Scope note: This page covers integrated micro-module options that can be specified with aisle containment. Physical containment architecture, sealing class and airflow design are documented on the dedicated containment page.
I. System Introduction
The modular cold and hot aisle containment system serves as the core infrastructure for airflow organization and environmental management in data center computer rooms. It uses an enclosed cold-hot air isolation design to organize airflow paths. Cooling utilization and room management performance are confirmed per project. Integrated with multiple subsystems including cabinets, aisle containment components, in-row air conditioners, power supply and distribution, environment monitoring, and security protection, the system features a modular architecture that supports rapid deployment, flexible expansion, and intelligent operation and maintenance. It can help manage data-center energy use (PUE confirmed per project), improve equipment operation reliability and energy efficiency ratio, and comply with the national “dual carbon” strategic goals and green development requirements of data centers.
Core Working Principle
Dual rows of cabinets are arranged face-to-face to form cold aisles and back-to-back to form hot aisles. After the cold aisles are enclosed, the system is designed to guide supply air into the contained aisle toward server inlets; performance is confirmed per project. The heated hot air flows back to the air conditioner return air side through the top of the hot aisles, realizing physical isolation of cold and hot airflow. This mechanism eliminates local hotspots thoroughly and greatly improves the overall cooling efficiency of the computer room.
II. System Composition
| System Module | Core Components | Function Description |
| Aisle Containment System | Manual/automatic sliding glass doors, fixed/flip skylights, aisle frames, blanking panels, sealing strips | Realize physical isolation of cold and hot aisles, block airflow short circuits, and support automatic opening via fire linkage |
| Cabinet System | Standard server cabinets (600/800mm width), equipment mounting rails, cable organizers, thermal blanking panels | Bear IT equipment loads, optimize internal airflow paths, and eliminate internal cabinet hotspots |
| Cooling System | In-row air conditioners, air wall systems, airflow distribution devices | Adopt proximal cooling and precise air supply with temperature-control accuracy and cooling capacity confirmed per project |
| Power Supply & Distribution System | Intelligent precision distribution cabinets, UPS modules, battery packs, PDU | Provide high-efficiency power supply with redundant design and hot-swap support, achieving power conversion efficiency over 96% |
| Environment Monitoring System | Temperature and humidity sensors, airflow sensors, smoke detectors, monitoring hosts, alarm devices | Real-time monitoring of environmental parameters with multi-channel alarms, shortening fault location time to 8 minutes |
| Security System | Access control (password/card/fingerprint/face recognition), video surveillance, electronic locks | Implement aisle access authority management, safety protection and fire linkage control |
| Lighting System | LED cool white lighting, human body induction control, emergency lighting | Realize energy-saving intelligent lighting and ensure emergency lighting guarantee |

III. System Classification
1. Classification by Aisle Type
| Type | Features | Applicable Scenarios |
| Cold Aisle Containment System | Enclosed cold aisle with centralized cold air supply and open hot aisles | Medium and low-density data centers, traditional computer room renovation, scenarios with a defined PUE target (confirmed per project) |
| Hot Aisle Containment System | Enclosed hot aisle for centralized hot air discharge and open cold aisles | High-density data centers and heat-concentrated areas requiring precise hot air backflow control |
| Dual Cold & Hot Aisle Containment System | Fully enclosed cold and hot aisles with complete airflow isolation and independent circulation | High-density cabinets with a defined PUE target (confirmed per project) |
2. Classification by Deployment Mode
| Type | Features | Applicable Scenarios |
| Single-Row Aisle System | Single row of cabinets with single-side enclosure, simple structure and flexible deployment | Small computer rooms, edge computing nodes, space-limited scenarios |
| Double-Row Aisle System | Dual rows of cabinets arranged face-to-face for excellent enclosure effect and high cooling efficiency | Small and medium-sized data centers, standard computer room construction with 12-48 cabinets |
| Multi-Row Aisle System | Combined multi-row cabinets forming multiple cold and hot aisles with large-scale expansion support | Large-scale data centers, cloud data centers and ultra-large-scale deployment scenarios |
3. Classification by Intelligence Level
| Type | Features | Applicable Scenarios |
| Basic System | Manual control, basic environmental monitoring without intelligent adjustment | Budget-limited small computer rooms and non-critical business scenarios |
| Intelligent System | Automatic control, intelligent environmental monitoring, remote management and fault early warning | Medium-sized data centers and critical business scenarios requiring improved O&M efficiency |
| Smart System | AI intelligent adjustment, load linkage control, energy consumption analysis and predictive maintenance | Large-scale data centers, core business scenarios in finance and telecommunications, and green data center certification scenarios |

IV. System Configuration List (Brand: KITOZER)
4.1 Cold Aisle Containment System Configuration
| No. | Product Name | Model | Brand | Quantity | Technical Specifications |
| 1 | Standard Server Cabinet | KT-Z600/KT-Z800 | KITOZER | On-demand | 2000/2200mm height, 600/800mm width, 1100/1200mm depth, load capacity ≥1000kg, equipped with thermal blanking panels |
| 2 | Manual Sliding Glass Door | KT-CG600/KT-CG800 | KITOZER | 2 sets per aisle | Tempered glass with thickness ≥8mm, DC-24V fire linkage core-pulling lock, manual opening force ≤50N |
| 3 | Fixed Flip Skylight | KT-CT600/KT-CT800 | KITOZER | 1 set per aisle | Fire-retardant material, automatic fusing opening function (72℃), fire linkage control support |
| 4 | Aisle Frame | KT-CK600/KT-CK800 | KITOZER | 1 set per aisle | Aluminum alloy material, modular design, 450mm higher than cabinet top, compatible with mainstream cabinet layouts |
| 5 | Sealing Blanking Panel | KT-MB19/KT-MB24 | KITOZER | On-demand | 19/24-inch size, ABS material, used for sealing unused cabinet U positions to eliminate turbulent flow |
| 6 | Sealing Strip | KT-MS10 | KITOZER | On-demand | EPDM rubber material, temperature resistance range: -40℃~120℃, excellent sealing performance |
4.2 Cooling & Power Supply Distribution System Configuration
| No. | Product Name | Model | Brand | Quantity | Technical Specifications |
| 1 | In-Row Air Conditioner | KT-LK20/KT-LK30 | KITOZER | 1-2 units per aisle | cooling capacity and temperature-control accuracy confirmed per project, EC variable frequency fan, variable frequency compressor, hot-swap support |
| 2 | Intelligent Precision Distribution Cabinet | KT-PD630 | KITOZER | 1 unit per aisle | 630A input, 16-channel C13/C19 output, hot-swap support, conversion efficiency >96%, built-in monitoring module |
| 3 | UPS Power Module | KT-UPS10/KT-UPS20 | KITOZER | On-demand | Power-module capacity, redundancy, and conversion efficiency confirmed per project |
| 4 | Battery Pack | KT-BT12 | KITOZER | On-demand | 12V/100Ah valve-regulated lead-acid battery, 16/32 units per UPS, hot-swap support |
| 5 | Intelligent PDU | KT-PDU16 | KITOZER | 1-2 units per cabinet | 16-channel output, current monitoring, remote control and overload protection functions |
4.3 Environment Monitoring & Security System Configuration
| No. | Product Name | Model | Brand | Quantity | Technical Specifications |
| 1 | Environment Monitoring Collector | KT-DH800 | KITOZER | 1 unit per aisle | 16×RS485, 12×DI, 4×DO, 2×LAN ports, dual power supply, Modbus protocol support |
| 2 | Temperature & Humidity Sensor | KT-TH100 | KITOZER | 2-4 units per aisle | Sensor range and accuracy confirmed per project |
| 3 | Airflow Sensor | KT-QF100 | KITOZER | 2 units per aisle | Measuring range 0~10m/s, accuracy ±0.1m/s, for real-time monitoring of aisle airflow velocity |
| 4 | Access Controller | KT-MJ800 | KITOZER | 1 unit per aisle | Supports password, card, fingerprint and face recognition composite verification, storage of ≥100,000 records |
| 5 | Alarm Device | KT-GJ800 | KITOZER | 1 set per aisle | Sound & light alarm, multi-channel remote notification via WEB, email, SMS and WeChat |
| 6 | LED Lighting System | KT-LM600 | KITOZER | 1 set per aisle | LED cool white light, power ≤20W, human body induction control and emergency lighting function |

V. System Schematic Diagram
5.1 Airflow Organization Schematic of Cold Aisle Containment System
┌─────────────┐ ┌─────────────┐
│ Server Cabinet │ │ Server Cabinet │
│ (Face-to-Face Layout) │ │ (Face-to-Face Layout) │
└──────┬──────┘ └──────┬──────┘
│ │
▼ ▼
┌─────────────┐ ┌─────────────┐
│ Cold Aisle Space │◄─────┤ In-Row Air Conditioner │
│ (Enclosed Design) │ │ (Proximal Cooling) │
└──────┬──────┘ └──────┬──────┘
│ │
▼ ▼
┌─────────────┐ ┌─────────────┐
│ Hot Aisle Space │─────►│ Air Return Outlet │
│ (Open/Enclosed) │ │ (Hot Air Backflow)│
└─────────────┘ └─────────────┘
5.2 System Topology Diagram
┌─────────────────────────────────────────────────┐
│ Modular Cold & Hot Aisle System │
│ ┌─────────┐ ┌─────────┐ ┌─────────┐ ┌─────────┐ │
│ │Aisle Containment│ │ Cabinet Group │ │ Cooling System │ │ Power Distribution │ │
│ └─────────┘ └─────────┘ └─────────┘ └─────────┘ │
│ ┌─────────┐ ┌─────────┐ ┌─────────┐ ┌─────────┐ │
│ │Environment Monitoring│ │ Security System │ │ Lighting System │ │ Management Platform │ │
│ └─────────┘ └─────────┘ └─────────┘ └─────────┘ │
└─────────────────────────────────────────────────┘
│ │ │
▼ ▼ ▼
┌─────────────┐ ┌─────────────┐ ┌─────────────┐
│ Fire System Linkage │ │ Remote O&M Center │ │ Energy Consumption Analysis System │
└─────────────┘ └─────────────┘ └─────────────┘
VI. Core Technical Parameters
6.1 Aisle Containment System Parameters
| Parameter Item | Technical Index | Remark |
| Aisle Width | 1200-1500mm | Adapt to dual-row layout of 600/800mm wide cabinets |
| Aisle Height | 2050-2400mm | 450mm higher than cabinet top, balancing ergonomics and equipment hoisting |
| Glass Door Specification | Tempered glass thickness ≥8mm, light transmittance ≥90% | Comply with GB15763.2 impact resistance standard |
| Skylight Opening Mode | Automatic flip + manual opening, manual opening angle ≥90° | 72℃ fusing automatic opening for fire linkage |
| Sealing Performance | Cold air leakage rate ≤5% | 15-20% lower than traditional open computer rooms |
| Frame Material | Aluminum alloy 6063-T5 with anodized surface | Strong corrosion resistance |
| Protection Grade | IP20 | Prevent human contact with live parts |
6.2 Cooling System Parameters
| Parameter Item | Technical Index | Remark |
| Cooling Capacity Range | 5-41kW, support multi-module parallel expansion | In-row air conditioner customized configuration |
| Temperature Control Accuracy | Confirmed per project | Comply with ASHRAE data center environmental standards |
| Air Supply Temperature | 18-22℃ | Comply with T/GDEA 002-2023 standard |
| Air Return Temperature | 28-33℃ | Optimize cooling efficiency |
| Fan Type | EC variable frequency fan, 0-100% speed regulation | Energy-saving efficiency is confirmed per project |
| Compressor Type | Compressor type and COP confirmed per project | Soft start support |
| Noise Level | Confirmed per project | Meet computer room noise standards |
6.3 Monitoring & Security System Parameters
| Parameter Item | Technical Index | Remark |
| Temperature & Humidity Monitoring | Temperature and humidity range confirmed per project | Real-time monitoring and over-limit alarm |
| Access Control System | Multi-factor verification, storage of ≥100,000 records | Data storage duration ≥1 year |
| Alarm Mode | Sound & light alarm + remote notification (email/SMS/WeChat) | Fault location time ≤8 minutes |
| Communication Interface | RS485, DI/DO, LAN, USB | Support Modbus, SNMP protocols |
| Power Supply Mode | DC12V/24V, dual power redundancy | Ensure stable system operation |

VII. Application Scope
7.1 Industry Application Fields
| Industry | Application Scenarios | Core Requirements |
| Internet & Cloud Computing | Large data centers, edge computing nodes | High-density deployment; PUE and expansion time confirmed per project |
| Financial Industry | Bank data centers, securities trading systems | High reliability, redundant design, fast fault recovery |
| Telecom Operators | Core computer rooms, aggregation computer rooms | Large-scale deployment, remote O&M, energy consumption optimization |
| Government Institutions | Government cloud platforms, e-government systems | Safety and reliability, green energy saving, policy compliance |
| Energy Industry | Power dispatch centers, new energy monitoring systems | Harsh environment adaptability, strong anti-interference ability |
| Medical Industry | Medical data centers, image storage systems | Constant temperature and humidity, data security, 24-hour operation |
| Education & Research | University data centers, scientific computing platforms | High-performance computing, flexible expansion, cost control |
7.2 Scenario Application Classification
| Scenario Type | Features | Recommended Solution |
| New Data Center | Full planning and construction from scratch | Dual cold & hot aisle containment, smart configuration; PUE confirmed per project |
| Computer Room Renovation | Upgrade based on existing facilities with space constraints | Cold aisle containment, modular rapid deployment |
| High-Density Area | High power density with hotspot issues (density confirmed per project) | Hot aisle containment + in-row air conditioner for precise cooling |
| Edge Computing Node | Miniaturized, flexible deployment, unattended operation | Single-row aisle system, intelligent configuration & remote management |
VIII. Core Product Advantages
8.1 Core Technical Advantages
- Precise Airflow Control: The enclosed aisle is designed to isolate cold and hot air streams. Airflow isolation performance is confirmed per project. PUE and energy saving versus a traditional room are confirmed per project.
- Modular Architecture: Interchangeable component design supports rapid deployment (deployment time confirmed per project) and flexible later expansion, effectively reducing initial investment and operation & maintenance costs.
- Intelligent Environmental Management: AI algorithm adjusts cooling capacity and airflow; temperature-control accuracy is confirmed per project. Fault-location time and O&M efficiency are confirmed per project.
- High-Reliability Design: Adopts redundant power supply, fire linkage and multi-layer security protection, helping reduce downtime risk. MTTR is confirmed per project.
- Green Energy-Saving Certification: Certification support is confirmed per project when a bid requires it.
8.2 Full Lifecycle Value
| Stage | Value Reflection | Quantitative Index |
| Design Stage | Shorten design cycle and reduce on-site survey work | Design time and drawing standardization are confirmed per project |
| Construction Stage | Rapid deployment and shortened construction cycle | Installation efficiency and deployment time confirmed per project |
| Operation Stage | Energy saving and consumption reduction, lower O&M costs | Large data centers save 21 million kWh annually, 50% less O&M manpower |
| Expansion Stage | Smooth expansion without business interruption | 80% shorter expansion time, online hot-swap support |
| Decommissioning Stage | Component recycling and waste reduction | Component recycling rate ≥90%, compliant with circular economy standards |

IX. Reference Parameters
9.1 Aisle Containment System Reference Parameters
| Parameter Item | Bid Requirements | Compliance Standard |
| Aisle Frame | Aluminum alloy modular design, 450mm higher than cabinet top, compatible with 600/800mm wide cabinets | T/GDEA 002-2023 Clause 5.2 |
| Glass Door | Tempered glass thickness ≥8mm, light transmittance ≥90%, DC-24V fire linkage lock, opening force ≤50N | GB15763.2 Standard |
| Skylight | Fire-retardant material, 72℃±2℃ fusing automatic opening, fire linkage control, opening angle ≥90° | GB50116-2013 |
| Sealing Performance | Cold air leakage rate ≤5%, airflow velocity uniformity deviation ≤10% | T/GXDSL 003-2025 |
| Protection Grade | Component protection grade ≥IP20, glass door impact resistance up to national standard | GB4208-2017 |
9.2 Cooling and Monitoring System Reference Parameters
| Parameter Item | Bid Requirements | Compliance Standard |
| Cooling Capacity | In-row air conditioner cooling capacity and expansion confirmed per project | ASHRAE Data Center Standard |
| Temperature Control Accuracy | Cold aisle temperature and regional difference confirmed per project | T/GDEA 002-2023 Clause 5.3 |
| Monitoring System | Support multi-parameter monitoring, ≥5 alarm modes, response time ≤3 seconds | GB50174-2017 |
| Redundancy Design | N+1 redundancy for power supply and cooling systems, no single point of failure | Uptime Tier Standard |
| Energy Saving Index | PUE, cooling COP, and fan type confirmed per project | National Energy-Saving & Carbon Reduction Guidelines |
9.3 Safety and Reliability Reference Parameters
| Parameter Item | Bid Requirements | Compliance Standard |
| Fire Linkage | Fire signal linkage, skylight opening time ≤3s, automatic glass door unlocking | GB50116-2013 |
| Access Control System | Multi-factor authentication, 100,000+ record storage, data retention ≥1 year | GB50348-2018 |
| Seismic Performance | Aisle frame seismic grade ≥8, cabinet seismic grade ≥9 | GB50011-2010 |
| Service Life | Main components service life ≥10 years, MTBF≥100,000 hours | Data Center Infrastructure Reliability Standard |
| Environmental Protection | RoHS compliant, noise ≤60dB, national first-class energy efficiency | GB/T 2887-2011 |

X. Customized Solution Packages
10.1 New Data Center Solution
Solution Overview: Adopt dual cold and hot aisle containment system, integrate power supply, cooling, monitoring and security subsystems to build a green, efficient, intelligent and reliable data center infrastructure.
Core Configuration:
- Aisle System: Dual cold & hot aisle containment, aluminum alloy frame, automatic sliding glass door, fixed flip skylight
- Cooling System: In-row air conditioner and air-wall capacity confirmed per project
- Power Supply: Intelligent precision distribution cabinet + UPS module and battery redundancy confirmed per project
- Monitoring System: Smart environment monitoring, AI predictive maintenance, multi-channel alarm
- Security System: Face recognition access control + video surveillance + electronic lock with multi-level authority management
Implementation Steps: 1. BIM+CFD simulation for layout optimization; 2. Foundation construction and equipment positioning; 3. Multi-system integration and commissioning; 4. Performance testing and acceptance; 5. Long-term remote O&M support
Expected Effect: PUE, cooling efficiency, O&M cost, and recovery time are confirmed per project
10.2 Computer Room Renovation Solution
Solution Overview: Upgrade existing computer rooms with cold aisle containment system to eliminate hotspot problems, improve cooling efficiency and reduce energy consumption without business interruption.
Core Configuration:
- Aisle System: Cold aisle containment, manual sliding glass door, fixed flip skylight and sealing blanking panels
- Cooling System: In-row air conditioner capacity confirmed per project, linked with existing cooling equipment
- Monitoring System: Intelligent environment monitoring with temperature, humidity and airflow monitoring & remote alarm
- Power Optimization: Add intelligent PDU for energy consumption monitoring and remote control
Implementation Steps: 1. Current situation assessment and hotspot detection; 2. Modular customized design; 3. Rapid on-site assembly; 4. System linkage debugging; 5. Effect verification and parameter optimization
Expected Effect: PUE, hotspot control, energy saving, and renovation method are confirmed per project
10.3 High-Density Area Solution
Solution Overview: Targeting high-density areas (power density confirmed per project), adopt hot aisle containment + high-power in-row air conditioner scheme