KITOZER Non-Piped Gas Fire Suppression Solution

I. System Introduction

1.1 System Definition

The KITOZER Pre-Engineered (Non-Piped) Gas Fire Suppression System, also known as a modular gas fire extinguishing system, is an integrated, modular automatic fire suppression unit. It highly integrates core components including agent storage cylinders, actuation devices, nozzles, and control units. Without complex piping networks, it is installed directly inside or adjacent to the protected zone. Upon fire detection, it discharges extinguishing agent rapidly and precisely to achieve total flooding or local application fire suppression. Ideal for data centers, computer rooms, and other space‑ and environment‑sensitive facilities, it serves as an excellent alternative to traditional piped gas fire suppression systems.

1.2 Working Principle

When a fire breaks out in the protected zone, smoke and heat detectors send signals to the fire alarm control panel. The panel activates audible and visual alarms, initiates interlock controls (closing ventilation, cutting off power, closing fire dampers), and enters a programmable delay stage (0–30 seconds adjustable). After the delay, the panel sends an actuation signal to open the cylinder valve. High-pressure agent is discharged directly into the zone through nozzles, quickly filling the space to extinguish fire via chemical inhibition or physical cooling. The system sends a feedback signal to the panel and illuminates the gas discharge indicator outside the zone to warn personnel against entry. The entire process is fast‑responding, highly efficient, and causes no secondary contamination to equipment or the environment.

1.3 Design Codes

  • GB 50370‑2017 Code for Design of Gas Fire Extinguishing Systems
  • GB 50116‑2013 Code for Design of Automatic Fire Alarm Systems
  • GB 50016‑2014 Code for Design of Building Fire Protection (2018 Edition)
  • GB 25972‑2010 Gas Fire Extinguishing Systems and Components
  • GB 16670‑2006 Cabinet Gas Fire Extinguishing Equipment
pipeless gas fire suppression solution for computer room (1)

II. System Composition

The KITOZER Non-Piped Gas Fire Suppression System consists of the following core components that work together to ensure reliable operation:

Extinguishing Unit

  • Agent Storage Cylinder: Stores clean agent such as HFC‑227ea, withstands high pressure, and ensures tight sealing.
  • Cylinder Valve: Controls agent release with automatic and manual actuation functions.
  • Nozzle: Distributes agent uniformly for effective fire suppression.
  • High-Pressure Hose: Connects the cylinder valve to the nozzle for agent delivery.
  • Cabinet / Hanging Bracket: Secures and protects the unit; cabinet type features a protective enclosure.

Control & Detection Unit

  • Fire Alarm Control Panel: Receives detection signals, issues alarms, and controls interlocks.
  • Smoke / Heat Detectors: Provide dual‑confirmation fire detection.
  • Manual Start Button: For emergency manual system activation.
  • Emergency Stop Button: Interrupts system startup during the delay phase.
  • Gas Discharge Indicator: Lights up to show agent discharge and warn personnel.
  • Audible & Visual Alarm: Alerts occupants to evacuate.

Actuation & Feedback Unit

  • Solenoid Actuator: Receives electrical signals to open the cylinder valve.
  • Pressure Transmitter: Feeds back agent discharge status.
  • Mechanical Emergency Actuator: Enables manual startup during power failure.
  • Interlock Control Module: Controls ventilation, power, and other external devices.
pipeless gas fire suppression solution for computer room (2)

III. System Classification

3.1 By Structural Form

  • Cabinet Type: Integrated in a freestanding cabinet, large capacity, wide coverage. Suitable for small computer rooms, power distribution rooms, archives; protected area ≤500㎡, volume ≤1600m³.
  • Hanging Type: Compact, lightweight, ceiling‑mounted, no floor space. For local protection in cabinets, power distribution boxes, small equipment rooms.
  • Modular Combined System: Multiple units interconnected for expanded coverage. For larger computer rooms or multiple adjacent zones.

3.2 By Extinguishing Agent

  • HFC‑227ea (FM‑200): Colorless, odorless, non‑conductive, high efficiency, zero ODP. For computer rooms, data centers, precision instrument rooms.
  • IG‑541 Inert Gas: Blend of nitrogen, argon, COâ‚‚; eco‑friendly, non‑toxic. For occupied areas and high‑environmental‑requirement rooms.
  • COâ‚‚: Effective, low cost, good for local application. For cable tunnels, transformer rooms (with personnel safety precautions).

3.3 By Actuation Mode

  • Automatic Actuation: Detector alarm → panel confirmation → delay → automatic discharge. For unmanned or fast‑response required rooms.
  • Manual Actuation: Personnel confirms fire → presses start button → discharge. For occupied areas.
  • Mechanical Emergency Actuation: Manual mechanical startup during power failure. Backup for emergency situations.
pipeless gas fire suppression solution for computer room (3)

IV. System Configuration List (KITOZER Brand)

4.1 Cabinet Type HFC‑227ea Non-Piped System

  1. Cabinet HFC‑227ea Unit KT‑GQQ70/2.5 (70L, 2.5MPa)
  2. Cabinet HFC‑227ea Unit KT‑GQQ90/2.5 (90L, 2.5MPa), as required
  3. Fire Alarm Control Panel KT‑FAC2000
  4. Photoelectric Smoke Detector KT‑JTY‑GD‑3001, as required
  5. Heat Detector KT‑JTW‑ZD‑3002, as required
  6. Manual Start Button KT‑MS‑830 (1 per zone)
  7. Emergency Stop Button KT‑ES‑831 (1 per zone)
  8. Gas Discharge Indicator KT‑GAS‑832 (1 per zone exit)
  9. Audible & Visual Alarm KT‑SA‑833 (1 per zone)
  10. Interlock Control Module KT‑IO‑834, as required
  11. Pressure Transmitter KT‑PS‑835 (1 per unit)
  12. Solenoid Actuator KT‑SOL‑836 (1 per unit, DC24V, 1.5A)
  13. Mechanical Emergency Actuator KT‑ME‑837 (1 per unit)
  14. HFC‑227ea Agent KT‑HFC‑227ea, as required
  15. Installation Accessories: brackets, cables, etc.

4.2 Hanging Type HFC‑227ea Non-Piped System

  1. Hanging HFC‑227ea Unit KT‑GQX40/2.5 (40L) / KT‑GQX60/2.5 (60L), as required
  2. Fire Alarm Control Panel KT‑FAC1000
  3. Smoke / Heat Detectors KT‑JTY‑GD‑3001 / KT‑JTW‑ZD‑3002, as required
  4. Manual Start Button KT‑MS‑830
  5. Gas Discharge Indicator KT‑GAS‑832
  6. Audible & Visual Alarm KT‑SA‑833
  7. Solenoid Actuator KT‑SOL‑836 (1 per unit)
  8. Pressure Transmitter KT‑PS‑835 (1 per unit)
  9. Hanging Mounting Bracket KT‑MOUNT‑838 (1 per unit)
  10. HFC‑227ea Agent KT‑HFC‑227ea, as required
pipeless gas fire suppression solution for computer room (4)

V. System Schematic & Flow

5.1 System Structure Diagram

[Smoke + Heat Detectors] → [Fire Alarm Control Panel] → [Interlock Module] → [Close Ventilation / Cut Power / Close Fire Damper]

↓ ↓

→ [Audible & Visual Alarm] → [Gas Discharge Indicator]

↓ ↓

→ [Manual Start Button] → [Emergency Stop Button]

↓ ↓

→ [Solenoid Actuator] → [Mechanical Emergency Actuator]

↓

[Agent Cylinder] → [Cylinder Valve] → [High-Pressure Hose] → [Nozzle] → [Protected Zone]

↓

[Pressure Transmitter] → [Feedback to Control Panel]

5.2 Operating Flow

  1. Fire occurs; smoke and heat detectors alarm simultaneously.
  2. Control panel confirms fire upon dual signals.
  3. Audible and visual alarm activates; interlocks start with 0–30s adjustable delay.
  4. Delay ends; control panel issues actuation signal.
  5. Solenoid opens cylinder valve; high-pressure nitrogen drives agent discharge.
  6. Agent discharges through nozzles to suppress fire.
  7. Pressure transmitter sends discharge feedback; gas indicator lights up.
  8. After extinguishment, system resets automatically or manually.
pipeless gas fire suppression solution for computer room (5)

VI. Technical Parameters

6.1 Cabinet Type HFC‑227ea Unit (KT‑GQQ Series)

  • Models: KT‑GQQ40/2.5, 70/2.5, 90/2.5, 120/2.5 (40L–120L)
  • Working Pressure: 2.5MPa@20℃; max 4.2MPa@50℃
  • Agent: HFC‑227ea, purity ≥99.9%
  • Filling Density: ≤1.15kg/L
  • Discharge Time: ≤10s
  • Design Concentration: 8% (computer room), 10% (archive)
  • Soaking Time: ≥3min
  • Actuation Power: DC24V, 1.5A
  • Ambient Temperature: 0℃–55℃
  • Protected Volume: Single unit ≤1600m³; multiple units ≤5000m³

6.2 Hanging Type HFC‑227ea Unit (KT‑GQX Series)

  • Models: KT‑GQX20/2.5, 40/2.5, 60/2.5 (20L–60L)
  • Working Pressure: 2.5MPa@20℃
  • Discharge Time: ≤10s
  • Design Concentration: 8%–10%
  • Actuation: Automatic / Manual / Mechanical Emergency
  • Ambient Temperature: -10℃–55℃
  • Mounting Height: 2.5m–3.5m
  • Protected Area: Single unit ≤50㎡

6.3 Fire Alarm Control Panel (KT‑FAC Series)

  • Model KT‑FAC2000: up to 32 zones
  • Power: AC220V / DC24V dual supply
  • Backup Battery: ≥8h operation
  • Alarm: Audible & visual, ≥85dB
  • Interlock Output: 16 channels
  • Display: 7-inch color LCD
  • Communication: RS485, Ethernet
  • Ambient: 0℃–40℃, ≤95%RH (non‑condensing)

VII. Application Scope

  • Data Centers & Computer Rooms: Server rooms, network rooms, storage rooms
  • Telecommunication: Base stations, transmission centers, switching rooms
  • Power Systems: Distribution rooms, transformer rooms, generator rooms, UPS rooms
  • Finance: Bank vaults, archives, bill storage, trading centers
  • Medical: Operating rooms, ICUs, precision instrument rooms, pharmaceutical storage
  • Industry: Precision workshops, control rooms, instrument rooms, cable tunnels
  • Cultural Heritage: Museums, archives, libraries, relic storage
  • Commercial Buildings: Office machine rooms, elevator rooms, AC rooms, fire control rooms
pipeless gas fire suppression solution for computer room (6)

VIII. Product Advantages

8.1 Technical Advantages

  • No Piping Required: Eliminates complex piping design, installation, and maintenance, reducing engineering difficulty and cost.
  • Easy Installation: Modular design enables fast on‑site assembly without building structure damage, ideal for retrofitting.
  • Fast Response: Installed directly in the zone with no pipeline loss; discharge time ≤10s for high efficiency.
  • Precise Suppression: Total flooding or local application with uniform agent distribution.
  • High Reliability: Triple actuation (automatic / manual / mechanical) and dual detection to prevent false activation.

8.2 Economic Advantages

  • Space Saving: No dedicated cylinder room, saving valuable floor area.
  • Low Maintenance: Modular structure with minimal upkeep; no regular pipeline inspection needed.
  • Scalable: Multiple units can be interconnected for various room sizes.
  • Long Service Life: Main equipment ≥10 years; agent refillable.

8.3 Environmental Advantages

  • Clean & Non‑Residue: HFC‑227ea and IG‑541 are colorless, odorless, non‑conductive, with no post‑discharge residue.
  • Eco‑Friendly: HFC‑227ea ODP = 0; IG‑541 uses natural gases.
  • Non‑Toxic: Safe for personnel at design extinguishing concentration.

IX. Tender Control Parameters

9.1 Core Control Parameters

  • System Type: Pre‑engineered non‑piped gas fire suppression system, complying with GB 50370‑2017.
  • Agent: HFC‑227ea, purity ≥99.9%, ODP = 0, complying with GB 18614.
  • Discharge Performance: Discharge time ≤10s; concentration 8%–10% (computer room); soaking time ≥3min.
  • Working Pressure: 2.5MPa@20℃; max ≤4.2MPa@50℃.
  • Actuation: Automatic (dual detection), manual, mechanical emergency, complying with GB 25972.
  • Protected Zone: Single unit area ≤500㎡, volume ≤1600m³; interlock time difference ≤2s for multiple units.
  • Control Panel: Dual power supply, backup ≥8h, RS485/Ethernet communication.
  • Safety: Pressure feedback, gas discharge indication, emergency stop, complying with GB 16670.

9.2 Quality Control Parameters

  • Certification: National fire product testing and 3C certification.
  • Material: Cylinder: high‑quality alloy steel, thickness ≥6mm, pressure resistance ≥6.3MPa.
  • Sealing: Cylinder valve leakage rate ≤0.5%/year.
  • Weather Resistance: -20℃–55℃, IP54.
  • Service Life: Main equipment ≥10 years; agent validity ≥5 years.

X. Customized Solutions

10.1 Small Computer Room (≤200m³)

  • Configuration: 1×KT‑GQQ70/2.5 cabinet unit; 1×KT‑FAC2000 panel; 2 smoke + 2 heat detectors; manual start, emergency stop, gas indicator, alarm, interlock module.
  • Design: Unit placed in corner, ≥0.15m above floor; nozzles distributed evenly; ventilation closed 30s before discharge; fire resistance of doors/walls ≥0.5h, ceiling ≥0.25h.

10.2 Medium Computer Room (200–500m³)

  • Configuration: 2×KT‑GQQ90/2.5 cabinet units (interlocked); 1×KT‑FAC2000 panel; 4 smoke + 4 heat detectors; dual start/stop buttons, indicators, alarms; interlock for ventilation, power, dampers.
  • Design: Symmetrical placement, spacing ≤10m; discharge time difference ≤2s; pressure relief device installed; connected to fire control center for remote monitoring.

10.3 Cabinet-Level Local Protection

  • Configuration: 1×KT‑GQX40/2.5 hanging unit per cabinet; 1×KT‑FAC1000 mini panel; 1 smoke + 1 heat detector per cabinet; centralized start/stop; gas indicator above each cabinet.
  • Design: Unit hung ≥0.5m above cabinet; nozzles pointing downward; interlocked with cabinet power; fault monitoring enabled.

10.4 Retrofit Project Solution

  • Configuration: KT‑GQQ cabinet units without structure modification; wireless detectors for easy installation; modular interlock modules compatible with existing systems; custom cabinet color.
  • Design: Units placed in idle corners; detectors mounted on existing ceiling/wall; compatible with original fire alarm system; short construction period without room shutdown.

XI. Application Cases

Case 1: Guangzhou Data Center Computer Room

  • 300㎡, 900m³; server cluster, storage, network equipment; 24h unmanned operation.
  • Solution: 2×KT‑GQQ90/2.5 interlocked units; KT‑FAC2000 with Ethernet; 4 smoke + 4 heat detectors; interlocked ventilation, UPS, fire dampers.
  • Result: 3‑day installation; non‑piped design preserves layout; response ≤5s; integrated with monitoring system for remote control.

Case 2: Shenzhen Telecommunication Base Station

  • 50㎡, 150m³; communication and power equipment; outdoor harsh environment, limited space.
  • Solution: 1×KT‑GQQ40/2.5 cabinet unit; KT‑FAC1000 panel; 2 smoke + 2 heat detectors; full set of alarms and buttons.
  • Result: Compact size fits narrow space; wide temperature range -20℃–55℃; IP54 dust‑ and moisture‑proof; stable operation.

Case 3: Shanghai Financial Institution Archive

  • 100㎡, 300m³; paper and electronic archives, servers; occupied, high environmental requirement.
  • Solution: 1×KT‑GQQ70/2.5 cabinet unit; KT‑FAC2000 with RS485; 2 smoke + 2 heat detectors; interlocked ventilation and lighting.
  • Result: Clean, residue‑free agent; extinguishment ≤8s; integrated with security system; simple routine maintenance.

XII. SEO Keywords & Tags

Core Search Keywords

Non-piped gas fire suppression system, KITOZER pre-engineered fire suppression, computer room gas fire solution, HFC-227ea fire system, cabinet gas extinguishing unit, hanging gas extinguishing unit, data center fire protection, computer room fire retrofit

SEO Optimization Keywords

KITOZER non-piped gas fire suppression for computer rooms, pre-engineered HFC-227ea system, cabinet type fire extinguishing unit parameters, data center gas fire design, non-piped fire suppression tender parameters

Tags

#NonPipedFireSuppression #ComputerRoomFire #HFC227ea #KITOZER #DataCenterSafety #PreEngineeredSystem #CabinetFireUnit #HangingFireUnit #GasFireTechnology

Shopping Cart