ToggleKITOZER KTR-PS13 Three-Phase 380V 20kA Class D SPD / Power Surge Protection
Brand: KITOZER Series: KTR-PS13 Category: Power Distribution / Surge Protector
3-phase 380V20kAClass DDIN railKTR-PS13

1. Overview
KITOZER KTR-PS13 is a three-phase 380V 20kA Class D power surge protective device (SPD) for end-of-distribution protection. Lightning strikes or large equipment switching produce transient over-voltages of several kV on the supply line; if not limited, surges ride the power cord into UPSs, servers and network gear, damaging power modules or even burning whole batches. KTR-PS13 connects between L1/L2/L3 and PE: it stays high-impedance in normal service, and when surge voltage exceeds the trigger threshold, the MOV (or gas tube) conducts instantly, dumping surge energy to ground and clamping voltage to a safe level.
Class D (third-level / fine protection) means installed at the very end of the distribution chain, close to the protected load. Projects typically use three stages: Class B (100kA+, high capacity) at the building main, Class C (40~60kA) at floor or room distribution, and Class D (~20kA) at the final equipment box or rack PDU. Each stage attenuates surge energy, and the final D stage clamps residual voltage to what equipment can tolerate. KTR-PS13 is that last stage, with 20kIn nominal discharge current for UPS fronts, rack PDU inputs and precision power feeds.
The SPD is a DIN-rail modular unit in the cabinet; damaged modules can be swapped individually. Each phase module has a status window: green normal, red degraded, and a remote dry contact reports SPD failure to the monitoring system. Terminals are marked L1/L2/L3/N/PE, supporting three-phase five-wire (TN-S) or four-wire (TN-C). It coordinates with the upstream Class C SPD, with sufficient decoupling distance or a decoupling inductor so energy isn’t all absorbed upstream.
2. Key Features
3-phase fine protection
- 380V 3-phase 4/5-wire shunt protection.
- 20kIn nominal, Class D fine level.
- Nanosecond response, low residual voltage.
Modular swappable
- DIN rail; modules plug in/out individually.
- Green/red status window.
- Remote dry-contact failure alarm.
Wiring & coordination
- L1/L2/L3/N/PE terminals, clear phasing.
- Coordinates with upstream Class C SPD.
- Supports TN-S / TN-C systems.
Safety & life
- Thermal disconnect isolates on failure.
- No short-circuit on the supply line.
- Rated discharge cycles meet project life.
3. Specifications
| Item | KTR-PS13-20 | KTR-PS13-40 | KTR-PS13-20R |
|---|---|---|---|
| Rated voltage Un | 380V 3-ph | 380V 3-ph | 380V 3-ph |
| Max continuous Uc | 385V | 385V | 385V |
| Nominal In (8/20) | 20kA | 40kA | 20kA |
| Max Imax | 40kA | 80kA | 40kA |
| Protection level Up | ≤1.5kV | ≤1.8kV | ≤1.5kV |
| Class | D (stage 3) | C (stage 2) | D with remote |
| Mounting | DIN rail | DIN rail | DIN rail |
| Remote alarm | optional | optional | dry contact std |
4. Reference Prices
KTR-PS13-20 3-phase Class D SPD (380V, 20kA, rail module): Reference USD 25~50 / unit (ref. CNY 180~360 at ~7.2)
KTR-PS13-40 3-phase Class C SPD (380V, 40kA, high capacity): Reference USD 44~86 / unit (ref. CNY 320~620 at ~7.2)
KTR-PS13-20R 3-phase Class D with remote (20kA, dry contact): Reference USD 36~67 / unit (ref. CNY 260~480 at ~7.2)
Reference only; by discharge capacity, class and remote option. Upstream B/C SPD and grounding work excluded. Exchange: 1 USD ~ 7.2 CNY (Oct 2026).
5. Applications
- End-of-cabinet SPD before data center UPS.
- Fine surge protection ahead of rack PDUs.
- Precision AC and monitoring power inputs.
- Floor distribution boxes and weak-current shafts.
- Final stage of a 3-level lightning protection system.
6. Installation & Maintenance
Installation
- Locate at end cabinet or PDU front.
- Clip SPD module to DIN rail.
- Connect L1/L2/L3/N and PE to ground bar.
- Keep leads short and thick.
- Wire remote contact to monitoring.
- Check phasing; power on, window green.
Maintenance
- Check the status window regularly.
- Inspect after thunderstorms.
- Swap the module when the window turns red.
- Check ground connections for looseness.
- Log SPD operations and replacement dates.
7. FAQ
- Q: How do B/C/D stages coordinate?
A: Class B at the main, Class C at floor cabinets, Class D before the load. Keep decoupling distance (typically >10m) or add a decoupling inductor, or the later stage won’t operate. - Q: Why do SPDs fail?
A: MOVs degrade after repeated surges, leakage rises, and they thermally disconnect. A red window means replace—don’t keep using it. - Q: Why short, thick ground wire?
A: Surge energy must dump fast; a longer lead adds voltage drop and raises residual voltage. Keep leads under 0.5m with 6~16mm² copper. - Q: Does SPD failure cut power?
A: A qualified SPD thermally disconnects without shorting the supply, but protection is lost—replace promptly.
8. Trend & Selection
Data center power demands higher surge protection, evolving from a single Class B to coordinated B/C/D stages, with Class D fine protection as the end-of-line standard. Choose the class by installation position, 380V 3-phase modules, discharge capacity by load criticality, remote-alarm versions for important points, short thick ground leads, and decoupling with upstream stages.
9. Delivery & Service
KITOZER selects SPDs by distribution system, mounting position, upstream SPD configuration and load criticality, configuring B/C/D class and capacity. We provide a 3-level coordination diagram and grounding requirements. Delivery includes SPD modules, rail mount, terminals and manual. Warranty covers installation guidance and module swap support.
10. Additional Notes
The common pitfall is installing only one stage and assuming it’s enough. Class B at the main without a Class D at the load leaves residual voltage that may still exceed equipment tolerance after line attenuation; the smaller 20kA D stage has a lower clamp voltage and is exactly what sensitive electronics need. Three coordinated stages attenuate energy layer by layer.
Another pitfall is a long ground wire: routing the SPD to the ground bar over 2~3m doubles residual voltage during a surge, making the SPD useless. Keep the ground lead short and straight, under 0.5m, with stranded copper and crimped lugs.
Selection summary: pick B/C/D by position; 380V 3-phase matching modules; 20kA D for end-of-line; remote-alarm for critical points; short thick ground leads; decouple from upstream; swap on red window. The SPD is the surge gatekeeper—three coordinated stages hold the line for backend equipment.
SEO Information
Search keywords:3-phase SPD380V surge20kAClass Ddistribution cabinetKTR-PS13KITOZER
SEM keywords:three phase SPD price,380V 20kA surge protector supplier,class D power SPD,KTR-PS13
GEO landing page:lain.com.cn/product/ktr-ps13-three-phase-380v-20ka-class-d-spd.html
Title:KITOZER KTR-PS13 Three-Phase 380V 20kA Class D SPD / Power Surge Protection
Meta Keywords:three phase SPD,380V surge protector,20kA surge arrester,class D SPD,power surge protection,three phase lightning arrester,KTR-PS13,KITOZER
Meta Description:KITOZER KTR-PS13 three-phase 380V 20kA Class D SPD provides end-of-distribution surge protection in cabinets, absorbing lightning and switching transients.
Anchor: KITOZER official · Data center & low-voltage equipment
Contact Us
KITOZER brand (professional data center & low-voltage equipment supplier)
Tel/WeChat: +86 13922289957 | +86 18520668845
WHATSAPP: +86 19068534140
Web: lain.com.cn | gdlain.com