I. System Introduction
1.1 Core Definition
The KITOZER computer room lighting distribution cabinet (distribution box) is a professional lighting power distribution system specially designed for precision electronic equipment environments such as data centers, computer rooms and server rooms. As an essential part of the computer room power supply and distribution system, it undertakes centralized control, protection and management of the computer room lighting system, ensuring the reliability, safety, stability and intelligent control of lighting power supply.
1.2 Design Standards
The system strictly complies with the following national standards and specifications:
- GB 50174-2017 Code for Design of Data Centers
- GB 50034-2013 Standard for Lighting Design of Buildings
- GB 7251.1-2013 Low-voltage Switchgear and Controlgear Assemblies – Part 1: General Rules
- GB 51348-2019 Standard for Electrical Design of Civil Buildings
- Data center illumination standards: Main computer room: 300lx~500lx; Auxiliary area: ≥300lx; Standby lighting: ≥10% of general lighting illuminance
1.3 Core Values
- Power Supply Reliability: Dual-circuit power supply design ensures continuous and stable computer room lighting, enabling seamless switching between auxiliary area and main computer room standby lighting.
- Safety Protection: Multiple electrical protection mechanisms prevent electrical faults such as short circuit, overload and electric leakage to protect personnel and equipment safety.
- Intelligent Management: Supports remote monitoring, timing control and scene control to improve operation and maintenance efficiency and reduce energy consumption.
- Precise Power Distribution: Modular design adapts to lighting demands of computer rooms of different scales, facilitating expansion and maintenance.

II. System Composition
The KITOZER computer room lighting distribution cabinet system consists of the following core components to form a complete lighting power distribution solution:
| Module | Core Components | Function Description |
| Cabinet Structure | Cold-rolled steel enclosure, protective panel, mounting bracket | Provides mechanical protection and installation foundation; protection grade optional from IP30 to IP54 |
| Main Power Distribution Unit | Main circuit breaker, disconnector, Automatic Transfer Switch (ATS) | Realizes main power control and automatic switching between main and standby power sources to guarantee power supply continuity |
| Branch Protection Unit | Miniature Circuit Breaker (MCB), Residual Current Circuit Breaker (RCCB/RCBO) | Provides branch overload, short circuit and leakage protection; single-circuit current ≤16A, maximum 25 lamps per circuit |
| Measurement & Monitoring Unit | Multi-functional power meter, current transformer, temperature and humidity sensor | Real-time monitoring of voltage, current, power, electric energy, temperature and other parameters |
| Intelligent Control Unit | Intelligent lighting controller, communication module, HMI | Supports remote control, timing control and scene mode switching; compatible with Modbus/DNP3 communication protocols |
| Surge Protection Unit | Surge Protective Device (SPD), lightning protection module | Protects against induced lightning and power overvoltage to safeguard lighting equipment |
| Auxiliary Components | Busbar, terminal block, identification system, ventilation and heat dissipation device | Guarantees reliable electrical connection and facilitates maintenance and management |

III. System Classification
3.1 Classification by Installation Mode
| Type | Features | Application Scenarios |
| Wall-mounted | Compact size, flexible installation, small space occupation | Lighting power distribution for small and medium-sized computer rooms and auxiliary areas; installed on walls or equipment rooms |
| Floor-standing | Large capacity, strong expandability, suitable for multi-circuit complex systems | Large-scale data centers and main computer rooms requiring centralized control of multi-region lighting |
| Recessed | Concealed installation, neat and aesthetic appearance, excellent protection performance | High-end computer rooms and highly intelligent sites with integrated decoration design |
3.2 Classification by Control Mode
| Type | Core Features | Technical Advantages |
| Conventional Type | Manual control with basic protection functions | Low cost and simple operation, applicable to small computer rooms |
| Intelligent Type | Remote monitoring + local control, supports scene modes | Reduces energy consumption by 30%–40%, improves O&M efficiency by 50%, and enables accurate fault location |
| Emergency Type | Integrated EPS emergency power supply with automatic standby lighting switching | Complies with GB 50174-2017 standby lighting requirements to meet computer room emergency lighting demands |
3.3 Classification by Capacity Scale
| Capacity Grade | Circuit Quantity | Rated Current | Application Scenarios |
| Small | 8~20 circuits | Total current ≤63A | Computer room area <100㎡, lighting power <15kW |
| Medium | 24~40 circuits | Total current ≤125A | Computer room area 100~500㎡, lighting power 15~50kW |
| Large | 45~60 circuits | Total current ≤250A | Computer room area >500㎡, multi-level lighting system, power >50kW |

IV. System Configuration List (Brand: KITOZER)
4.1 Configuration List of Small Computer Room Lighting Distribution Cabinet (8-circuit Wall-mounted)
| No. | Product Name | Model & Specification | Brand | Quantity | Remarks |
| 1 | Lighting Distribution Box Enclosure | KITOZER-KMZ-8 | KITOZER | 1 Set | Size: 400×300×150mm, cold-rolled steel plate, IP30 protection grade |
| 2 | Main Circuit Breaker | KITOZER-KMB63-3P C63 | KITOZER | 1 Pc | 3-pole, rated current 63A, C-type tripping curve |
| 3 | Branch Miniature Circuit Breaker | KITOZER-KMB16-1P+N C16 | KITOZER | 8 Pcs | 1P+N, rated current 16A, maximum 25 lamps per circuit |
| 4 | Residual Current Circuit Breaker | KITOZER-KMR-63 30mA | KITOZER | 1 Pc | General leakage protection, operating current 30mA, fast fault cutoff |
| 5 | Multi-functional Power Meter | KITOZER-KMP-2000 | KITOZER | 1 Pc | Monitors voltage, current, power and electric energy, supports RS485 communication |
| 6 | Surge Protective Device | KITOZER-KMS-20 2P 20kA | KITOZER | 1 Pc | Protects power side surge, response time ≤25ns |
| 7 | Busbar & Terminal Block | KITOZER-KMT Series | KITOZER | 1 Set | Copper busbar meeting current-carrying requirements with clear identification |
| 8 | Installation Accessories | KITOZER-KMF Series | KITOZER | 1 Set | Fixing brackets, terminal blocks, nameplates and other accessories |
4.2 Configuration List of Medium Computer Room Lighting Distribution Cabinet (24-circuit Floor-standing)
| No. | Product Name | Model & Specification | Brand | Quantity | Remarks |
| 1 | Lighting Distribution Cabinet Enclosure | KITOZER-KMZ-24 | KITOZER | 1 Set | Size: 800×600×1000mm, cold-rolled steel plate, IP40 protection grade |
| 2 | Automatic Transfer Switch (ATS) | KITOZER-KMA-125 3P | KITOZER | 1 Pc | Rated current 125A, automatic switching time ≤0.5s |
| 3 | Main Circuit Breaker | KITOZER-KMB125-3P C125 | KITOZER | 2 Pcs | 1 for main power, 1 for standby power, 3-pole, rated current 125A |
| 4 | Branch Miniature Circuit Breaker | KITOZER-KMB16-1P+N C10/C16 | KITOZER | 24 Pcs | 12×C10A (general lighting), 12×C16A (emergency lighting) |
| 5 | Intelligent Lighting Controller | KITOZER-KMC-8000 | KITOZER | 1 Pc | 8-channel control output, supports timing and scene control, Modbus protocol |
| 6 | Residual Current Circuit Breaker | KITOZER-KMR-100 3P+N 30mA | KITOZER | 2 Pcs | 1 for main circuit, 1 for standby circuit, leakage protection, operating time ≤0.1s |
| 7 | Multi-functional Power Meter | KITOZER-KMP-3000 | KITOZER | 1 Pc | Three-phase monitoring, harmonic analysis, power quality evaluation, LCD display |
| 8 | Surge Protection System | KITOZER-KMS-40 3P+N 40kA | KITOZER | 1 Set | Three-level surge protection for full-range lighting system protection |
| 9 | Temperature & Humidity Sensor | KITOZER-KMT-100 | KITOZER | 2 Pcs | Monitors internal cabinet temperature with over-temperature alarm to ensure equipment safety |
| 10 | Ventilation & Heat Dissipation Device | KITOZER-KMV-200 | KITOZER | 2 Pcs | Automatic temperature-controlled fans to maintain optimal internal cabinet temperature |
| 11 | Busbar System | KITOZER-KMB Series | KITOZER | 1 Set | Segmented busbar for easy expansion, copper material with insulation treatment |
| 12 | Installation & Identification Accessories | KITOZER-KMF Series | KITOZER | 1 Set | Complete installation accessories with clear zoning identification for easy maintenance |

V. System Schematic Diagram
Topology Diagram of KITOZER Computer Room Lighting Distribution System
Utility Power 1 ────────┐ ┌─────── Main Lighting Circuit 1 (MCB C16) ─────── General Lighting Lamps
│ │
├─ ATS Automatic Transfer Switch ────┐
│ │ ├─────── Main Lighting Circuit 2 (MCB C16) ─────── General Lighting Lamps
Utility Power 2 ────────┘ │ │
│ └─────── … (max. 24 circuits) ───────── …
│
├─ Standby Lighting Circuit (MCB C16) ─────── Standby Lighting Lamps (≥10% illuminance)
│
├─ Intelligent Control Unit ──────┐
│ │
└─ Measurement & Protection Unit ├─ Remote Monitoring System
│
└─ Scene Control Terminal
Core Control Logic Description
- Dual-power Automatic Switching: When the main power fails, the ATS automatically switches to standby power within 0.5 seconds to ensure uninterrupted lighting.
- Graded Protection Mechanism: Main circuit breaker → branch MCB → leakage protection, realizing accurate fault isolation and minimizing impact scope.
- Intelligent Control Process:
- Timing Control: Automatically turns on/off lighting according to computer room schedule and reduces illuminance during unmanned periods.
- Scene Control: Presets multiple lighting scenes including “Normal Operation”, “Inspection & Maintenance” and “Emergency Mode”.
- Linkage Control: Links with the computer room fire protection system to automatically switch to emergency lighting mode in case of fire.
- Remote Monitoring: Real-time viewing of each circuit status via the monitoring platform, supporting remote control and fault alarm.

VI. Product Technical Parameters
General Technical Parameters of KITOZER Computer Room Lighting Distribution Cabinet
| Parameter Category | Technical Index | Description |
| Basic Parameters | Rated Voltage | AC 380V/220V, 50Hz, three-phase four-wire system |
| Rated Current | 8-circuit: 63A; 24-circuit: 125A; 48-circuit: 250A | |
| Protection Grade | Optional: IP30 (basic), IP40 (enhanced), IP54 (outdoor) | |
| Cabinet Material | High-quality cold-rolled steel plate, 1.5~2.0mm thickness, electrostatic spray surface treatment | |
| Protection Performance | Short-circuit Breaking Capacity | ≥15kA, meeting computer room power distribution safety requirements |
| Overload Protection | Compliant with IEC 60898 standard, C-type curve (5In~10In) | |
| Leakage Protection | Operating current 30mA, operating time ≤0.1s, ensuring personal safety | |
| Surge Protection | Class II protection grade, maximum discharge current 20~40kA | |
| Intelligent Functions | Communication Interface | RS485, supports Modbus-RTU protocol, expandable Ethernet interface |
| Control Mode | Local manual + remote automatic, supports timing, scene and linkage control | |
| Monitoring Accuracy | Voltage: ±0.5%, Current: ±0.5%, Power: ±1.0% | |
| Environmental Adaptability | Operating Temperature | -10℃~+40℃, adaptable to computer room environment |
| Relative Humidity | ≤90% (+20℃), non-condensing | |
| Altitude | ≤2000m, derating required for higher altitude | |
| Pollution Degree | Grade 3, adaptable to computer room industrial environment | |
| Certification & Qualification | Product Certification | CCC compulsory certification, compliant with GB 7251.1-2013 standard |
| Environmental Certification | RoHS compliant, meeting EU environmental requirements | |
| Quality Standard | ISO 9001 quality management system certification with strict quality control |
Special Technical Parameters of KITOZER Branch Protection Switch
| Model | Pole Number | Rated Current | Tripping Curve | Leakage Protection | Application Scenarios |
| KMB16-1P+N | 1P+N | 6A/10A/16A | C-type | Optional | General lighting circuits, ≤25 lamps per circuit |
| KMB32-2P | 2P | 20A/25A/32A | C-type | Optional | Large combined lighting circuits, ≤60 lamps per circuit |
| KMR-63 | 3P+N | 32A/40A/63A | C-type | 30mA | General leakage protection for overall system safety |
VII. Product Application Scope
KITOZER computer room lighting distribution cabinets are applicable to the following scenarios, meeting lighting power distribution demands of computer rooms of different scales and types:
7.1 Data Center Scenarios
- Large Cloud Data Centers: Multi-area hierarchical lighting control, automatic main/standby power switching, supporting remote monitoring and energy consumption management
- Enterprise-level Data Centers: Modular design adapting to phased computer room construction for easy expansion and maintenance
- Edge Computing Data Centers: Compact design adapting to space constraints of small computer rooms and ensuring lighting reliability
7.2 Computer Room Type Adaptation
| Computer Room Type | Recommended Configuration | Core Requirements |
| Main Computer Room | 24-circuit floor-standing intelligent type | High reliability, standby lighting ≥10% of general lighting, intelligent control |
| Auxiliary Area | 8-circuit wall-mounted conventional type | Basic lighting, meeting 300lx illuminance with cost optimization |
| Monitoring Center | 16-circuit recessed intelligent type | High color rendering index (≥80), glare-free, scene-based control |
| Battery Room / Distribution Room | 12-circuit protected type | Explosion-proof lighting, IP54 protection, linkage with fire protection system |
7.3 Special Application Scenarios
- Medical Computer Rooms: Isolated from medical equipment power supply system with low electromagnetic interference to ensure normal operation of medical devices
- Financial Computer Rooms: Compliant with financial industry specifications, dual-circuit + emergency power supply to guarantee business continuity
- Military Computer Rooms: Electromagnetic shielding design with strong anti-interference capability to meet military-grade safety requirements
- Rail Transit Computer Rooms: Vibration-resistant design, IP40+ protection grade, supporting remote centralized management
VIII. Product Advantages
Compared with traditional lighting distribution boxes, KITOZER computer room lighting distribution cabinets have the following core advantages:
8.1 Safety & Reliability Advantages
- Multiple Electrical Protection: Full-range protection against short circuit, overload, electric leakage and surge with fault response time ≤0.1s to protect personnel and equipment safety.
- Dual-power Redundant Design: ATS automatic switching enables seamless connection between main and standby power to avoid lighting interruption affecting computer room O&M.
- Fire & Flame Retardant: Cabinet material reaches V0 flame retardant grade, and all internal components pass fire protection certification to reduce fire risks.
- Reliable Grounding: Dedicated grounding bar design with grounding resistance ≤4Ω to effectively prevent electric shock accidents.
8.2 Intelligent Management Advantages
- Remote Monitoring Capability: Real-time monitoring of each circuit status and energy consumption data, supporting remote control and fault alarm to improve O&M efficiency by over 50%.
- Scene-based Control: Presets multiple lighting modes adapting to different working scenarios, reducing energy consumption by 30%–40%.
- Data Visualization: Intuitively displays operational data of each circuit via the monitoring platform, supporting energy consumption analysis and optimization suggestions.
- System Linkage: Links with computer room Environmental Monitoring System (EMS) and fire protection system to realize intelligent management.
8.3 Structural Design Advantages
- Modular Design: Standard module combination facilitates expansion and maintenance, shortening computer room construction cycle.
- User-friendly Operation: Transparent protective door, convenient operation and clear identification reduce misoperation risks.
- Optimized Heat Dissipation: Reasonable air duct design ensures high heat dissipation efficiency and long-term stable operation of components.
- Space Adaptability: Multiple installation methods including wall-mounted, floor-standing and recessed adapt to various computer room spatial layouts.
8.4 Full Lifecycle Advantages
- High-quality Components: Core components service life ≥10 years, Mean Time Between Failures (MTBF) ≥50,000 hours.
- Maintenance-free Design: Reduces maintenance workload and O&M costs, lowering full lifecycle cost by 22%–28%.
- Upgradability: Reserved expansion interfaces support subsequent intelligent upgrading and protect upfront investment.
- Energy-saving & Eco-friendly: Compliant with RoHS standards, reduces energy consumption and supports green data center construction.
IX. Bid Control Parameters
The following core bid control parameters of KITOZER computer room lighting distribution cabinets are formulated for project bidding and technical specification compilation:
9.1 Basic Parameter Requirements
- Rated voltage: AC 380V/220V, three-phase four-wire system, 50Hz, voltage fluctuation range ±10%.
- Rated current: Total current ≥125A (medium type), branch current ≤16A, compliant with GB 51348-2019 standard.
- Protection grade: ≥IP30, floor-standing type ≥IP40, special area type ≥IP54.
- Cabinet material: Cold-rolled steel plate thickness ≥1.5mm, electrostatic spray surface, color RAL7035 (industrial gray).
9.2 Core Function Requirements
- Dual-power Switching: Equipped with ATS automatic transfer switch, switching time ≤0.5s, compliant with GB/T 14048.11 standard.
- Protection Functions:
- Short-circuit protection: Breaking capacity ≥15kA, compliant with IEC 60947-2 standard
- Leakage protection: Operating current ≤30mA, operating time ≤0.1s, compliant with GB 16917 standard
- Surge protection: Class II grade, maximum discharge current ≥20kA, response time ≤25ns
- Intelligent Control:
- Supports remote monitoring, RS485 communication interface, Modbus-RTU protocol
- Equipped with timing and scene control functions, compatible with third-party system linkage
- Monitoring accuracy: Voltage ±0.5%, Current ±0.5%, Power ±1.0%
9.3 Certification & Quality Requirements
- Product Certification: Must possess valid CCC compulsory certification certificate, compliant with GB 7251.1-2013 standard.
- Environmental Requirements: Compliant with RoHS directive with environmental test report provided.
- Quality System: Manufacturer holds ISO 9001 quality management system certification with certificate provided.
- Warranty Period: Overall warranty ≥2 years, core components (circuit breaker, controller) warranty ≥5 years.
9.4 Special Technical Requirements
- Standby Lighting: Independent standby lighting circuits with illuminance ≥10% of general lighting, compliant with GB 50174-2017 standard.
- Emergency Switching: Links with fire protection system to automatically switch to emergency lighting mode within 0.3s during fire incidents.
- Electromagnetic Compatibility: Compliant with GB/T 18802.1 standard, electromagnetic interference ≤40dBμV, anti-interference capability ≥10V/m.
- Identification System: Equipped with clear circuit identification, operation instructions and warning marks, compliant with GB 7251.1 standard.
X. System Solutions
10.1 Lighting Power Distribution Solution for Large-scale Data Center
Project Requirements
- Computer room area: 800㎡, divided into main computer room, auxiliary area and monitoring center
- Illuminance requirements: Main computer room 500lx, auxiliary area 300lx, monitoring center 400lx, standby lighting ≥10% of general lighting
- Power supply requirements: Dual-circuit power supply with automatic standby power switching to ensure 7×24-hour lighting continuity
- Management requirements: Remote monitoring, energy consumption statistics and scene control to reduce O&M costs
Solution Design
- System Architecture: Adopts 3 sets of KITOZER-KMZ-24 floor-standing intelligent lighting distribution cabinets for zonal control.
- Power Supply Scheme:
- Main power: 380V three-phase four-wire utility power
- Standby power: UPS power supply for standby and key area lighting
- ATS automatic transfer switch with switching time ≤0.5s
- Circuit Configuration:
- Main computer room: 16 circuits with C16A MCB, maximum 25 LED lamps per circuit
- Auxiliary area: 8 circuits with C10A MCB to meet basic lighting demands
- Monitoring center: 6 circuits with C16A MCB, equipped with high color rendering index (≥85) lamps
- Standby lighting: 4 independent circuits physically isolated from main lighting circuits for high reliability
- Intelligent Control:
- Equipped with KITOZER-KMC-8000 intelligent lighting controller supporting Modbus protocol
- Presets three scene modes: Normal Operation, Night Inspection and Emergency Mode
- Connects with computer room EMS to realize data sharing and linkage control
- Protection Mechanism:
- Dual protection of general and branch leakage protection with 30mA operating current
- Three-level Class II surge protection with maximum discharge current 40kA
- Temperature and humidity monitoring with over-temperature alarm to ensure equipment safety
Implementation Effects
- Power Supply Reliability: Achieves 99.999% reliability with zero lighting interruption incidents, guaranteeing 7×24-hour computer room operation
- Energy Saving: Intelligent control reduces lighting energy consumption by 35%, saving approximately RMB 80,000 in electricity costs annually
- O&M Efficiency: Remote monitoring reduces manual inspection workload by 60% and shortens fault location time by 80%
- Safety Guarantee: Multiple protection mechanisms eliminate electrical safety hazards and protect personnel and equipment safety
10.2 Lighting Power Distribution Solution for Small & Medium-sized Enterprise Computer Rooms
Project Requirements
- Computer room area: 150㎡, single-area design
- Illuminance requirements: 300lx, standby lighting ≥10% of general lighting
- Limited budget requiring high cost performance and simple maintenance
- Basic remote monitoring capability required
Solution Design
- System Architecture: Adopts 1 set of KITOZER-KMZ-16 wall-mounted intelligent lighting distribution cabinet.
- Power Supply Scheme:
- Main power: 220V single-phase three-wire utility power
- Standby power: EPS emergency power supply for standby lighting
- Manual/automatic transfer switch balances cost and reliability
- Circuit Configuration:
- Main lighting: 12 circuits with C16A MCB, maximum 25 LED lamps per circuit
- Standby lighting: 4 independent control circuits with illuminance ≥30lx
- Intelligent Control:
- Simplified intelligent controller supports timing control and remote status monitoring
- Mobile APP remote viewing with basic fault alarm function
- Protection Mechanism:
- General leakage protection + branch overload protection to meet basic safety requirements
- Two-level Class II surge protection with maximum discharge current 20kA
Implementation Effects
- Cost Optimization: Reduces cost by 20% compared with traditional solutions while improving reliability
- Easy Maintenance: Modular design shortens fault troubleshooting time by 50%
- Enhanced Safety: Leakage and surge protection eliminate common electrical safety hazards
- Upgraded Management: Remote monitoring reduces manual inspection frequency and improves management efficiency
XI. Product Application Cases
Case 1: Cloud Computing Data Center Project
Project Overview
- Project Scale: Total construction area 20,000㎡, 10 independent computer room modules
- Implementation Time: March 2025
- Solution: 20 sets of KITOZER-KMZ-24 floor-standing intelligent lighting distribution cabinets for zonal control
- Core Requirements: High reliability, intelligent management, energy consumption optimization
Implementation Highlights
- Dual-bus Power Supply: Fully isolated main and standby power with ATS automatic switching ensures zero lighting interruption.
- Intelligent Linkage: Deeply integrated with Data Center Infrastructure Management (DCIM) platform to realize linkage of lighting, air conditioning and security systems.
- Energy Consumption Management: Intelligent control reduces lighting energy consumption by 38%, saving approximately RMB 500,000 in annual electricity costs.
- Fault Early Warning: Real-time current and temperature monitoring predicts potential faults in advance, cutting maintenance costs by 60%.
Customer Evaluation
“The KITOZER computer room lighting distribution system features high stability and powerful intelligent management functions. It not only meets our data center lighting demands, but also realizes energy consumption optimization and management upgrading, making it the preferred product for data center construction.” — O&M Director of Cloud Computing Company Data Center
Case 2: Financial Institution Disaster Recovery Center Project
Project Overview
- Project Scale: 500㎡ computer room constructed per Class A computer room standards
- Implementation Time: August 2025
- Solution: 8 sets of KITOZER-KMZ-16 recessed intelligent lighting distribution cabinets
- Core Requirements: High safety, emergency guarantee, electromagnetic compatibility
Implementation Highlights
- Electromagnetic Shielding Design: The cabinet adopts electromagnetic shielding materials to reduce interference of the lighting system on financial equipment.
- Emergency Lighting: Standby lighting is completely independent of main lighting with illuminance ≥50%, meeting financial industry specifications.
- Fire Protection Linkage: Links with fire alarm system to automatically switch to emergency lighting mode during fires to ensure personnel evacuation.
- Remote Management: Supports 7×24-hour remote monitoring and real-time fault alarm push to guarantee safe operation of the disaster recovery center.
Customer Evaluation
“The KITOZER lighting distribution system fully meets the high safety requirements of our disaster recovery center. Especially the emergency lighting and fire linkage functions provide strong support for our business continuity.” — Person-in-charge of Bank Disaster Recovery Center
Case 3: University Data Center Computer Room Renovation Project
Project Overview
- Project Scale: 200㎡ existing computer room renovation
- Implementation Time: January 2026
- Solution: 4 sets of KITOZER-KMZ-8 wall-mounted conventional lighting distribution cabinets
- Core Requirements: Cost control, rapid deployment, reliability improvement
Implementation Highlights
- Rapid Installation: Wall-mounted design requires no computer room renovation, cutting installation time by 70%.
- Cost Optimization: Renovation cost reduced by 40% compared with new construction while improving lighting quality.
- Illuminance Upgrade: Post-renovation illuminance increased from 200lx to 400lx, complying with GB 50174-2017 standards.
- Protection Upgrade: Added leakage and surge protection to improve computer room power utilization safety.
Customer Evaluation
“The KITOZER lighting distribution system provides a cost-effective solution for our old computer room renovation. It not only improves lighting quality and safety, but also helps control the renovation budget. We are highly satisfied.” — Director of University Information Center
XII. Search Keywords, SEO & Tags
Core Search Keywords
Computer room lighting distribution cabinet, computer room lighting distribution box, KITOZER lighting distribution cabinet, data center lighting power distribution, computer room emergency lighting system, intelligent lighting distribution box, computer room lighting solution, computer room lighting bid parameters, GB50174 computer room lighting standard, dual-power lighting distribution box
SEO Optimization Keywords
Primary Keywords
Computer room lighting distribution cabinet, data center lighting distribution box
Long-tail Keywords
- KITOZER intelligent lighting distribution cabinet solution
- Computer room dual-power lighting distribution box system design
- Data center standby lighting power distribution standard
- Computer room lighting distribution cabinet bid parameter requirements
- Application of intelligent lighting distribution box in computer rooms
Product Tags
#ComputerRoomLightingDistributionCabinet #DataCenterLighting #KITOZER #IntelligentLighting #DualPowerSwitching #EmergencyLighting #ComputerRoomDistributionSystem #LightingBidParameters #GB50174 #EnergySavingLighting