ToggleKITOZER KTR-BAT150V 12V150Ah Deep-Cycle VRLA Battery
Brand: KITOZER Series: KTR-BAT150V Category: Power Distribution / VRLA Battery
12V150Ahdeep cycleVRLAAGMvalve regulatedKTR-BAT150V

1. Overview
The KITOZER KTR-BAT150V is a 12V150Ah valve-regulated lead-acid (VRLA) battery using AGM (absorbent glass mat) separator technology. Electrolyte is absorbed in the glass mat, so it cannot flow or leak, and the battery can be mounted in any orientation (except inverted). The deep-cycle design recovers after deep discharge, suiting UPS backup, solar storage, telecom sites and room distribution.
The battery uses a high-quality lead-calcium alloy grid for low self-discharge and long float life (design float life 10~12 years). The safety valve vents automatically when internal gas pressure is abnormal and stays sealed under normal operation — maintenance-free with no watering needed. Terminals are tinned copper with low connection resistance, suited to high-current discharge. The ABS case is impact-resistant and UL94 V-0 flame-retardant.
In room UPS systems, the battery bank consists of multiple 12V batteries in series (e.g. a 384 V DC bus from 32 × 12V150Ah), providing backup runtime after mains failure. The 150 Ah capacity (C10) delivers 15 A for 10 hours at the 10-hour rate. Versus ordinary float batteries, the deep-cycle design withstands repeated deep discharge, suiting frequent outages or storage applications.
2. Key Features
Deep cycle
- Recovers after deep discharge.
- For frequent outages and storage.
- Long cycle life.
- Stable discharge plateau.
AGM sealed VRLA
- Electrolyte in glass mat.
- No leak, any orientation.
- Auto safety valve.
- Maintenance-free.
Long float life
- Lead-calcium grid.
- Low self-discharge.
- 10~12 year float design.
- Low annual fade.
Flame-safe
- ABS UL94 V-0 case.
- Tinned copper terminals.
- Stable high-current discharge.
- Impact-resistant.
3. Specifications
| Item | Parameter |
|---|---|
| Nominal voltage | 12V |
| Rated capacity | 150Ah (C10, 25℃) |
| Float life | 10~12 years (25℃) |
| Internal resistance | ~3.5 mΩ |
| Max discharge current | 1500 A (5 s) |
| Charge voltage | float 13.5~13.8V / boost 14.4~14.9V |
| Operating temp | -15~50℃ |
| Terminals | tinned copper |
| Case | ABS UL94 V-0 |
| Weight | ~43 kg |
4. Reference Prices
KTR-BAT150V 12V150Ah深循环VRLA电池(单只): Reference USD 136~233 / pc (ref. CNY 980~1680 at ~7.2)
KTR-BAT150V 32只串联电池组(含连接条、支架): Reference USD 4444~7222 / bank (ref. CNY 32000~52000 at ~7.2)
Reference only; priced per pc. UPS unit and battery cabinet excluded.. Exchange: 1 USD ~ 7.2 CNY (Oct 2026).
5. Applications
- Room UPS backup.
- Solar PV storage.
- Telecom battery banks.
- Industrial DC power.
- Emergency lighting and fire power.
6. Installation & Maintenance
Installation
- Mount upright, not inverted.
- Tighten connectors to torque.
- Series polarity correct.
- Ventilate battery cabinet.
- 20~25℃ ambient ideal.
- Check open-circuit voltage before install.
Maintenance
- Measure per-cell voltage monthly.
- Measure internal resistance quarterly.
- Keep surface clean and dry.
- Coat terminals with petroleum jelly.
- Ambient under 30℃.
- Replace failed cells promptly; replace bank as a set.
7. FAQ
- Q: Deep-cycle vs ordinary float battery?
A: Ordinary float batteries stay fully charged with occasional shallow discharge. Deep-cycle batteries have thicker grids and mats to withstand repeated deep discharge (below 50%). Choose deep cycle for frequent outages or storage; choose float type for long-term float with rare discharge. - Q: Why replace the whole bank?
A: One failed cell in a series bank drags down the whole set; old cells have high internal resistance and new cells paired with old ones are dragged down. Replace same-model same-batch cells as a set; do not mix old and new. - Q: What load can 12V150Ah carry?
A: Estimate by discharge rate. 150Ah (C10) delivers 15 A at the 10-hour rate — about 180 W (12V × 15A) for 10 hours. Real UPS DC buses differ (e.g. 384 V); bank power is calculated on the whole set, and 150Ah per cell only denotes capacity. - Q: Signs of end-of-life?
A: Per-cell voltage low, internal resistance rising, float current high, case swelling, runtime shortened. These signs mean degradation — schedule replacement to avoid outage during mains failure.
8. Trend & Selection
Data centers and storage raise demands on battery life, safety and monitoring; VRLA deep-cycle batteries remain the UPS mainstream, while LiFePO4 lithium is gradually entering new projects. Size capacity by backup time and discharge rate; choose AGM deep-cycle for deep-discharge scenes, pair with a battery monitoring system (BMS) for per-cell voltage and temperature, and replace banks as a set without mixing.
9. Delivery & Service
KITOZER selects the KTR-BAT150V count by UPS DC bus voltage, backup time and discharge rate, providing capacity calc, connector specs and cabinet layout. Delivery includes batteries, connectors, racks and install manual. Warranty covers internal-resistance testing and replacement guidance.
10. Additional Notes
A common pitfall is mixing old and new cells. To save cost, installers replace only one or two failed cells, putting new cells in series with old ones. High-resistance old cells charge first while new cells under-charge; on discharge old cells deplete first and force new cells into over-discharge, accelerating new-cell damage. Replace the whole bank from the same batch.
Another pitfall is high ambient temperature. Every 10℃ rise cuts float life roughly in half. If the battery cabinet sits near heat sources or vents poorly, sustained over-30℃ operation swells cells within 2~3 years. Keep the battery room at 20~25℃ with good ventilation, away from AC vents and heat sources.
Selection summary: 12V150Ah deep-cycle AGM; sealed VRLA maintenance-free; lead-calcium long life; flame-retardant ABS; same-batch whole-bank replacement; 20~25℃ ambient; periodic voltage and resistance checks; no old-new mixing. The battery is the heart of the UPS — right capacity, proper connections, controlled temperature, timely replacement keep backup power ready when mains fails.
SEO Information
Search keywords:battery12V150Ahdeep cycleVRLAAGMKTR-BAT150VKITOZER
SEM keywords:12V150Ah battery price,deep cycle VRLA battery supplier,AGM battery,KTR-BAT150V
GEO landing page:lain.com.cn/product/ktr-bat150v-12v150ah-deep-cycle-vrla.html
Title:KITOZER KTR-BAT150V 12V150Ah Deep-Cycle VRLA Battery
Meta Keywords:12V150Ah battery,deep cycle VRLA battery,AGM battery,valve regulated lead acid battery,UPS battery,KTR-BAT150V,KITOZER
Meta Description:KITOZER KTR-BAT150V 12V150Ah deep-cycle VRLA battery with AGM valve-regulated sealed design, for UPS, energy storage and room distribution backup power.
Anchor: KITOZER official · Data center & low-voltage equipment