KITOZER
KITOZER

KITOZER locating leak cable

KITOZER KTR-LC2 Locating-Type Leak Detection Cable (Sensing Cable)

Brand: KITOZER Series: KTR-LC2 Category: Environmental Monitoring / Leak Detection Cable

locating typeleak detection cablesensing cabledistance locationKTR-LC2

KITOZER KTR-LC2 locating type water leak detection sensing cable

1. Overview

The KITOZER KTR-LC2 is a locating-type leak detection cable, also called a sensing wire. Unlike point leak sensors that only judge one spot, it monitors along the whole cable: when a segment touches a conductive liquid (water), the controller not only alarms but also computes the exact distance to the leak (usually within ±0.5 m), shown on the controller screen or uploaded to the BMS. This is highly useful for long-distance, large-area pipe leak monitoring.

The cable usually has four conductors: two sensing lines and two reference lines, covered by a braid and a PVC jacket. When dry, the sensing lines are insulated and the controller outputs a weak measurement signal; when liquid covers a segment, its conductivity makes the two sensing lines conduct at that point, and the controller computes the distance from loop impedance or signal attenuation. The cable responds only to conductive liquids (water, dilute acid) and not to non-conductive oils — keep the medium type in mind.

The cable works with a locating leak controller, which closes the loop at one end with a terminator resistor. The cable is routed under AC units, along water pipes and at low floor points, fixed every so often with dedicated clips. The controller provides relay dry contacts and RS485/Modbus output to the room BMS for real-time alarm and location display. Along precision-AC condensate, chilled water and drainage lines, the KTR-LC2 is a continuous monitoring means with wider coverage and more accurate location than point sensors.

2. Key Features

Precise location

  • Continuous along full length.
  • Computes leak distance.
  • Within ±0.5 m.
  • Location on controller.

4-conductor sensing

  • Two sense + reference lines.
  • Braided layer.
  • PVC jacket.
  • Responds to conductive liquid.

Controller paired

  • Terminator resistor at end.
  • Relay dry-contact output.
  • RS485/Modbus.
  • Feeds BMS.

Continuous routing

  • Along AC and pipes.
  • Dedicated clips.
  • Long distance, large area.
  • Wider than point sensors.

3. Specifications

Item Parameter
Type locating sensing cable
Conductors 4 (sense + reference)
Jacket PVC
Location accuracy ±0.5 m
Response liquid conductive (water, dilute acid)
Cable length per meter, custom
Operating voltage DC12/24V (controller)
Output dry contact + RS485/Modbus
Operating temp -10~60℃
Termination terminator resistor / connector

4. Reference Prices

KTR-LC2 定位漏水检测绳(按米计): Reference USD 4~8 / m (ref. CNY 28~55 at ~7.2)

KTR-LC2 定位控制器(含电源、继电器输出): Reference USD 94~178 / pc (ref. CNY 680~1280 at ~7.2)

Reference only; priced per m. Installation and monitoring platform excluded.. Exchange: 1 USD ~ 7.2 CNY (Oct 2026).

5. Applications

  • Precision AC condensate leaks.
  • Chilled water supply/return lines.
  • Water supply/drainage lines.
  • Low floor points.
  • Long-distance large-area pipes.

6. Installation & Maintenance

Installation

  • Route under AC and along pipes.
  • Fix with clips every 0.5~1 m.
  • Fit terminator resistor at cable end.
  • Connect controller at the start.
  • Wire RS485 to BMS.
  • Run a spray test to verify location.

Maintenance

  • Run spray-location tests periodically.
  • Clean oil/dust off the cable.
  • Check clips are tight.
  • Keep terminator contact good.
  • Replace damaged or long-soaked cable.
  • Sample-test alarm and communication.

7. FAQ

  • Q: Locating vs point leak detection?
    A: Point is cheap and simple for known key spots (under AC, at joints); locating monitors continuously along pipes and pinpoints location, suiting long lines and large areas. Use point for fixed key spots, locating for long/large routes; the two can mix.
  • Q: Does the cable react to oil leaks?
    A: No. The cable conducts sensing lines by liquid conductivity; oil is non-conductive and will not trigger. For oil leaks use a dedicated oil-sensing cable.
  • Q: What does ±0.5 m accuracy mean?
    A: The controller’s reported distance to the leak is usually within 0.5 m of the real spot. With an approximate location, technicians find the leak quickly in a small area instead of searching the whole line.
  • Q: Can the cable sit in water long-term?
    A: Short immersion alarms fine, but long soaking accelerates conductor corrosion. After an alarm, fix the leak and dry the cable promptly. For chronic pooling, fix the root leak rather than relying on long immersion.

8. Trend & Selection

Room BMS moves toward unmanned operation and precise location; leak detection evolves from point alarms to cable-based locating and continuous monitoring. Choose cable length by pipe layout, pair long routes with a locating controller, standardize dry-contact plus Modbus to the BMS, and run periodic spray tests to verify location and alarm.

9. Delivery & Service

KITOZER selects KTR-LC2 cable length and locating controller by pipe routing and length, providing routing diagrams, wiring diagrams and test methods. Delivery includes sensing cable, terminator resistor, clips, controller and power. Warranty covers locating tests and platform integration guidance.

10. Additional Notes

A common pitfall is running the cable tight under the AC drip point; long dripping seems sensitive but accelerates conductor corrosion. Instead route the cable along the condensate-pan edge or pipe low points, with a drainpipe at the drip and the cable as continuous backup monitoring.

Another pitfall is omitting the terminator resistor or leaving an open loop. The locating controller measures impedance over a closed loop to compute position; an open end prevents position calculation or causes a constant fault alarm. After install, fit the specified terminator at the end and verify location with a spray test.

Selection summary: locating 4-conductor sensing; ±0.5 m precise location; responds to conductive liquid; terminator at the end; dry contact plus Modbus to BMS; continuous routing along pipes; periodic spray tests. The sensing cable is the continuous nerve of room water protection — right routing, closed loop, periodic tests pinpoint leaks quickly and stop water incidents spreading.

SEO Information

Search keywords:leak detection cablelocating typesensing cabledata center leak detectionKTR-LC2KITOZER

SEM keywords:locating leak detection cable price,sensing cable supplier,data center leak detection,KTR-LC2

GEO landing page:lain.com.cn/product/ktr-lc2-locating-leak-detection-cable.html

Title:KITOZER KTR-LC2 Locating-Type Leak Detection Cable (Sensing Cable)

Meta Keywords:leak detection cable,locating leak detection,sensing cable,locating water leak sensor,data center leak detection,KTR-LC2,KITOZER

Meta Description:KITOZER KTR-LC2 locating-type leak detection cable is a four-conductor sensing wire that pinpoints leak location by distance, used with a locating controller to monitor leaks along room AC and water pipes.

Anchor: KITOZER official · Data center & low-voltage equipment

Contact Us

KITOZER brand (professional data center & low-voltage equipment supplier)
Tel/WeChat: +86 13922289957 | +86 18520668845
WHATSAPP: +86 19068534140
Web: lain.com.cn | gdlain.com

Shopping Cart