Table of Contents
ToggleI. System Introduction
1.1 Technical Definition
KITOZER Modular Double-Row Cold Aisle Containment is a high-efficiency airflow management solution specially designed for data center facilities. Cabinets are arranged face-to-face to form fully enclosed cold aisles and back-to-back to form open hot aisles via physical partitioning, completely eliminating short-circuit of hot and cold airflow to realize precise cooling and power consumption optimization. Built on modular design philosophy, all components are factory prefabricated for fast on-site assembly, supporting flexible capacity expansion and later renovation, applicable for both new-build and retrofit data center projects of all specifications.
1.2 Core Working Principle
Energy efficiency improvement is realized via four core mechanisms:
- Airflow Isolation: Fully sealed cold aisle ensures 100% of chilled air from CRAC enters server intake; hot exhaust returns to air conditioner return air plenum from top of hot aisle
- Static Pressure Balancing: Cold aisle top cover extends 450mm above cabinet roof to form stable static pressure chamber for even cold air distribution across entire aisle
- Intelligent Fire Linkage: Aisle skylights interlock with fire alarm system and auto-open upon fire detection to comply with fire safety codes
- Precision Monitoring: Real-time collection of aisle temperature, humidity and differential pressure to dynamically adjust cooling output of air conditioning units

1.3 Application Benefits
| Benefit Item | Core Gain | Quantified Index |
|---|---|---|
| Energy Efficiency | PUE Reduction | PUE down to 1.3~1.5, 20%~35% lower vs conventional open computer room |
| OPEX Saving | Electricity Cost Cut | Annual operating expense reduced by over 30% |
| Equipment Safety | Hotspot Elimination | Intra-aisle temperature deviation ≤1℃, no local hotspot above 24℃ |
| O&M Optimization | Simplified Daily Management | 40% less maintenance frequency, 50% shorter fault response time |
| Project Delivery | Fast Site Deployment | Construction cycle shortened by 60%, plug-and-play installation |
II. System Composition
KITOZER double-row cold aisle system consists of six highly integrated subsystems for coordinated operation.
2.1 Sealed Cold Aisle Subsystem (Core Part)
| Component | Specification | Function Description |
|---|---|---|
| Cold Aisle Frame | 1.5mm cold rolled steel with electrostatic spray coating | Load-bearing support structure, compatible with standard server racks |
| End Access Door | 2050mm height, tempered glass + metal frame | Operator access & visual inspection, equipped with electronic access control lock |
| Modular Top Cover | Flat type, 1305mm width, 450mm higher than cabinet top | Air sealing, integrated embedded LED lighting |
| Fire Linkage Skylight | Auto-fusible opening, flame retardant fire-rated material | Automatic release during fire incident for smoke exhaust |
| Sealing Accessories | 5mm thick PVC baffle with rubber gasket | Fill cabinet clearance, cold air leakage rate<5% |
| Aisle LED Lighting | Recessed installation, brightness ≥300Lux | Energy-saving uniform aisle illumination |
2.2 Cabinet Subsystem
- Standard Rack: 600/800(W)×1200(D)×2200(H)mm (42U), 1.2~2.0mm cold rolled steel plate
- Load Capacity: Static full rack load ≥1500kg, single shelf rated load ≥80kg
- Compatibility: Standard 19-inch equipment mounting, front & rear perforated door ventilation ratio ≥70%
- Expansion Option: Pre-reserved interface for top cable tray, bottom wiring duct and side-mounted PDU
2.3 Cooling Subsystem
- In-row CRAC Unit: Horizontal air supply, cooling capacity ranging 5~41kW, available for N+X redundant configuration
- Air Distribution: Dual airflow mode (underfloor / horizontal supply), partitioned static plenum adapting for variable rack power density
- Intelligent Regulation: Remote monitoring supported; cooling capacity auto-adjusted according to real-time aisle ambient temperature
2.4 Power Distribution Subsystem
- End-of-row Power Cabinet: Integrated PDM power distribution module with multi-circuit input & output
- Intelligent PDU: Real-time monitoring of voltage, current & power; remote on/off switch control
- Redundant Design: Dual-circuit incoming power for non-stop power supply
2.5 Intelligent Monitoring Subsystem
- Environmental Sensors: Temp/humidity, differential pressure, smoke & water leakage probes; accuracy ±0.5℃ / ±3%RH
- Central Controller: Local 10-inch touch screen + WEB remote access & mobile APP monitoring
- Multi-level Alarm: Audible-visual alert, SMS & email notification for fault auto-reporting
- Data Visualization: 3D digital twin platform with real-time aisle thermal cloud map display
2.6 Fire Protection Linkage Subsystem
- Interlock Logic: Auto skylight opening + CRAC shutdown triggered by fire alarm signal
- Emergency Evacuation: Automatic unlock of end access doors for personnel escape
- Gas Suppression Compatibility: Seamless docking with FM200 and other clean-agent fire suppression systems

III. System Classification
3.1 By Rack Power Density
| Type | Rack Power Load | Application | Cooling Configuration |
|---|---|---|---|
| Standard Density | 3~6kW/rack | General IDC & small-scale data center | Standard underfloor supply in-row air conditioner |
| Medium Density | 6~12kW/rack | Cloud computing & enterprise DC | Enhanced horizontal air supply in-row CRAC |
| High Density | 12~20kW/rack | HPC & AI server cluster | Water-cooled in-row precision cooling unit |
3.2 By Installation Mode
- New-build Integrated Type: Co-designed with civil construction, full factory prefabrication & rapid on-site assembly
- Retrofit Adaptation Type: Fit existing room layout without large-scale civil modification, phased construction without service interruption
- Hybrid Deployment Type: Partial cold aisle sealing + partial open layout for phased DC expansion project
3.3 By Skylight Opening Type
- Auto-fusible skylight: Thermal trigger opening, mainly for clean-agent fire suppression computer room
- Electric control skylight: Local/remote motorized opening for conventional fire alarm system
- Manual emergency skylight: Backup mechanical opening for extreme emergency evacuation

IV. Bill of Materials (Brand: KITOZER | Standard Pack: 12-Rack Double-Row Cold Aisle)
| No. | Item | Model | Spec | Qty | Brand |
|---|
Part 1: Sealed Aisle System
1|Cold Aisle Frame|KZ-CCF-1200|1200mm width for 600mm standard rack|6 sets|KITOZER|
2|End Access Door|KZ-CCM-2050|2050H, Al+Tempered Glass, digital lock|2 sets|KITOZER|
3|Modular Top Cover|KZ-CCT-1305|1305mm width, +450mm over rack, built-in LED|6 pcs|KITOZER|
4|Fire Interlock Skylight|KZ-CCS-1200|Auto thermal fuse, B1 fire rating|6 pcs|KITOZER|
5|Gap Sealing Kit|KZ-CCS-05|5mm PVC with rubber gasket|12 sets|KITOZER|
6|Aisle LED Lamp|KZ-CCL-300|≥300Lux, 90min emergency backup|6 sets|KITOZER|
Part 2: Cabinet System
7|42U Server Rack|KZ-RACK-42U|600×1200×2200mm, 1.5mm steel|12 units|KITOZER|
8|Perforated Door|KZ-RM-70|≥70% ventilation rate with inspection window|24 pcs|KITOZER|
9|Adjustable Load Shelf|KZ-RS-80|Single shelf load ≥80kg|24 pcs|KITOZER|
Part3: Cooling System
10|In-row CRAC|KZ-CA-15|15kW cooling, horizontal supply, N+1 redundant|2 units|KITOZER|
11|Partition Static Plenum|KZ-CP-1200|Covers 3~4 racks per section|3 sets|KITOZER|
Part4: Power Distribution System
12|End-of-row Power Cabinet|KZ-PDU-630|630A input, multi-outlet with monitoring|2 units|KITOZER|
13|Intelligent Switched PDU|KZ-PD-32|32A input,16 outlets, remote control|24 pcs|KITOZER|
Part5: Environmental Monitoring System
14|Temp&RH Sensor|KZ-TH-01|±0.5℃/±3%RH, RS485 Modbus|6 pcs|KITOZER|
15|Differential Pressure Sensor|KZ-DP-02|Measuring range ±500Pa|2 pcs|KITOZER|
16|Central Monitoring Host|KZ-MC-10|10-inch touch screen + WEB|1 unit|KITOZER|
17|Alarm Terminal|KZ-AL-03|Audible/visual + SMS alert module|1 set|KITOZER|
Part6: Fire Interlock System
18|Fire Linkage Controller|KZ-FC-01|Fire signal reception & skylight drive|1 unit|KITOZER|
19|Emergency Manual Button|KZ-EB-02|Manual forced skylight open|2 pcs|KITOZER|
Optional Upgrade Components
| Item | Model | Function | Application Scenario |
|---|---|---|---|
| Access Control System | KZ-AC-05 | Face recognition / card swipe & access log | High-security data center |
| HD CCTV | KZ-VC-1080 | IR night vision surveillance | Unattended computer room |
| 3D Airflow Visualization | KZ-AV-3D | Real-time airflow thermal cloud display | Ultra-high density rack zone |
| Smart Variable Skylight Control | KZ-SC-03 | Temp/DP linked auto opening adjustment | Dynamic variable IT load IDC |
| 4G Remote Gateway | KZ-RM-4G | Wireless cloud remote monitoring | Distributed branch computer room |

V. System Principle Drawings
5.1 Airflow Distribution Diagram
┌─────────────────────────────────────────┐
│ CRAC Supply Air Zone │
│ ┌─────────────────────────────────┐ │
│ │ SEALED COLD AISLE │ │
│ │ ┌─────┐ ┌─────┐ ┌─────┐ │ │
│ │ │RACK1│ │RACK2│ │RACK3│ │ │
│ │ │Face-to-Face │Face-to-Face│ │ │
│ │ └─────┘ └─────┘ └─────┘ │ │
│ │ Cold Air →→→→→→→→→→→→→→→→→→→→→ │ │
│ └─────────────────────────────────┘ │
│ ↑ ↓ │
│ ┌─────────────────────────────────┐ │
│ │ OPEN HOT AISLE │ │
│ │ ┌─────┐ ┌─────┐ ┌─────┐ │ │
│ │ │RACK1│ │RACK2│ │RACK3│ │ │
│ │ │Back-to-Back│Back-to-Back│ │ │
│ │ └─────┘ └─────┘ └─────┘ │ │
│ │ Hot Air →→→→→→→→→→→→→→→→→→→→→ │ │
│ └─────────────────────────────────┘ │
│ CRAC Return Air Zone │
└─────────────────────────────────────────┘
Airflow Description: Cold air flows into rack front intake inside enclosed cold aisle; after heat absorption, hot air exhausts from rack rear to open hot aisle, then returns to air conditioner for cyclic cooling.
5.2 Overall System Architecture Diagram
┌─────────────┐ ┌─────────────┐ ┌─────────────┐
│Cooling System│───▶│Cold Aisle Sys│───▶│Hot Aisle Zone│
└─────────────┘ └─────────────┘ └─────────────┘
│ │ │
▼ ▼ ▼
┌─────────────┐ ┌─────────────┐ ┌─────────────┐
│Power Dist Sys│ │Monitor Sys │ │Fire Control │
└─────────────┘ └─────────────┘ └─────────────┘
│ │ │
└───────────────────┼───────────────────┘
▼
┌─────────────┐
│Central Platform│
└─────────────┘
Logic Note: All subsystems realize centralized monitoring & intelligent linkage via central management platform.
5.3 Fire Interlock Logic Diagram
┌─────────────┐ Fire Alarm Signal ┌─────────────┐
│Fire Alarm Host│───────────────────────▶│Linkage Module│
└─────────────┘ └─────────────┘
│
┌───────────────────────┼───────────────────────┐
│ │ │
▼ ▼ ▼
┌─────────────┐ ┌─────────────┐ ┌─────────────┐
│Skylight Auto│ │CRAC Shutdown│ │Door Unlock │
│Opening Drive│ │ │ │ │
└─────────────┘ └─────────────┘ └─────────────┘
Note: Once fire signal triggered, linkage module synchronously controls three sets of equipment for equipment protection & personnel evacuation safety.

VI. Technical Specifications
6.1 Core Aisle Component Parameters
| Component | Item | Spec | Compliance Standard |
|---|---|---|---|
| Aisle Frame | Material & Thickness | 1.5mm cold rolled steel | GB/T708-2019 |
| Surface Finish | Pickling+Phosphating+Electrostatic Coating, IP20 | GB/T1771-2007 | |
| Top Load | ≥200kg/㎡ | Industry Specification | |
| End Access Door | Dimension | 2050×1200mm | Custom Standard |
| Material | Al frame+10mm tempered glass | GB15763.2-2005 | |
| Access Control | Digital lock + IC card compatible | ISO15693 | |
| Top Cover | Single Module Size | 1305×1000mm | Custom Standard |
| Fire Rating | B1 flame retardant | GB8624-2012 | |
| Light Transmittance | ≥85% | GB/T2410-2008 | |
| Fire Skylight | Fuse Temp | 70℃±5℃ | GB16806-2018 |
| Full Open Time | ≤5s | Fire Code Standard | |
| Seal Kit | Material | 5mm PVC+rubber ring | GB/T10002.1-2006 |
| Cold Air Leakage | <5% | Factory Test Standard |
6.2 Overall System Performance Index
| Category | Parameter | Value | Test Condition |
|---|---|---|---|
| Energy | System PUE | 1.3~1.5 | Normal rated IT load |
| Cold Air Utilization | ≥95% | Fully sealed status | |
| Power Saving | ≥30% | Compared with open room | |
| Ambient | Cold Aisle Temp | 18~22℃ | Steady operation |
| Temp Uniformity | ≤±1℃ | All measuring points | |
| RH Range | 45%~60%RH | 24h continuous test | |
| Structure | Aisle Width | 1200~1800mm | Matches standard raised floor |
| Installation Speed | ≤4h/12 racks | Professional construction crew | |
| Safety | Material Standard | RoHS compliant + B1 fire grade | National Fire Standard |
6.3 Cabinet Detailed Spec
- Dimension:600×1200×2200mm(42U); Frame 2.0mm, door 1.5mm cold rolled steel
- Static full rack load≥1500kg, single shelf≥80kg; front/rear door ventilation≥70%
- Anti-corrosion coating pass 1000h salt spray test, IP20 protection rating
6.4 Monitoring Device Spec
- Temp&RH: -40~85℃ / 0~100%RH, ±0.5℃/±3%RH, Modbus-RTU
- Differential Pressure: ±500Pa, accuracy ±1%FS
- Central Controller:10-inch touch screen, 4-core CPU, 2GB RAM+8GB storage; support WEB/APP/4G remote access; 365-day historical data storage
VII. Application Industry & Scenarios
7.1 Vertical Industry Matching
| Industry | Core Requirement | Project Value |
|---|---|---|
| Cloud & Internet | High density, flexible expansion, low PUE | Rapid capacity expansion & substantial electricity cost reduction |
| Financial DC | Ultra-high reliability & safety | Hotspot elimination to guarantee uninterrupted transaction system |
| Telecom Operator | Large-scale distributed deployment | Centralized remote O&M to cut field maintenance expense |
| Government Cloud | Regulatory compliance & audit traceability | Meet Grade Protection standard for government IT infrastructure |
| Enterprise Private Cloud | Fast deployment & lower upfront investment | Shorten construction period & reduce total ownership cost(TCO) |
| Medical Data Center | 24/7 non-stop stable running | Secure continuous operation for medical image & patient database |
| University HPC Lab | High computing density & energy saving | Stable cooling for supercomputing research & lower lab power expense |
###7.2 Three Major Project Types
- New-build Data Center: Factory prefabrication cuts construction cycle by 60%, phased installment to lower initial CAPEX, standardized compatible design for future upgrade
- Legacy Room Retrofit: No large civil alteration; phased off-hour construction without service outage; rapidly improve cooling efficiency & extend existing equipment lifespan
- Hybrid Mixed Layout: Partial cold aisle sealing for mixed low/high power density racks, smooth transition toward full enclosed cold aisle in later stage
###7.3 Special High-Density & Edge Scenarios
- High-density AI/HPC: Support single rack up to 20kW, precise airflow to eliminate hotspot
- Edge Computing Hub: Compact footprint design for narrow space, full remote monitoring to minimize on-site maintenance
- Green Energy-saving DC: RoHS eco-friendly material, compatible with free air cooling to further optimize PUE

VIII. Core Product Advantages
###8.1 Technical Superiority
- Modular prefabricated structure: 60% faster installation speed, free capacity expansion & easy spare part replacement
- Superior airflow sealing: ≥95% cold air utilization, stable static pressure for uniform temperature distribution & zero hotspot
- Multi-layer intelligent linkage: Fire-skylight interlock + cooling-temperature linkage + cloud remote centralized management
###8.2 Economic Benefits
| Cost Item | Profit | Quantified Index |
|---|---|---|
| Initial CAPEX | Shorten construction period | 60% less build time, 40% saving on labor cost |
| Phased investment | Expand along business growth to lower upfront fund pressure | |
| Long-term OPEX | Electricity & maintenance | ≥30% annual power saving, 40% less maintenance workload |
| Equipment Lifespan | IT & cooling equipment life extended 15%~20% | |
| Investment Return | Payback Period | ROI within 1.5~2 years |
###8.3 Safety Advantages
- Physical access control via electronic lock to prevent unauthorized equipment touch
- Constant ambient temperature avoids overheating & reduces server failure rate
- 24/7 real-time monitoring with pre-alarm to avoid unexpected downtime & data loss
###8.4 Performance Comparison Table
| Comparison Item | KITOZER Double-Row Cold Aisle | Traditional Open Room | Single-Row Cold Aisle |
|---|---|---|---|
| PUE | 1.3~1.5 | 1.8~2.2 | 1.4~1.6 |
| Cold Air Utilization | ≥95% | 60~70% | 90~95% |
| Install Speed | Fast(4h/12rack) | Slow(2~3d/12rack) | Medium(6h/12rack) |
| Max Supported Rack Load | 3~20kW | ≤3kW | 3~12kW |
| Space Utilization | High | Medium | Low |
| Running OPEX | Low | High | Medium |

IX. Tender Specification Parameters
###9.1 Mandatory Technical Bid Spec (Non-negotiable core clauses)
- Structure: Double-row face-to-face enclosed cold aisle modular assembly, GB/T41783-2022 compliant
- Airflow: Cold sealed + hot open layout to prevent air short-circuit, ISO/IEC11801 standard
- Energy: PUE≤1.5, cold air utilization≥95%, per GB/T41783
- Temp Control: Cold aisle 18~22℃, intra-aisle deviation ≤±1℃, GB50174
- Top Cover Height: +450mm over cabinet top, aisle width 1200~1800mm
- Fire Skylight: 70℃±5℃ thermal fuse, full open ≤5s, GB16806
- Material: Frame steel ≥1.5mm, coating ≥1000h salt spray resistance GB/T10125
- Monitoring: Local touch screen + remote WEB/APP dual management GB50462
- Install Cycle: ≤4h for standard 12-rack set (±1h tolerance allowed) 10.Warranty: Whole system ≥5Y warranty, core components ≥10Y
###9.2 Commercial Bid Requirement
- Manufacturer with ISO9001/ISO14001/ISO45001 certification (mandatory qualification)
- At least 10 similar completed projects over past 3 years with single contract ≥2 million RMB
- After-sale service: 2h remote response, on-site engineer within 24h, fault fixed within 48h
X. Three Typical Customized Solutions
###10.1 New-Build Green Data Center Solution
- Key Feature: Full-process BIM pre-design + energy consumption simulation; all parts factory prefabricated, 12-rack set finished within 4h on site; integrated intelligent centralized monitoring platform
- Execution Flow: Demand Survey→BIM Modeling→Energy Simulation→Factory Production→On-site Install→Commissioning→User Training
###10.2 Existing Open Computer Room Retrofit Solution
- Key Feature: Phased zone-by-zone construction during off-business hour without service interruption; original air conditioner & fire system reserved for cost saving; PUE optimized down to1.3~1.5 after renovation
- Execution Flow: On-site Audit→Optimization Design→Risk Plan→Staged Construction→Test & Acceptance
###10.3 Ultra-High Density AI/HPC Solution(≥12kW/Rack)
- Key Feature: Water-cooled in-row CRAC + enhanced sealing (air leakage<3%) + dynamic skylight auto-adjust by temp/differential pressure + 3D airflow visualization; every 2m equipped with independent temp sensor for precise cooling control
- Execution Flow: Load Calculation→Cooling Sizing→System Install→Airflow Calibration→Simulation Test→Delivery
XI. Reference Project Cases
###Case1: Cloud Service Provider IDC (Shenzhen, 1000 racks,6~12kW/rack)
- Result: Original PUE1.8 reduced to1.4, annual power saving ≈8 million CNY; full 1000-rack installation finished within 45 days, 60% shorter than traditional build; intra-aisle temp stably 20±1℃ with zero hotspot
###Case2: National Head Office Bank DC Retrofit (Beijing,500 racks, old PUE1.9)
- Result: PUE down to1.5, annual electricity saving≈3.5 million CNY; 5-phase phased renovation with each section ≤100 racks & minimal service interruption; investment payback within 1.8 years
###Case3: University HPC Supercomputing Center(Shanghai,200 racks@20kW/rack)
- Result: Successfully solve extreme high-density heat dissipation, final PUE=1.4 to meet national green DC standard; becomes provincial energy-saving demonstration research data center
XII. SEO Keywords & Tags
###12.1 Core Primary Keywords
Modular Hot Cold Aisle Containment, Double-Row Cold Aisle Solution, KITOZER Cold Aisle System, Data Center Airflow Management, Cold Aisle Sealing System, PUE Optimization for Green Data Center, Data Center Retrofit Energy Saving
###12.2 Long-tail Keywords
Double-row cold aisle working principle, cold aisle tender parameter specification, legacy computer room cold aisle renovation plan, high-density AI rack cooling solution, cold aisle fire linkage design standard
###12.3 Hashtag Tags
#ModularColdAisle #DoubleRowContainment #DataCenterEnergySaving #PUEOptimization #IntelligentDC #ColdAisleRetrofit #FireInterlockSystem