KITOZER 3phase 380V 100KA B

KITOZER KTR-PS16 Three-Phase 380V 100kA Class B Surge Protective Device (SPD)

Brand: KITOZER Series: KTR-PS16 Category: Power Distribution / Surge Protective Device

3-phase 380V100kAClass BDIN railKTR-PS16

1. Overview

The KITOZER KTR-PS16 is a three-phase AC surge protective device (SPD), installed on the busbar of the room mains incomer or main distribution cabinet as a first-level (Class B) surge protector. It diverts transient over-voltage from lightning or switching into the ground and clamps residual voltage within equipment tolerance, protecting downstream UPS, distribution and loads. A Class B SPD has a high nominal discharge current (I_n) and a maximum discharge current (I_max) up to 100 kA, suited to large-energy diversion at the building incomer.

The KTR-PS16 is modular: each phase is a pluggable surge module built with a metal-oxide varistor (MOV) and a thermal disconnect. At normal voltage the MOV is high-impedance and does not affect supply; under transient over-voltage it conducts in nanoseconds, diverting surge energy to ground and clamping voltage at the residual level. Each module has a status window (green OK, red failed); a failed module is replaced individually without interrupting other phases. Some versions include a remote-signaling contact to upload module failure to monitoring.

The device is three-phase four-wire plus PE (3P+N) on a DIN rail, marked L1/L2/L3/N on the line side and grounded at the bottom. The SPD is wired in parallel ahead of the protected circuit, with a short, thick ground lead (at or above the required cross-section) to limit residual-voltage rise from lead inductance. At room mains incomers, floor distribution cabinets and outdoor equipment supply, the KTR-PS16 acts as first-level protection, paired with downstream Class C SPDs for staged protection that weakens surge energy step by step.

2. Key Features

3-phase 100kA capacity

  • 3P+N structure.
  • I_max 100 kA.
  • Class B first diversion.
  • Parallel on incomer busbar.

Modular pluggable

  • Independent module per phase.
  • MOV diversion.
  • Thermal disconnect.
  • Replace alone, supply intact.

Status & remote

  • Green/red window.
  • Remote-signaling contact.
  • Failures found early.
  • Inspect without opening.

DIN rail mount

  • Standard DIN rail.
  • Clear L1/L2/L3/N marks.
  • Short thick ground lead.
  • Staged with Class C.

3. Specifications

Item Parameter
System voltage 3-phase 380V AC
Configuration 3P+N
Max discharge I_max 100 kA (8/20μs)
Nominal I_n 40 kA
Voltage protection Up ≤1.8 kV
Response time ≤25 ns
Mounting 35 mm DIN rail
Fail indication green/red window + remote
Wire cross-section ≤35 mm²
Operating temp -40~85℃

4. Reference Prices

KTR-PS16 三相B级防雷器(3P+N整套): Reference USD 53~108 / pc (ref. CNY 380~780 at ~7.2)

KTR-PS16 备用防雷模块(单相): Reference USD 9~17 / pc (ref. CNY 65~120 at ~7.2)

Reference only; priced per pc. Distribution cabinet and earthing works excluded.. Exchange: 1 USD ~ 7.2 CNY (Oct 2026).

5. Applications

  • Room mains incomer cabinet.
  • First-level at main distribution.
  • Floor distribution boxes.
  • Outdoor equipment supply.
  • Surge protection ahead of UPS.

6. Installation & Maintenance

Installation

  • Wire in parallel ahead of the incomer busbar.
  • Connect L1/L2/L3/N correctly.
  • Use a short thick ground lead to the nearest ground bar.
  • Keep decoupling distance between stages.
  • Seat modules firmly; window green.
  • Wire remote contact to monitoring.

Maintenance

  • Check the window is green.
  • Replace modules on remote alarm.
  • Tighten terminals.
  • Inspect modules after thunderstorms.
  • Replace failed or end-of-life modules to spec.
  • Test earth resistance periodically.

7. FAQ

  • Q: Class B vs Class C SPD?
    A: Class B (first level) sits at the incomer with large discharge current (tens to hundreds of kA), diverting main lightning energy; Class C (second level) sits at the equipment with low residual voltage for fine protection. The two stage together and cannot replace each other.
  • Q: Can I keep using a red module?
    A: No. Red means the MOV has degraded or the thermal disconnect opened; replace the same-spec module promptly. Running it removes surge protection and leaves equipment at risk.
  • Q: Why must the ground lead be short and thick?
    A: A longer, thinner lead has more inductance, adding voltage drop during a surge and raising real residual voltage, weakening protection. Codes require a short, adequately sized lead to the nearest ground bar.
  • Q: Does the SPD need its own earth?
    A: No. It must land on the room equipotential ground bar, sharing earth with equipment. A separate earth creates a ground-potential difference and defeats equipotential protection.

8. Trend & Selection

Room distribution moves toward equipotential, staged surge protection; SPDs evolve from generic single-stage to B/C staged, modular replaceable, remote-monitored designs. Choose the Class B rating by system voltage and discharge current; install Class B at the incomer and Class C at equipment, share the equipotential earth, and wire remote signaling to the BMS for failure early-warning.

9. Delivery & Service

KITOZER selects KTR-PS16 rating by system voltage, lightning exposure and incomer capacity, providing wiring diagrams, staged-protection plans and earthing requirements. Delivery includes the SPD, modules and mounting parts. Warranty covers install guidance and test support.

10. Additional Notes

A common pitfall is running the ground lead a long way to the ground bar. Long leads add inductance, spiking residual voltage during a surge and making the SPD nearly useless. Use a short, straight, adequately sized lead to the nearest equipotential bar with minimal joints.

Another pitfall is staging B and C SPDs without decoupling. When B and C sit too close, the downstream unit diverts before the upstream acts, possibly overloading it. Codes require a decoupling distance or decoupling device between stages so surge energy is divided and discharged step by step.

Selection summary: 3-phase 380V 100 kA Class B; 3P+N modular; nanosecond MOV diversion; green/red window plus remote; short thick shared earth; staged with Class C; swap red modules promptly. The SPD is the safety gate of the power system — right rating, good earth, staged coordination keep surges away from equipment.

SEO Information

Search keywords:surge protector3-phase 380V100kAClass B SPDKTR-PS16KITOZER

SEM keywords:three phase SPD price,100kA class B SPD supplier,380V surge protective device,KTR-PS16

GEO landing page:lain.com.cn/product/ktr-ps16-3phase-380v-100ka-class-b-spd.html

Title:KITOZER KTR-PS16 Three-Phase 380V 100kA Class B Surge Protective Device (SPD)

Meta Keywords:three phase SPD,380V surge protective device,100kA class B SPD,power surge protector,DIN rail surge arrester,KTR-PS16,KITOZER

Meta Description:KITOZER KTR-PS16 three-phase 380V 100kA Class B power SPD with high discharge current and DIN-rail mounting, for first-level surge protection at the mains incomer and distribution cabinet.

Anchor: KITOZER official · Data center & low-voltage equipment

Contact Us

KITOZER brand (professional data center & low-voltage equipment supplier)
Tel/WeChat: +86 13922289957 | +86 18520668845
WHATSAPP: +86 19068534140
Web: lain.com.cn | gdlain.com

Shopping Cart