Table of Contents
ToggleKITOZER KTR-WS4 Point-Type Water Leak Sensor
Brand: KITOZER Series: KTR-WS4 Category: Environmental Monitoring / Water Leak Sensor
point typewater leak sensorleak detectiondry contactKTR-WS4

1. Overview
The KITOZER KTR-WS4 is a point-type water leak sensor (leak detection probe), installed in equipment rooms, distribution rooms or warehouses where water may appear. When pooling reaches the probe, it outputs a dry-contact alarm signal to the environmental monitoring system, prompting O&M to handle the leak promptly.
The probe uses dual stainless-steel electrodes. Normally dry, the electrodes are insulated and the contact output stays open; when water covers the probe, conductivity closes the contact and triggers an alarm. Sensitivity is high — a few millimeters of water triggers it. Output is a dry contact (NO/NC optional), compatible with mainstream BMS hosts and PLC acquisition modules.
Versus cable-based (locating) leak systems, point sensors are low-cost and easy to install, suited to key leak points (AC condensate pans, pipe joints, below windows, under raised floors). The KTR-WS4 probe is IP65 waterproof, the ABS housing is flame-retardant, powered by DC12V or DC24V (by model), with customizable lead length. Multiple point sensors can be paralleled on one monitoring channel or deployed independently.
2. Key Features
Point, high sensitivity
- Dual stainless electrodes.
- Few-mm water triggers.
- Fixed-point leak detection.
- Fast response.
Dry contact output
- NO/NC selectable.
- Compatible with BMS.
- Compatible with PLC.
- Connects to alarm platform.
IP65 probe
- IP65 waterproof probe.
- ABS flame-retardant case.
- DC12/24V supply.
- Custom lead length.
Easy install
- Fix on floor or near pipe.
- No calibration.
- Long-term stable.
- Multiple sensors parallel.
3. Specifications
| Item | Parameter |
|---|---|
| Detection principle | Electrode conduction |
| Sensitivity | ≥2 mm water |
| Output | dry contact (NO/NC opt.) |
| Contact rating | DC30V / 1A |
| Power | DC12V or DC24V |
| Probe protection | IP65 |
| Housing | ABS UL94 V-0 |
| Operating temp | -10~60℃ |
| Lead length | 1 m (customizable) |
| Mounting | wall / floor |
4. Reference Prices
KTR-WS4 点式水浸传感器(探头+1m引线): Reference USD 6~13 / pc (ref. CNY 45~95 at ~7.2)
KTR-WS4 10只装(含继电器模块、接线端子): Reference USD 58~108 / box (ref. CNY 420~780 at ~7.2)
Reference only; priced per pc. Environmental monitoring host excluded.. Exchange: 1 USD ~ 7.2 CNY (Oct 2026).
5. Applications
- Under room precision AC.
- Near pipe joints and valves.
- Under raised floors.
- Distribution room leak detection.
- Warehouse and basement water protection.
6. Installation & Maintenance
Installation
- Place probe at the most likely pooling point.
- Electrodes touch the floor.
- Wire lead to BMS dry contact.
- Select NO/NC per system.
- Do not cover probe with debris.
- Clean electrodes periodically.
Maintenance
- Clean probe electrodes regularly.
- Check lead for damage.
- Simulate water to test alarm.
- Verify monitoring channel status.
- Replace corroded probe.
- Tighten terminals.
7. FAQ
- Q: Point vs cable leak system?
A: Point sensors are cheap and simple, for known key leak points (under AC, near joints). Cable-based (locating) systems run along pipes to detect and locate leaks anywhere along the route, suiting long lines and large areas. Choose point for fixed critical points, cable for large areas; the two can mix. - Q: Will the sensor false-alarm?
A: Not in a dry environment. False alarms usually come from dust or oil on electrodes causing weak conduction, damp leads shorting, or reversed NO/NC. Keep the probe clean and dry, route leads away from pipes, and run periodic simulated tests. - Q: Can several sensors share one channel?
A: Yes. Multiple dry-contact sensor outputs can be paralleled; any trigger closes the alarm, but you cannot tell which probe fired. For location use one channel per probe or an address module. - Q: Will the probe survive long immersion?
A: The IP65 probe tolerates short immersion, but long soaking accelerates electrode corrosion. After an alarm, fix the leak and dry the probe promptly. For chronic pooling choose a cable-based locating system rather than a point probe.
8. Trend & Selection
Room environmental monitoring moves toward unmanned operation and early warning; leak sensors evolve from single-point alarms to networked multi-point location. Choose point count by leak-point density, add cable-based locating for long lines, standardize dry-contact output to the BMS, and run periodic simulated tests to ensure alarms work.
9. Delivery & Service
KITOZER selects the KTR-WS4 count by room leak-risk distribution, providing point layout, wiring diagrams and NO/NC configuration. Delivery includes probes, leads, terminals and install manual. Warranty covers simulated testing and monitoring integration guidance.
10. Additional Notes
A common pitfall is placing the probe directly under the AC drip point, where falling water hits it — seemingly sensitive but it corrodes the electrodes over time. Instead place the probe at the condensate-pan edge or the lowest pooling point, not directly under the drip; the drip point should first have a drainpipe, with the probe as backup monitoring.
Another pitfall is reversed NO/NC. The BMS usually expects NC (normally closed), opening on leak; if NO (normally open) is mistakenly wired, it reads as either constant alarm or no alarm. Confirm NO/NC by the channel definition before wiring, and run one simulated water test.
Selection summary: point dual-electrode high sensitivity; dry contact NO/NC; IP65 probe; DC12/24V; place at key leak points; do not sit under the drip; periodic cleaning and simulated testing; add cable-based locating for long lines. The leak sensor is the eye of room water protection — right location, right polarity, periodic testing catch leaks early and avoid water incidents.
SEO Information
Search keywords:water leak sensorpoint typeleak detectiondry contactKTR-WS4KITOZER
SEM keywords:point water leak sensor price,leak detection probe supplier,data center leak alarm,KTR-WS4
GEO landing page:lain.com.cn/product/ktr-ws4-point-water-leak-sensor.html
Title:KITOZER KTR-WS4 Point-Type Water Leak Sensor
Meta Keywords:point water leak sensor,water leak detection probe,data center water sensor,dry contact leak sensor,leak alarm,KTR-WS4,KITOZER
Meta Description:KITOZER KTR-WS4 point-type water leak sensor with dry contact output, for leak detection under room AC, at pipe joints and under raised floors.
Anchor: KITOZER official · Data center & low-voltage equipment
Contact Us
KITOZER brand (professional data center & low-voltage equipment supplier)
Tel/WeChat: +86 13922289957 | +86 18520668845
WHATSAPP: +86 19068534140
Web: lain.com.cn | gdlain.com