KITOZER Fire Alarm Control & Sensor Solution for Data Centers & Computer Rooms

I. System Overview

The KITOZER Fire Alarm Control & Sensor System is an automatic fire detection and linkage control system purpose-built for mission-critical facilities including data centers, server rooms, and network equipment rooms. As the nerve center and sensory network of computer room fire safety, it performs fire signal acquisition, analysis, alarm, and interlock control to enable ultra-early fire detection, precise localization, and rapid response, delivering all-round, multi-layered protection for equipment and data security.

Compliant with national standards including GB 50116 Code for Design of Automatic Fire Alarm Systems and GB 50174-2017 Code for Data Centers, the system integrates advanced intelligent sensing, network communication, and automatic control technologies. It features high sensitivity, low false-alarm rate, strong anti-interference capability, and fast response, adapting to harsh computer room environments such as high temperature, high humidity, strong electromagnetic interference, and dense equipment layout. It effectively resolves pain points of conventional systems including high false alarms, delayed response, and poor interlock coordination.

The system supports a multi-stage pre-alarm mechanism (Pre-alarm → Alert → Fire Alarm → Interlock Action) and seamlessly integrates with gas fire suppression, HVAC, access control, and UPS systems. It issues timely alerts at the incipient fire stage and activates corresponding fire-fighting facilities to minimize fire losses and ensure uninterrupted operation of equipment and data.

computer room fire alarm control and sensors (1)

II. System Composition

The system comprises five core layers: Sensing Layer, Control Layer, Network Layer, Interlock Layer, and Application Layer, forming a complete fire alarm and linkage control architecture.

  • Sensing Layer: Aspirating smoke detectors (ASD), point-type photoelectric smoke detectors, point-type heat detectors, linear heat detectors, flame detectors, manual call points, hydrant buttons, gas extinguishing control units, fire equipment power monitoring sensors, fire door monitoring modules. Functions: fire signal acquisition, environmental parameter monitoring, manual alarm triggering, equipment status supervision.
  • Control Layer: Addressable fire alarm control panels (FACP), zone fire alarm panels, fire linkage control units, fire control room graphic display terminals. Functions: signal processing, alarm control, interlock logic execution, status indication, operation control.
  • Network Layer: Dedicated fire network switches, fiber transceivers, communication modules (RS485, CAN, Ethernet), wireless transmission modules. Functions: data transmission, device interconnection, remote communication, system expansion.
  • Interlock Layer: Gas fire suppression units, smoke exhaust fans, pressurized air supply fans, fire dampers, smoke exhaust valves, fire elevator control modules, access control modules, UPS control modules, HVAC control modules. Functions: execute control commands to activate suppression, shut down HVAC, cut power, start ventilation, etc.
  • Application Layer: Fire safety management software, mobile APP, remote monitoring platform. Functions: system administration, data logging, report generation, remote supervision, fault diagnosis, maintenance management.

III. System Classification

1. Zone Fire Alarm System

  • Application: Small computer rooms, standalone server cabinets, edge computing nodes requiring basic alarm only.
  • Core Components: Zone fire alarm panel, point-type smoke/heat detectors, manual call points, audible-visual alarms.
  • Features: Simple structure, low cost, easy installation & maintenance; alarm-only, no interlock control.
  • Cases: Small enterprise rooms, remote office closets, data collection stations.

2. Centralized Fire Alarm System

  • Application: Medium computer rooms, data center modules, enterprise-grade rooms requiring alarm + basic interlock.
  • Core Components: Addressable centralized FACP, multi-type detectors, manual call points, hydrant buttons, linkage control unit, graphic display terminal, gas extinguishing controller, fire door monitoring system, fire equipment power monitoring system.
  • Features: Full alarm + interlock control; manages gas suppression, smoke extraction, fire doors; supports multi-zone supervision.
  • Cases: Enterprise data centers, financial institution rooms, research computing centers.

3. Control Center Fire Alarm System

  • Application: Large data centers, room clusters, hyperscale cloud computing hubs requiring centralized management and multi-level interlock.
  • Core Components: Control center FACP, multiple centralized systems, graphic display terminal, fire linkage control center, remote monitoring platform, emergency public address, fire telephone system.
  • Features: Multi-zone coordinated control, powerful interlock logic, remote centralized management; meets complex large-scale room requirements.
  • Cases: Internet data centers (IDC), large cloud hubs, financial data centers, government data centers.
computer room fire alarm control and sensors (2)

IV. System Configuration List (KITOZER Brand)

  • Fire Alarm Control Panel (Addressable): KT-FP2000
  • Fire Control Room Graphic Display Terminal: KT-GD5000
  • Aspirating Smoke Detector (ASD): KT-ASD100
  • Point-Type Photoelectric Smoke Detector: KT-JTY-GD-KT100
  • Point-Type Heat Detector (A2R): KT-JTW-ZD-KT200
  • Linear Heat Fire Detector: KT-JTW-LCD-KT300
  • Flame Detector: KT-JTG-ZM-KT400
  • Manual Call Point: KT-J-SAP-KT500
  • Fire Hydrant Button: KT-J-XAP-KT600
  • Gas Extinguishing Control Unit: KT-QM-KT700
  • Fire Equipment Power Monitoring Sensor: KT-PM-KT800
  • Fire Door Monitoring Module: KT-FM-KT900
  • Audible-Visual Alarm: KT-SG-KT1000
  • Dedicated Fire Network Switch: KT-SW-KT2000
  • Communication Module (RS485 to Ethernet): KT-CM-KT3000
  • Backup Power Supply (UPS): KT-UPS-KT4000

V. System Schematic Diagram

plaintext

┌─────────────────────────────────────────────────────────────┐
│                    Fire Control Room                        │
│  ┌─────────────┐  ┌─────────────┐  ┌─────────────┐         │
│  │ FACP        │  │ Graphic     │  │ Linkage     │         │
│  │ (KT-FP2000) │──│ Display     │──│ Control Unit│         │
│  └──────┬──────┘  └─────────────┘  └──────┬──────┘         │
│         │                                 │                │
└─────────┼─────────────────────────────────┼────────────────┘
          │                                 │
┌─────────┼─────────────────────────────────┼────────────────┐
│  ┌──────▼──────┐  ┌─────────────┐  ┌──────▼──────┐         │
│  │ Sensing     │  │ Manual Call │  │ Gas         │         │
│  │ Detectors   │  │ Points      │  │ Controller  │         │
│  └──────┬──────┘  └─────────────┘  └──────┬──────┘         │
│         │                                 │                │
└─────────┼─────────────────────────────────┼────────────────┘
          │                                 │
┌─────────┼─────────────────────────────────┼────────────────┐
│  ┌──────▼──────┐  ┌─────────────┐  ┌──────▼──────┐         │
│  │ Interlock   │  │ Power       │  │ Fire Door   │         │
│  │ Equipment   │  │ Monitor     │  │ Modules     │         │
│  └─────────────┘  └─────────────┘  └─────────────┘         │
│                                                              │
│                       Computer Room Area                     │
└─────────────────────────────────────────────────────────────┘
computer room fire alarm control and sensors (3)

VI. Technical Specifications

1. Fire Alarm Control Panel (KT-FP2000, Addressable)

  • Power: AC 220V (±15%), 50Hz; DC 24V (backup)
  • Loops: 8 alarm loops (256 addressable points/loop, max 2048); 8 interlock loops (128 modules/loop, max 1024)
  • Display: 10.1-inch color touchscreen, 1280×800, Chinese UI
  • Response Time: ≤10s (fire alarm); ≤100s (fault)
  • Memory: 10,000 fire logs, 10,000 fault logs, 10,000 operation logs
  • Interfaces: RS485, CAN, Ethernet (RJ45), USB, HDMI
  • Ambient: 0℃~40℃, ≤95%RH (non-condensing)
  • Backup Battery: ≥180 minutes operation
  • Ingress Protection: IP30

2. Aspirating Smoke Detector (KT-ASD100)

  • Principle: Laser scattering, ultra-early smoke detection
  • Sensitivity: 0.005%~20% obs/m, multi-level adjustable
  • Sampling Tube: Max 100m, up to 4 tubes
  • Sampling Ports: Max 32
  • Alarm Levels: Pre-alarm, Alert, Fire1, Fire2
  • Response Time: ≤3s (Fire); ≤10s (Pre-alarm)
  • Communication: RS485, Modbus
  • Power: DC 24V (18V~30V)
  • Ambient: -10℃~55℃, ≤95%RH (non-condensing)
  • IP Rating: IP54 (main unit), IP65 (sampling tube)

3. Linear Heat Fire Detector (KT-JTW-LCD-KT300)

  • Principle: Digital cable-type heat sensing, distributed temperature monitoring
  • Temperature Range: -40℃~+120℃
  • Alarm Temperature: 85℃ (customizable)
  • Response Time: ≤30s (sudden rise); ≤60s (gradual rise)
  • Max Length: 1000m/loop
  • Communication: RS485, Modbus
  • Power: DC 24V (18V~30V)
  • Ambient: -40℃~+70℃, ≤95%RH (non-condensing)
  • IP Rating: IP67 (cable), IP30 (controller)
computer room fire alarm control and sensors (4)

VII. Application Scope

  • Data Centers: IDC, cloud computing hubs, financial/government/enterprise data centers
  • Server Rooms: Enterprise server rooms, network rooms, storage rooms, edge nodes
  • Telecommunication Rooms: Operator rooms, base stations, core network rooms
  • Power Rooms: Substation control rooms, distribution rooms, UPS rooms, battery rooms
  • Industrial Rooms: Automation control rooms, PLC/DCS rooms, smart manufacturing data centers
  • Medical/Financial/Research Rooms: Hospital IT centers, bank data rooms, supercomputing labs

VIII. Product Advantages

  1. Ultra-Early Detection & Precise Alarm: ASD detects smoke at 0.005% obs/m, hours earlier than conventional detectors; 4-level alarm + adaptive algorithm reduce false alarms to ≤0.1%/year.
  2. Full-Coverage, Zero-Blind-Spot Monitoring: Multi-detector combination (ASD + point-type + linear + flame); cabinet-level linear heat detection for hotspot monitoring; power & fire door status supervision.
  3. Intelligent Interlock & Rapid Response: Programmable complex interlock logic; seamless integration with suppression, HVAC, access, UPS; remote control via network & mobile APP.
  4. High Reliability & Stable Operation: Industrial-grade components for harsh environments; redundant power & dual-link communication; full fault self-diagnosis.
  5. Easy Installation & Low Maintenance: Modular design, auto-addressing, plug-and-play; remote diagnosis, configuration & upgrade; intuitive graphical UI.
computer room fire alarm control and sensors (5)

IX. Tender Control Parameters

Fire Alarm Control Panel (Addressable)

  • Complies with GB 4717-2005, GB 16806-2006
  • ≥8 alarm loops (≥256 points/loop); ≥8 interlock loops (≥128 points/loop)
  • ≥10-inch color touchscreen, ≥1280×800 resolution
  • ≥10,000 fire/fault/operation logs
  • Fire response ≤10s; fault response ≤100s
  • Dual power supply, backup ≥180 minutes; IP≥30
  • KITOZER brand with original authorization & service commitment

Aspirating Smoke Detector

  • Complies with GB 15631-2008
  • Laser scattering, ultra-early detection
  • Sensitivity 0.005%~20% obs/m; ≥4 alarm levels
  • Max sampling tube ≥100m, ≥4 tubes, ≥32 ports
  • Fire response ≤3s; Pre-alarm ≤10s
  • RS485 Modbus; IP54(main)/IP65(tube)
  • KITOZER brand with original authorization & service commitment

Linear Heat Fire Detector

  • Complies with GB 16280-2014
  • Digital cable-type, distributed temperature monitoring
  • -40℃~+120℃; alarm 85℃ (customizable)
  • Response ≤30s/60s; max length ≥1000m/loop
  • RS485 Modbus; IP67(cable)/IP30(controller)
  • KITOZER brand with original authorization & service commitment

X. Solution Design

Design Concept

Ultra-early Detection + Precise Alarm + Intelligent Interlock + Comprehensive Supervision

Full compliance with national standards; integration of cutting-edge fire and IoT technologies to minimize losses and ensure safe operation.

Design Principles

Safety, Reliability, Advanced Technology, Cost-Effectiveness, Scalability, Ease of Maintenance

Key Design Points

  • Main Computer Rooms: KT-ASD100 ASD for ultra-early smoke detection.
  • Server Cabinets: KT-JTW-LCD-KT300 linear heat detectors for internal temperature monitoring.
  • Auxiliary Areas: Point-type smoke/heat detectors for full coverage.
  • Flammable Storage/Entrances: Flame detectors for rapid flame detection.
  • Manual Alarm: Call points at corridors, stairwells, room entrances.
  • Control & Interlock: KT-FP2000 FACP + KT-GD5000 graphic terminal; automatic activation of suppression, power cutoff, HVAC shutdown, access control.
  • Monitoring: Power monitoring sensors, fire door modules, gas extinguishing controllers.
  • Communication: Wired dedicated network + wireless for hard-to-wire areas; remote access via Ethernet/4G/5G.

Implementation Steps

Requirement Analysis → Scheme Design → Equipment Selection → Construction & Installation → System Commissioning → Personnel Training → Acceptance → Operation & Maintenance

XI. Application Cases

Case 1: Large Internet Data Center

  • 5,000㎡, 10 main halls, 2 distribution rooms, 1 UPS room, 1 battery room.
  • Solution: KT-FP2000 FACP + KT-GD5000 display; ASD per hall; linear heat in every cabinet; point-type detectors in support areas; full interlock with suppression, HVAC, access, UPS.
  • Outcome: Detected 2 incipient events (cabinet overheating smoke, AC dust); issued early warnings; avoided fires; highly praised by customer.

Case 2: Financial Data Center Retrofit

  • 2,000㎡, 3 main halls, 1 distribution room, 1 UPS room; old system high false alarms.
  • Solution: Upgrade to KT-FP2000 + KT-GD5000; replace with ASD; add linear heat in cabinets; dual detection in power rooms; optimized interlock logic.
  • Outcome: False alarms ≤0.1%/year; ultra-early detection; intelligent interlock; passed fire department acceptance.

XII. SEO Keywords & Tags

Core Search Keywords

Computer Room Fire Alarm System, Fire Sensors for Data Centers, KITOZER Fire Alarm Control Panel, Aspirating Smoke Detector, Linear Heat Detector, Data Center Fire Solution, Automatic Fire Alarm System, Intelligent Fire Linkage Control, Ultra-Early Fire Detection