KITOZER Fire Detection Tube Gas Fire Suppression Solution for Computer Rooms

Table of Contents

I. System Introduction

Fire detection tube fire suppression system, also known as fire trace tube extinguishing device, is an innovative automatic fire-fighting unit integrating fire detection and fire suppressant discharge into one set. It is specially developed for fire protection of enclosed or semi-enclosed narrow spaces such as computer rooms and server cabinets. Free from external power supply and complicated electrical control assemblies, the system relies on a single pressurized flexible fire detection tube to fulfill both fire sensing and fire agent delivery functions. When ambient temperature around the tube hits the preset activation value of 170±10℃, the tube softens and ruptures at the hottest spot to instantly release fire suppressant for ultra-early rapid fire suppression, safeguarding precision electronic equipment and data security inside computer rooms.

With advanced design concepts and premium raw materials, KITOZER fire detection tube gas fire suppression system features easy installation, low maintenance cost, fast response and outstanding fire extinguishing efficiency. It serves as an ideal fire protection option for computer rooms, especially for electronic equipment premises requiring high cleanliness and zero water damage pollution.

II. System Composition

The KITOZER fire detection tube gas fire suppression system consists of the below core components which coordinate to guarantee stable and reliable system operation:

  • Fire suppressant cylinder assembly: Stores clean gaseous extinguishing agents including HFC-227ea and carbon dioxide as fire suppression medium; manufactured with high-strength alloy for safety and stability.
  • Container valve: Core control component for suppressant release, connected with fire detection tube and discharge piping, pre-installed with built-in pressure gauge and safety relief assembly.
  • Fire detection tube: Flexible composite pipeline combining fire detection and medium conveyance; made of special high-temperature resistant composite material with nominal activation temperature at 170±10℃.
  • Discharge pipe: Connects container valve to nozzles to convey extinguishing agent into protected enclosure.
  • Nozzle: Evenly diffuses fire suppressant to secure optimal fire suppression performance; multiple specifications available to match different protected spaces and agent types.
  • Signal feedback module: Monitors real-time system status and transmits alarm signal to central fire control panel upon fire breakout for remote supervision.
  • Terminal pressure gauge: Tracks internal pressure of fire detection tube to confirm system stays under normal working condition.
  • Pipe fittings & accessories: Including couplings, tees, elbows and fixing clips for pipe connection and secure mounting of detection tube and discharge pipeline.
  • Protection sleeve: Shields pipe sections passing through walls or floor slabs to avoid abrasion and mechanical damage of fire detection tube.
fire detection tube gas fire suppression solution (1)

III. System Classification

Classified by installation mode, working principle and extinguishing medium, KITOZER fire trace tube fire suppression solutions fall into three categories:

(I) Classification by structural configuration

1. Direct-type Fire Detection Tube Suppression System

  • Working Principle: Fire detection tube is laid directly inside protected equipment such as server cabinets. Once tube ruptures under fire heat, extinguishing agent sprays directly from the crack onto ignition source for pinpoint local fire putout.
  • Application: Compact independent confined spaces including server cabinets, UPS power cabinets and network equipment enclosures with clearly defined protected targets.
  • Advantages: Targeted fire suppression, less agent consumption, minimum impact on surrounding environment and flexible field layout.

2. Indirect-type Fire Detection Tube Suppression System

  • Working Principle: Fire trace tube is routed inside the overall protected room. Tube rupture triggers container valve opening; suppressant flows via discharge piping and nozzles to flood the entire compartment for total flooding fire suppression.
  • Application: Medium-size enclosed premises such as small computer rooms, power distribution rooms and battery rooms requiring full-space equipment protection.
  • Advantages: Large coverage range, perfect for clustered multi-equipment zones with comprehensive fire containment capability.

(II) Classification by extinguishing agent type

1. HFC-227ea Based Fire Trace Tube System

  • Features: Zero ODP (Ozone Depletion Potential), low GWP (Global Warming Potential), residue-free after discharge with no corrosion to electronic hardware; high extinguishing efficiency and suitable for manned computer room areas.
  • Application: Server rooms, data centers and precision instrument laboratories with stringent equipment & environmental requirements.

2. COâ‚‚ Based Fire Trace Tube System

  • Features: Excellent electrical insulation property, rapid fire knockdown and cost-effective; however COâ‚‚ displaces oxygen in enclosed space and is prohibited for long-term occupied areas.
  • Application: Unattended equipment chambers, UPS rooms and battery storage rooms.

3. FK-5-1-12 (Novec 1230) Perfluorohexanone Fire Suppression System

  • Features: New-generation eco-friendly clean agent with ultra-low toxicity; liquid under ambient temperature, fully vaporizes post-discharge leaving no residue and imposes no harm to devices or surroundings.
  • Application: High-end premium computer rooms and scientific research laboratories with strict environmental protection standards.
fire detection tube gas fire suppression solution (3)

(III) Classification by control mode

1. Fully Mechanical Fire Trace Tube System

  • Activates entirely via thermal sensing of fire detection tube without any electrical power supply; applicable for sites with no power access or unstable mains electricity.
  • Advantages: Simplified construction, superior reliability free from power failure failure risk and minimal routine maintenance expense.

2. Electrically Linked Fire Trace Tube System

  • Equipped with electric control system supporting automatic startup, local manual activation and remote emergency control; capable of interlocking power cut-off and ventilation shutdown in case of fire.
  • Advantages: Complete functional configuration and intelligent management, applicable for large-scale centralized-monitoring data centers and computer room clusters.

IV. Standard System Configuration List (KITOZER Brand)

Configurations can be flexibly adjusted according to computer room floor area and quantity of protected equipment.

(I) Direct HFC-227ea Fire Trace Tube System (Cabinet Dedicated)

  1. HFC-227ea Cylinder Set, Model KT-Q-3, 3kg agent filling, 2.5MPa storage working pressure
  2. Matching Container Valve KT-FV-3 with built-in pressure indicator
  3. Fire Trace Tube KT-T-6×4, specification OD6mm×ID4mm, activation temperature 170±10℃
  4. Pipe Connectors KT-JT-6 including tees and elbows for tube assembly
  5. Terminal Pressure Gauge KT-PG-1.6, measuring range 0~1.6MPa
  6. Signal Feedback Module KT-SF-24V, DC24V rated, contact capacity 1A/24VDC
  7. Fixing Clips KT-FC-6 for tube fastening with max mounting spacing ≤500mm
  8. Wall-penetration Protection Sleeve KT-ST-10, inner diameter 10mm
  9. Product Installation Manual KT-MS-Q3 with construction drawings and operation specification

(II) Indirect HFC-227ea Fire Trace Tube System (Whole Computer Room Protection)

  1. HFC-227ea Cylinder Assembly KT-Q-70, 70kg agent charge, rated storage pressure 4.2MPa@20℃
  2. Matching Electromagnetic Container Valve KT-FV-70 with solenoid actuator
  3. Fire Trace Tube KT-T-8×6, OD8mm×ID6mm, nominal activation temperature 170±10℃
  4. Main Discharge Pipe KT-RP-25, outer diameter 25mm for agent transportation
  5. Full-flooding Nozzle KT-NZ-25 matched for DN25 discharge pipeline
  6. Special Pipe Joint KT-JT-8 for 8×6mm specification fire detection tube
  7. Discharge Pipe Fitting Package KT-RP-JT consisting of elbows, tees and flanges
  8. AC220V Signal Feedback Device KT-SF-220V, contact load 5A/220VAC
  9. Cylinder Pressure Switch KT-PS-4.2, measurement scope 0~4.2MPa
  10. Emergency Manual Actuator KT-MS-220V with emergency stop function
  11. Cylinder Fixing Bracket KT-FR-70 for 70kg storage tank installation
  12. Fixing Clamp KT-FC-8 for 8×6mm fire trace tube
  13. Special Installation Tool Kit KT-TK-01 including sealing accessories
  14. Factory Acceptance Test Report KT-TR-Q70 covering pressure inspection and full function test records
fire detection tube gas fire suppression solution (5)

V. System Working Schematic & Operation Flow

(I) Direct-type System Flow

plaintext

HFC-227ea Cylinder → Container Valve → Fire Detection Tube → Terminal Pressure Gauge
                        ↳ Signal Feedback Module → Central Fire Control Panel
  1. Fire trace tube is arranged inside server cabinets closely adjacent to heating components and cable terminals.
  2. Tube softens and ruptures under high temperature during fire outbreak.
  3. Container valve opens automatically; extinguishing agent sprays directly from the broken tube onto fire source.
  4. Signal feedback component sends fire alarm to fire control center.
  5. After fire elimination, system can be manually reset by replacing damaged detection tube and refilling fire suppressant for reuse.

(II) Indirect-type System Flow

plaintext

HFC-227ea Cylinder → Container Valve → Discharge Pipeline → Full-flooding Nozzles
       ↳ Fire Detection Tube → Terminal Pressure Gauge
       ↳ Signal Feedback Module → Central Fire Control Panel
       ↳ Emergency Manual Starter
       ↳ Cylinder Pressure Switch
  1. Fire trace tube is mounted on ceiling to cover the entire protected computer room.
  2. Tube bursts at overheated position upon fire occurrence to trigger container valve opening.
  3. Fire suppressant flows via piping and nozzles to flood the full enclosed space.
  4. Alarm signal is uploaded to fire control room, supporting interlock power off and ventilation closure.
  5. On-site manual startup available for emergency fire response if detection tube fails to activate.
  6. Pressure switch continuously monitors cylinder internal pressure to ensure normal standby status.
fire detection tube gas fire suppression solution (6)

VI. Core Technical Specifications

(I) Universal Technical Parameters

  • Operating ambient temperature: -10℃ ~ +50℃
  • Storage temperature range: -20℃ ~ +55℃
  • Nominal activation temperature of fire trace tube: 170±10℃
  • Max permissible tube length: Direct system ≤35m; Indirect system ≤50m
  • Minimum bending radius of detection tube: ≥60mm
  • System full response duration (tube rupture to complete agent discharge): ≤10s, complying with GB50370-2005
  • Fire suppression mode: Direct = Local spot spray; Indirect = Total flooding
  • Max protected enclosure volume: Direct ≤10m³; Indirect ≤100m³
  • Design service lifespan of complete system: ≥8 years
  • Full agent ejection time: ≤10s

(II) HFC-227ea System Specific Index

  • Agent Grade: HFC-227ea with purity ≥99.9%
  • Storage Pressure@20℃: 2.5MPa (3kg direct set); 4.2MPa (70kg indirect set)
  • Design extinguishing concentration for computer room: 8%~10% by volume
  • Agent design dosage: ≥1.5kg per cubic meter
  • Cylinder material: High-grade alloy steel; Outer diameter:159mm(3kg)/325mm(70kg)
  • Discharge duration: ≤8s(3kg)/≤10s(70kg)

(III) Fire Detection Tube Technical Data

Specification 6×4mm / 8×6mm

  • Construction: Special high-temperature resistant composite material, standard red color with customizable alternative colors
  • Rated working pressure:1.6MPa; Minimum burst pressure under normal temperature:≥2.0MPa
  • Tensile strength:≥15MPa(6×4mm)/≥18MPa(8×6mm)
  • Chemical resistance: Resistant against common acid, alkali and petroleum solvent corrosion
  • Flame retardancy grade: UL94 V-0

(IV) Container Valve Technical Specification

  • Applicable cylinder capacity:3kg /70kg
  • Rated working pressure:2.5MPa /4.2MPa
  • Startup mode: Auto by tube rupture; Indirect version adds manual emergency opening
  • Built-in safety relief valve: Opening pressure 3.0MPa(3kg)/5.0MPa(70kg)
  • Thread interface:G1/2″(3kg)/G2″(70kg); Material: Chrome-plated brass / Stainless steel
  • Max manual opening operating force ≤150N
fire detection tube gas fire suppression solution (7)

VII. Application Scope

(I) IT & Telecommunication Industry

Data center server room, network equipment chamber, independent server cabinet, blade server enclosure, UPS and battery room, precision air conditioning room, communication base station core network room, cloud computing & big data storage center.

(II) Financial Industry

Bank core data & liquidation center, ATM machine server room, financial transaction system equipment chamber.

(III) Power Industry

Substation control & relay room, power dispatching center, automatic control equipment room of new energy power plant.

(IV) Industrial Sector

PLC & inverter control cabinet, industrial computer room, robot control cabinet, semiconductor production workshop and precision instrument lab.

(V) Other Fields

Medical MRI & CT equipment control room, archive & digital reading room, military confidential command room, rail transit signal equipment room.

fire detection tube gas fire suppression solution (8)

VIII. Core Product Advantages vs Conventional Fire Protection Systems

1. Easy Installation & Minimal Site Renovation

Simple structural layout requires few power cables and auxiliary pipelines with negligible damage to original room decoration; detection tube can be routed inside cabinets without cabinet modification. Single computer room can finish installation and commissioning within 1~2 working days.

2. Ultra-fast Response & Superior Fire Extinguishing Efficiency

Direct contact between sensing tube and heat source enables fire suppression within several seconds, much faster than conventional smoke/heat detector alarm systems. Local high agent concentration boosts fire knockdown efficiency by over 30% and restricts fire spread effectively.

3. Power-free Mechanical Design with Outstanding Stability

Direct-type setup runs fully mechanically independent from mains supply, perfectly suitable for backup power and UPS rooms affected by blackout. Less failure points with MTBF ≥50000 hours for round-the-clock unattended operation and low maintenance cost.

4. Residue-free Clean Fire Suppression without Secondary Damage

Adopts zero-ODP eco-friendly clean gaseous agents; no residual sediment or water stain after discharge to protect electronic devices, paper archives and interior decoration materials.

5. Targeted Suppression Reduces Agent Consumption

Direct system releases suppressant only at fire location to cut agent cost by 30%~50%; indirect system calculates precise filling volume based on actual enclosure volume to avoid redundant waste.

6. Intelligent Remote Monitoring & Emergency Manual Control

Built-in signal feedback component realizes real-time fault diagnosis and fire alarm linkage with central fire control room; indirect configuration supports on-demand manual emergency startup for unexpected fire events.

7. Low-cost Convenient Routine Maintenance

Annual single inspection on system pressure and tube condition suffices for regular maintenance; replacement of damaged tube and agent refill is quick without shutdown of normal computer room operation.

IX. Tender Bid Specification Parameters

Used as technical requirements for bidding and procurement, all products comply with GB 25972-2010 Gas Fire Extinguishing Systems & Components and GA 1167-2014 Fire Trace Tube Fire Extinguishing Device, with valid national fire product inspection report and CCC certification available.

1. Fire Trace Tube Requirement

Made of special high-temperature resistant composite material, nominal activation temperature 170±10℃ with permissible tolerance ±5℃; available in 6×4mm /8×6mm, seamless uniform wall thickness free of bubble or crack; rated working pressure 1.6MPa, minimum burst pressure ≥2.0MPa; min bending radius ≤60mm, excellent chemical stability with service life ≥8 years.

2. Fire Agent & Cylinder Requirement

HFC-227ea agent purity ≥99.9% complying with GB18614-2012; cylinder manufactured from qualified alloy steel per GB5099 with built-in pressure gauge and safety relief valve; standard storage pressure:2.5MPa(3kg)/4.2MPa(70kg)@20℃.

3. Container Valve Requirement

Indirect type supports automatic & dual manual startup; equipped with signal feedback output, good sealing performance under rated working pressure without leakage; manual opening pulling force ≤150N, standard national standard thread connection.

4. Overall System Performance Index

Total response time ≤10s; full agent ejection ≤10s; design extinguishing concentration 8%~10% for computer room; excellent anti-electromagnetic interference property with overpressure protection and low-pressure early warning function.

X. Customized Engineering Solutions

(I) Direct-type Cabinet Fire Protection Solution

  • Applicable for single or multiple independent server cabinets, high-density blade server computer room.
  • Design feature: Fire trace tube fixed inside cabinet alongside CPU, power supply and cable joints; 3kg HFC-227ea cylinder mounted on cabinet top/side without floor occupation; individual independent set for each cabinet connected to central fire control via signal feedback.
  • Design standard: Tube layout spacing ≤300mm, minimum 50mm clearance between tube and heating component to prevent false activation.

(II) Indirect Whole-room Computer Room Fire Protection

  • Suitable for small & medium enclosed computer room within 100㎡ floor area and room height ≤3.5m.
  • Design feature: Ceiling-mounted fire detection tube covering full space, 70kg cylinder matched according to room volume; uniformly distributed nozzles for full flooding, interlock with fire control center for remote monitoring and emergency manual startup, supporting power & ventilation cut-off linkage.
  • Design standard: Max nozzle spacing ≤3m, tube routed avoiding air supply outlet and ventilation duct.

(III) Hybrid Fire Protection for Large-scale Data Center

Combination of direct cabinet protection and indirect full-room flooding: Each server cabinet equipped with independent direct fire trace system; entire data center configured with indirect full-room suppression set; whole system interlinked with building BMS and gas fire controller for partitioned intelligent fire control, redundant design to guarantee continuous protection upon single component fault.

XI. Actual Project Cases

Case 1: Internet Enterprise Cloud Data Center (80㎡, 50 server racks)

Adopted hybrid solution: 50 sets KT-Q-3 direct system for individual cabinets + one set KT-Q-70 indirect full-room system. Completed installation within 3 days without equipment shutdown; simulated fire test response ≤5s with reliable suppression effect, later promoted across the enterprise’s other data center projects.

Case 2: Bank Financial Clearing Center (50㎡, 30 cabinets)

Full direct KT-Q-3 per cabinet linked with bank central fire control panel. Pure mechanical structure works stably during power outage; residue-free discharge ensures uninterrupted financial transaction operation and reduces long-term maintenance expenditure.

Case 3: Power Dispatching Control Room (100㎡,40 cabinets)

Two sets KT-Q-70 indirect system plus partial direct-type protection on core equipment; strong anti-electromagnetic interference to adapt complex high-voltage surrounding environment, linked with power automation platform and passed industry fire acceptance standard.

XII. SEO Keywords & Tags

Core Search Keywords

computer room fire protection, fire trace tube gas suppression, KITOZER fire detection tube, HFC-227ea fire suppression system, data center fire fighting, server cabinet fire protection, direct fire trace tube system, indirect fire trace tube system, clean gas fire extinguishing, computer room fire solution

SEO Optimization

Title: KITOZER Fire Trace Tube Gas Fire Suppression Solution for Computer Room | Clean & Precision Protection for Electronic Equipment

Meta Description: KITOZER fire detection tube fire suppression customized for data center & server room, power-free startup, rapid clean fire suppression to protect precision equipment and data safety, easy installation & low maintenance cost.

Tags

#ComputerRoomFireProtection #FireTraceTube #GasFireSuppression #HFC227ea #DataCenterSafety #ServerCabinetFire #KITOZER #CleanAgentFireSuppression #UPSRoomFire #ITRoomSolution

Shopping Cart