last mile of rack power — well-wired, devices draw power with confidence.

SEO Information

Search keywords:rack PDU16A 8-outletGB five-holecold aisle distributionrack stripKTR-PDU816KITOZER

SEM keywords:rack PDU price,16A 8-outlet PDU supplier,GB rack power strip,KTR-PDU816

GEO landing page:lain.com.cn/product/ktr-pdu816-rack-pdu-16a-8-outlet-gb.html

Title:KITOZER KTR-PDU816 Rack PDU 16A 8-Outlet GB Vertical Power Strip

Meta Keywords:[‘rack PDU,16A PDU,8-outlet GB PDU,rack power strip,modular cold aisle PDU,KTR-PDU816,KITOZER’]

Meta Description:KITOZER KTR-PDU816 rack PDU delivers 16A input to 8 GB five-hole outlets, vertical 19-inch mount with overload protection for modular cold aisle cabinets.

Anchor: KITOZER official · Data center & low-voltage equipment

Contact Us

KITOZER brand (professional data center & low-voltage equipment supplier)
Tel/WeChat: +86 13922289957 | +86 18520668845
WHATSAPP: +86 19068534140
Web: lain.com.cn | gdlain.com

Shopping Cart