The KITOZER KTR-BAT200V is a valve-regulated sealed lead-acid battery (VRLA) rated 12V and 200Ah, using AGM (absorbent glass mat) separator technology. The electrolyte is absorbed in the mat and immobilized; the battery is sealed, leak-proof and requires no water topping-up in normal use. Its deep-cycle design tolerates deeper discharge followed by recharge, outlasting starter batteries in cycle life — suited to repeated charge/discharge such as UPS backup, DC operating power and solar storage.
The plates use lead-calcium grids for corrosion resistance and long float life. Internal gas recombination is high: hydrogen and oxygen from charging recombine to water at the negative plate with minimal outgassing, so it is safe and maintenance-free. A built-in safety valve vents abnormal internal pressure and recloses when pressure normalizes. Each cell has top voltage-sensing terminals and a carry handle for series installation and inspection. The case is flame-retardant ABS, heat-resistant and dimensionally stable.
Batteries are typically wired in series into a string — for example sixteen 12V cells to form a 192V DC bus feeding a UPS or DC panel. In one string use the same brand, model and batch with matched internal resistance and capacity, so a weak cell does not drag down the whole string. Racks keep ventilation spacing; ambient should be 20~25℃, as float life roughly halves for every 10℃ rise. In room UPS, telecom sites and storage projects, the KTR-BAT200V provides backup energy that keeps power continuous after an outage.
2. Key Features
12V200Ah capacity
- 12V rated.
- 200Ah capacity.
- Deep-cycle design.
- Long cycle life.
VRLA sealed
- AGM mat.
- Immobilized electrolyte.
- Sealed, leak-proof.
- Maintenance-free.
Gas recombination valve
- H/O recombine to water.
- Minimal outgassing.
- Auto relief valve.
- Lead-calcium grid.
Easy series install
- Top sense terminals.
- Built-in handle.
- Flame-retardant ABS.
- Series strings.
3. Specifications
| Item | Parameter |
|---|---|
| Nominal voltage | 12V |
| Capacity (20hr) | 200Ah |
| Type | VRLA sealed lead-acid AGM |
| Float design life | 10~12 years (25℃) |
| Self-discharge | ≤3%/month (25℃) |
| Operating temp | -15~50℃ |
| Float voltage | 13.5~13.8V/cell (25℃) |
| Equalize charge | 14.4~15.0V/cell |
| Terminals | M8 copper |
| Weight | approx. 62 kg |
4. Reference Prices
KTR-BAT200V 12V200Ah电池(单只,含端子): Reference USD 233~372 / pc (ref. CNY 1680~2680 at ~7.2)
KTR-BAT200V 16只电池组(含电池架、连接线): Reference USD 4139~6500 / bank (ref. CNY 29800~46800 at ~7.2)
Reference only; priced per pc. UPS unit and installation works excluded.. Exchange: 1 USD ~ 7.2 CNY (Oct 2026).
5. Applications
- Room UPS backup.
- DC operating panels.
- Solar/PV storage.
- Telecom site backup.
- Emergency lighting.
6. Installation & Maintenance
Installation
- Match brand/model/batch per string.
- Tighten series terminals.
- Keep ventilation spacing on racks.
- Ambient 20~25℃, ventilated.
- Set float voltage to spec.
- Equalize charge after install.
Maintenance
- Measure terminal voltage and internal resistance.
- Check terminals for oxidation/looseness.
- Clean battery surface.
- Record temp and float current.
- Balance or replace weak cells.
- Recharge stored batteries periodically.
7. FAQ
- Q: Does a maintenance-free battery need water?
A: No. VRLA electrolyte is absorbed in the AGM mat and gas recombines internally; normal use needs no watering. Opening to add water breaks the seal and recombination. - Q: Why control ambient temperature?
A: Heat accelerates grid corrosion and water loss; float life roughly halves per 10℃ rise. Keep the battery room at 20~25℃ with ventilation to extend life. - Q: One cell is weak in a string?
A: A weak cell drags whole-string capacity. Try an equalize charge first; if still weak, replace it with a same-spec, same-batch cell. Do not mix old and new cells, as new ones get dragged down. - Q: Can batteries be mounted on their side?
A: AGM VRLA cells can mount in several orientations, but upright is recommended for gas recombination and inspection. Follow the manual’s allowed orientations; do not invert or exceed the allowed angle.
8. Trend & Selection
Backup power moves toward long life, high energy density and smart monitoring; VRLA evolves from vented cells to deep-cycle AGM with internal-resistance monitoring. Size series count by the UPS DC-bus voltage and capacity by backup runtime, choose long-life deep-cycle models, pair with a battery monitor for internal resistance and voltage, and keep temperature near 25℃.
9. Delivery & Service
KITOZER selects KTR-BAT200V count and rack by UPS DC-bus voltage and backup runtime, providing string wiring diagrams, charge parameters and rack layout. Delivery includes batteries, links, terminal parts and manual. Warranty covers install, equalizing and inspection guidance.
10. Additional Notes
A common pitfall is mixing old and new cells in one string. Old cells have high resistance and low capacity; in series they overheat first on charge and deplete first on discharge, dragging the whole string and accelerating new-cell damage. Strings must be same brand, model and batch; replace by group or by matched batch.
Another pitfall is loose or under-torqued terminals. Under high discharge current, loose terminals heat and oxidize, building contact resistance and possibly arcing. Torque the M8 terminals to spec, apply anti-oxidation grease, and re-tighten during inspection.
Selection summary: 12V200Ah deep-cycle VRLA; AGM sealed maintenance-free; gas-recombination valve; 10~12 year float; matched batch, no mixing; 25℃ ventilated; tightened terminals with voltage/resistance checks. The battery is the heart of the UPS — enough capacity, correct stringing, constant temperature and regular inspection deliver reliable backup at outage.
SEO Information
Search keywords:battery12V200Ahdeep cycleVRLA AGMKTR-BAT200VKITOZER
SEM keywords:12V200Ah battery price,deep cycle VRLA battery supplier,UPS battery,KTR-BAT200V
GEO landing page:lain.com.cn/product/ktr-bat200v-12v200ah-deep-cycle-vrla-battery.html
Title:KITOZER KTR-BAT200V 12V200Ah Deep-Cycle VRLA Lead-Acid Battery
Meta Keywords:12V200Ah battery,deep cycle VRLA battery,AGM lead acid battery,UPS battery,sealed maintenance free battery,KTR-BAT200V,KITOZER
Meta Description:KITOZER KTR-BAT200V 12V200Ah deep-cycle VRLA valve-regulated sealed lead-acid battery with AGM separator, maintenance-free, for UPS, DC panels and solar energy storage backup.
Anchor: KITOZER official · Data center & low-voltage equipment
Contact Us
KITOZER brand (professional data center & low-voltage equipment supplier)
Tel/WeChat: +86 13922289957 | +86 18520668845
WHATSAPP: +86 19068534140
Web: lain.com.cn | gdlain.com