KITOZER
KITOZER

KITOZER Computer Room Air Conditioner Condensate Drainage System Solution

1. System Introduction

1.1 System Definition

The computer room air conditioner condensate drainage system is a dedicated system for collecting, conveying, draining and treating condensate generated during the operation of precision air conditioners. It serves as a core component of infrastructure for precision environments such as data centers and communication computer rooms. With scientifically designed pipelines, pumps, valves and control components, the system ensures safe, efficient and leakage-free condensate drainage, preventing equipment damage, short circuits and environmental deterioration caused by condensate overflow.

1.2 Working Principle

Condensate forms on the surface of the air conditioner evaporator and converges in the water tray. It is delivered to the main drainage pipeline via gravity or mechanical lifting, then goes through water seal deodorization and filtration purification before finally discharging into the building drainage system or being recycled. Equipped with intelligent monitoring and alarm devices, the system real-timely monitors water level, flow rate and leakage conditions to ensure 24/7 uninterrupted safe operation.

1.3 System Importance

Computer rooms require extremely high precision in temperature and humidity control (typically temperature ±1℃, humidity ±5%RH). The reliability of the condensate drainage system is directly related to the following key indicators:

  • Prevent damage to core IT assets such as servers and network equipment caused by condensate leakage
  • Eliminate safety hazards arising from slippery ground
  • Inhibit microbial growth and odor diffusion to guarantee indoor air quality of computer rooms
  • Comply with environmental protection and energy-saving requirements and support condensate recycling and reuse
  • Ensure continuous and stable operation of precision air conditioners and extend equipment service life
computer room air conditioning condensate drainage system solution (7)

2. System Composition

The KITOZER computer room air conditioner condensate drainage system consists of the following core components:

Component CategoryMain EquipmentFunction Description
Collection SystemWater tray, diversion groove, filter screenCollect condensate generated by the air conditioner evaporator, preliminarily filter impurities and prevent pipeline blockage
Conveyance SystemCondensate pipelines, elbows, tees, connectorsTransport condensate and connect all components to ensure unobstructed pipelines
Drainage ComponentU-type/S-type water trap, condensate lifting pump, float switchRealize gravity drainage or pressure drainage and overcome height and distance limitations
Leakage Prevention & Alarm SystemWater leakage detector, alarm controller, audible and visual alarmReal-timely monitor leakage conditions, trigger alarm signals in a timely manner and activate emergency measures
Thermal Insulation & Protection SystemThermal insulation layer, protective layer, fixed bracketPrevent pipeline condensation and dripping, reduce energy loss and fix pipeline positions
Control & Monitoring SystemLiquid level sensor, flow sensor, intelligent controllerAutomatically control the start and stop of drainage pumps, monitor system operating status and record operating data
Auxiliary ComponentsInspection port, cleaning port, check valve, exhaust valveFacilitate system maintenance, prevent water backflow and exhaust air inside pipelines

3. System Classification

3.1 Classification by Drainage Power

3.1.1 Gravity Drainage System

  • Working Principle: Adopt gravity and pipeline slope (≥1.5%) to realize natural condensate flow and drainage
  • System Composition: Water tray + PVC/galvanized steel pipe + water trap + drainage riser/floor drain
  • Applicable Scenarios: Computer rooms with floor drainage points, air conditioners installed higher than drainage outlets and sufficient installation space
  • Advantages: Simple structure, zero energy consumption, low maintenance cost and stable operation
  • Limitations: Strict requirements on installation slope, terrain-restricted, not applicable to high-rise buildings and long-distance drainage

3.1.2 Pressure (Lifting Pump) Drainage System

  • Working Principle: When the water level of the water tray reaches the set height, the float switch triggers the lifting pump to start, pressurize and lift condensate for drainage
  • System Composition: Water tray + lifting pump + pressure pipeline + check valve + control system
  • Applicable Scenarios: Air conditioners installed lower than drainage outlets, or scenarios requiring long-distance and high-lift drainage with limited computer room space
  • Advantages: Free from height and distance restrictions, flexible installation and capable of multi-point centralized drainage
  • Limitations: Electrically driven, operating noise generated, regular maintenance required for pumps and control systems

3.1.3 Hybrid Drainage System

  • Working Principle: Integrate the advantages of gravity and pressure drainage and automatically switch drainage modes according to actual working conditions
  • System Composition: Water tray + double drainage outlets + gravity pipeline + lifting pump + intelligent switching device
  • Applicable Scenarios: Large-scale data centers, multi-story computer rooms and computer rooms with complex layouts
  • Advantages: High reliability, adaptable to complex working conditions, mutual backup and reduced system failure risks
  • Limitations: Complex system structure, high initial investment and stricter maintenance requirements
computer room air conditioning condensate drainage system solution (6)

3.2 Classification by Pipeline Layout

3.2.1 Independent Drainage System

  • Each air conditioner unit is equipped with an independent drainage pipeline connected to the nearest drainage point
  • Advantages: Independent operation without mutual interference, few failure points and convenient maintenance
  • Application: Small computer rooms, independent air conditioner units and scenarios requiring separate protection for key equipment

3.2.2 Centralized Drainage System

  • Drainage pipes of multiple air conditioner units converge into a main pipeline for unified drainage
  • Advantages: Neat pipeline layout, space-saving and convenient for centralized management and monitoring
  • Application: Large-scale data centers and computer rooms with multiple parallel operating units

3.2.3 Zoned Drainage System

  • Divide drainage subsystems by floors or areas before converging into the main pipeline
  • Advantages: Integrate the strengths of independent and centralized systems, facilitating zoned management and maintenance
  • Application: Multi-story building computer rooms and large campus data centers

3.3 Classification by Recycling Method

3.3.1 Direct Drainage System

  • Condensate is directly discharged into municipal sewage pipes or rainwater pipes
  • Advantages: Simple system, low cost and easy maintenance
  • Application: Ordinary computer rooms without condensate recycling demands

3.3.2 Recycling System

  • Collected condensate is filtered and purified for non-potable uses such as cooling tower water replenishment and greening irrigation
  • Advantages: Save water resources, reduce operating costs and comply with green environmental protection concepts
  • Application: Large-scale data centers, computer rooms with high environmental protection requirements and water-scarce areas
computer room air conditioning condensate drainage system solution (5)

4. System Configuration List (KITOZER Brand)

4.1 Gravity Drainage System Configuration List

No.Product NameBrandModelSpecification ParametersUnitQuantityRemarks
1Condensate Water TrayKITOZERKT-JSP-01Compatible with all brands of precision air conditioners, with filter screen, 304 stainless steel materialPc1Matched with air conditioner model
2PVC Condensate PipeKITOZERKT-PVC-20DN20, wall thickness 2.0mm, corrosion-resistant, compliant with GB/T 10002.1mAs actualHorizontal slope ≥1.5%
3U-type Water TrapKITOZERKT-SW-20DN20, height ≥150mm, compatible with air conditioners with external static pressure ≤300PaPc1Prevent odor backflow
4Filter ScreenKITOZERKT-FL-10Aperture 1.0mm, 304 stainless steel, detachable and washablePc1Installed at water tray outlet
5Water Leakage DetectorKITOZERKT-LD-01Sensitivity ≤0.3L/h, dry contact signal outputSet1Laid along pipelines
6Thermal Insulation SleeveKITOZERKT-BW-20Thickness 10mm, Class B1 flame-retardant rubber & plastic material with aluminum foil protective layermAs actualPrevent condensation dripping
7Pipe BracketKITOZERKT-ZJ-01Galvanized steel plate, load capacity ≥50kg/mPcAs actualSpacing ≤1.5m
8Inspection PortKITOZERKT-JK-20DN20, convenient for pipeline dredging and maintenancePc11 set per 10 meters
9Elbow/TeeKITOZERKT-WT-20/KT-ST-20DN20, 90° elbow, tee, PVC materialPcAs actualFor pipeline turning and branching

4.2 Pressure (Lifting Pump) Drainage System Configuration List

No.Product NameBrandModelSpecification ParametersUnitQuantityRemarks
1Condensate Lifting PumpKITOZERKT-TB-05Flow 5L/min, lift 5m, power 25W, with float switchSet1Automatic start-stop, IPX8 protection grade
2Water TrayKITOZERKT-JSP-02With liquid level sensor, 304 stainless steel, capacity ≥5LPc1Adapted for lifting pump installation
3Pressure PipelineKITOZERKT-PP-16DN16, PPR material, pressure resistance 1.0MPa, compliant with GB/T 18742.2mAs actualHorizontal/vertical installation available
4Check ValveKITOZERKT-ZH-16DN16, brass material, prevent water backflowPc1Installed at pump outlet
5Intelligent ControllerKITOZERKT-KZ-01With LCD display, adjustable high/low water level, alarm signal outputSet1Monitor pump operating status
6Audible & Visual AlarmKITOZERKT-BJ-01Volume ≥85dB, red LED flashing, AC220V power supplyPc1Alarm for leakage or faults
7Thermal Insulation SleeveKITOZERKT-BW-16Thickness 10mm, Class B1 flame-retardant rubber & plastic materialmAs actualPrevent condensation dripping
8Pipe BracketKITOZERKT-ZJ-02Aluminum alloy material, load capacity ≥30kg/mPcAs actualSpacing ≤1.0m
9Exhaust ValveKITOZERKT-PQ-16DN16, automatic exhaust, prevent air lockPc1Installed at pipeline highest point
10Filter ScreenKITOZERKT-FL-10Aperture 1.0mm, 304 stainless steel materialPc1Installed at pump inlet

4.3 Hybrid Drainage System Configuration List

The hybrid drainage system is a combination of gravity and pressure systems, with the following additional dedicated components:

No.Product NameBrandModelSpecification ParametersUnitQuantityRemarks
1Double-outlet Water TrayKITOZERKT-JSP-03Dual outlets connected to gravity and pressure systems respectivelyPc1Matched with air conditioner model
2Automatic Switching ValveKITOZERKT-QH-20DN20, electric control, manual/automatic switching availablePc1Automatic switch to backup system during faults
3Intelligent Monitoring HostKITOZERKT-ZJ-02Monitor operating status of two systems and record fault informationSet1Support remote monitoring
4Backup Power SupplyKITOZERKT-BY-01DC12V, endurance ≥8 hoursPc1Ensure operation of lifting pump and alarm system during power outage
computer room air conditioning condensate drainage system solution (4)

5. System Schematic Diagram

5.1 Gravity Drainage System Schematic

Precision Air Conditioner Evaporator → Water Tray (with filter screen) → U-type Water Trap → PVC Condensate Pipe (slope ≥1.5%) → Inspection Port → Drainage Riser → Building Drainage System

↓

Water Leakage Detector → Alarm Controller → Audible & Visual Alarm

↓

Thermal Insulation Sleeve (condensation prevention)

5.2 Pressure (Lifting Pump) Drainage System Schematic

Precision Air Conditioner Evaporator → Water Tray → Float Switch/Liquid Level Sensor → KITOZER Lifting Pump → Check Valve → Pressure Pipeline → Exhaust Valve → Inspection Port → Drainage Riser → Building Drainage System

↓

Intelligent Controller → Audible & Visual Alarm/Remote Monitoring System

↓

Thermal Insulation Sleeve (condensation prevention)

5.3 Hybrid Drainage System Schematic

Precision Air Conditioner Evaporator → Double-outlet Water Tray → Automatic Switching Valve

├─→ Gravity Drainage Branch (U-type Water Trap + PVC Pipe) → Drainage Riser

└─→ Pressure Drainage Branch (Lifting Pump + Pressure Pipe) → Drainage Riser

↓

Intelligent Monitoring Host → Audible & Visual Alarm/Remote Monitoring System

↓

Backup Power Supply (automatic switching during power outage)

computer room air conditioning condensate drainage system solution (2)

6. Product Technical Parameters (KITOZER Brand)

6.1 Technical Parameters of Condensate Lifting Pump

Parameter ItemKT-TB-05KT-TB-10KT-TB-20
Flow Range5L/min10L/min20L/min
Maximum Lift5m8m12m
Rated Power25W40W60W
Power VoltageAC220V/50HzAC220V/50HzAC220V/50Hz
Protection GradeIPX8IPX8IPX8
Medium Temperature0-40℃0-40℃0-40℃
Medium pH Value2.7-8.52.7-8.52.7-8.5
Float SwitchBuilt-in, dual water level controlBuilt-in, dual water level controlBuilt-in, dual water level control
MaterialPump body: engineering plasticImpeller: 304 stainless steelPump body: engineering plasticImpeller: 304 stainless steelPump body: engineering plasticImpeller: 304 stainless steel
Dimension150×100×80mm180×120×90mm200×140×100mm
Weight1.2kg1.8kg2.5kg
Control ModeAutomatic (float switch/liquid level sensor)Automatic (float switch/liquid level sensor)Automatic (float switch/liquid level sensor)
Operating Noise≤35dB≤40dB≤45dB
Service Life≥10,000 hours≥10,000 hours≥10,000 hours

6.2 Technical Parameters of Condensate Pipelines

Parameter ItemPVC Pipe (KT-PVC Series)Galvanized Steel Pipe (KT-ZG Series)PPR Pipe (KT-PP Series)
Nominal DiameterDN15-DN50DN15-DN50DN15-DN50
Wall Thickness1.5-3.0mm1.2-2.5mm2.0-4.0mm
MaterialUPVCQ235 Galvanized SteelRandom Copolymer Polypropylene
Working Pressure0.6MPa1.6MPa1.0MPa
Applicable Temperature0-60℃-20-120℃0-70℃
Connection ModeBonding/FlangeThread/FlangeThermal Fusion/Flange
Corrosion ResistanceExcellent (acid & alkali resistant)Good (anti-corrosion treatment required)Excellent (chemical corrosion resistant)
Insulation RequirementInsulation required (condensation prevention)Insulation required (condensation prevention)Insulation required (condensation prevention)
Compliant StandardGB/T 10002.1GB/T 3091GB/T 18742.2

6.3 Technical Parameters of Water Leakage Detection System

Parameter ItemKT-LD-01KT-LD-02 (Wired)KT-LD-03 (Wireless)
Induction ModeConductive TypeConductive TypeConductive Type
Induction Sensitivity≤0.3L/h≤0.3L/h≤0.3L/h
Response Time≤1s≤1s≤1s
Detection Distance10m50m100m (wireless transmission)
Output SignalDry contact (normally open/normally closed)4-20mA/RS485433MHz wireless/Bluetooth
Working VoltageDC12VDC12VDC12V (built-in battery)
Working Temperature-10-50℃-10-50℃-10-50℃
Protection GradeIP65IP65IP67
Alarm ModeAudible & Visual AlarmAudible & Visual Alarm + Remote NotificationAudible & Visual Alarm + APP Push
Battery Life––≥2 years (standby)

6.4 Technical Parameters of Water Trap

Parameter ItemKT-SW-20KT-SW-25KT-SW-32
Nominal DiameterDN20DN25DN32
Material304 Stainless Steel/UPVC304 Stainless Steel/UPVC304 Stainless Steel/UPVC
Water Seal Height≥150mm≥180mm≥200mm
Adaptable Pressure≤300Pa≤500Pa≤800Pa
Temperature Resistance Range-20-100℃-20-100℃-20-100℃
Connection ModeThread/BondingThread/BondingThread/Bonding
Deodorization EffectExcellent (complete odor isolation)Excellent (complete odor isolation)Excellent (complete odor isolation)
computer room air conditioning condensate drainage system solution (1)

7. Product Application Scope

The KITOZER computer room air conditioner condensate drainage system is applicable to the following scenarios:

7.1 Data Center & IT Computer Room

  • Large-scale cloud computing data centers, financial data centers, Internet Data Centers (IDC)
  • Enterprise-level server rooms, network communication rooms, storage rooms
  • Edge computing nodes, micro data centers, modular data centers

7.2 Communication & Power Industry

  • Telecom operator rooms, base station rooms, core network rooms
  • Power dispatch centers, substation control rooms, UPS rooms
  • Radio & TV transmitting rooms, satellite communication rooms

7.3 Industrial & Medical Fields

  • Precision manufacturing workshops, clean rooms, constant temperature & humidity laboratories
  • Medical imaging centers, inspection departments, pharmacy cold storage
  • Industrial automatic control rooms, PLC rooms, DCS system rooms

7.4 Other Precision Environments

  • Museum cultural relic warehouses, archives, libraries
  • Semiconductor clean workshops, photolithography rooms, electronic component production workshops
  • Aerospace ground control centers, radar station rooms

8. Product Advantages (KITOZER Brand)

8.1 Technical Advantages

  • Full Independent R&D: KITOZER owns a complete product line of condensate drainage systems, with independent R&D and production for all components from water trays to intelligent controllers, ensuring system compatibility and stability
  • Intelligent Control Technology: Adopt advanced liquid level sensing and automatic control technology to realize precise start-stop control of drainage pumps, reduce energy consumption and extend equipment service life
  • Leakage Prevention & Early Warning System: Multi-stage water leakage detection with response time ≤1s, effectively avoiding losses caused by condensate leakage
  • Innovative Materials: Key components adopt 304/316 stainless steel and engineering plastics with strong corrosion resistance and service life ≥10 years

8.2 Performance Advantages

  • High Reliability: System MTBF (Mean Time Between Failures) ≥50,000 hours, meeting the 7×24-hour continuous operation requirements of computer rooms
  • Efficient Drainage: Sufficient flow of lifting pumps and qualified lift height ensure smooth drainage for most computer room scenarios
  • Low-noise Operation: Lifting pump operating noise ≤35dB, causing no interference to computer room environment
  • Energy Saving & Environmental Protection: Zero energy consumption for gravity systems, low power (≤60W) for pressure systems, supporting condensate recycling and reuse

8.3 Installation & Maintenance Advantages

  • Modular Design: Standardized components for simple installation and shortened construction cycle
  • Wide Compatibility: Compatible with all mainstream brands of precision air conditioners (Emerson, Vertiv, Schneider, Huawei, etc.)
  • Easy Maintenance: Detachable and washable key components and reasonably arranged inspection ports reduce maintenance costs
  • Remote Monitoring: Support Modbus, BACnet and other communication protocols, connectable to computer room environment monitoring systems for remote management and fault early warning

8.4 Safety Advantages

  • Multiple Protection: Equipped with over-current, over-load and dry-burning protection functions to prevent equipment damage and safety accidents
  • Deodorization Design: Standard-height U-type water trap effectively isolates odor backflow from drainage systems
  • Fire Resistance: Partial products pass UL94 V0 flame retardant certification, complying with computer room fire protection requirements
  • Leakage Protection: Lifting pumps and controllers are equipped with leakage protection devices to ensure personnel safety

9. Bidding Specification Parameters (KITOZER Brand)

9.1 Core Product Bidding Parameters

9.1.1 Condensate Lifting Pump Bidding Parameters

  1. Brand: KITOZER (no alternative brands accepted)
  2. Flow: ≥5L/min (KT-TB-05), ≥10L/min (KT-TB-10), ≥20L/min (KT-TB-20)
  3. Lift: ≥5m (KT-TB-05), ≥8m (KT-TB-10), ≥12m (KT-TB-20)
  4. Protection Grade: IPX8 (continuous underwater operation available)
  5. Control Mode: Dual control via float switch + liquid level sensor to ensure reliable drainage
  6. Motor Protection: Equipped with over-current, over-load and dry-burning protection functions
  7. Noise: ≤35dB (KT-TB-05), ≤40dB (KT-TB-10), ≤45dB (KT-TB-20)
  8. Material: Pump body made of engineering plastic, impeller made of 304 stainless steel
  9. Service Life: ≥10,000 hours of continuous operation
  10. Certification: CE, RoHS certified

9.1.2 Water Leakage Detection System Bidding Parameters

  1. Brand: KITOZER (no alternative brands accepted)
  2. Induction Mode: Conductive type with sensitivity ≤0.3L/h
  3. Response Time: ≤1s for timely leakage detection
  4. Detection Distance: ≥10m (basic type), ≥50m (wired type), ≥100m (wireless type)
  5. Output Signal: Support dry contact, 4-20mA, RS485, 433MHz wireless and other output modes
  6. Working Voltage: DC12V, backup power endurance ≥8 hours
  7. Protection Grade: IP65 (basic type), IP67 (wireless type)
  8. Alarm Mode: Audible & visual alarm + remote notification, compatible with computer room environment monitoring system integration
  9. Certification: CE, FCC certified

9.1.3 Condensate Pipeline Bidding Parameters

  1. Brand: KITOZER (no alternative brands accepted)
  2. PVC Pipe: Compliant with GB/T 10002.1, wall thickness ≥2.0mm (DN20), corrosion-resistant and well insulated
  3. Water Trap: 304 stainless steel or UPVC material, water seal height ≥150mm (adapted for air conditioners with external static pressure ≤300Pa)
  4. Insulation Layer: Class B1 flame-retardant rubber & plastic material, thickness ≥10mm with aluminum foil protective layer to prevent condensation dripping
  5. Pipeline Slope: Horizontal section slope ≥1.5%, branch pipe slope ≥1% to ensure smooth drainage

9.2 Overall System Bidding Parameters

  1. System Design: Compliant with Code for Design of Heating, Ventilation and Air Conditioning of Civil Buildings (GB 50736-2012) and Code for Design of Data Centers (GB 50174-2017)
  2. Drainage Mode: Gravity, pressure or hybrid drainage system optional according to actual computer room conditions
  3. Leakage Prevention Measures: Multi-stage water leakage detection system must be equipped with detection tapes laid along pipelines and under air conditioners
  4. Maintenance Convenience: Inspection ports and cleaning ports shall be reserved for daily maintenance and pipeline dredging
  5. System Compatibility: Compatible with all mainstream brands of precision air conditioners and integrable with computer room environment monitoring systems
  6. Reliability: System MTBF ≥50,000 hours
  7. Safety Certification: Key system components pass CE, RoHS and other international certifications

10. Product Solutions

10.1 Small Computer Room Solution (Below 100㎡)

10.1.1 Solution Overview

For small computer rooms (enterprise server rooms, miniature IDCs, edge computing nodes), the KITOZER gravity drainage system is recommended, featuring simple structure, low cost and easy maintenance to meet basic drainage demands.

10.1.2 System Configuration

  • Core Components: KITOZER Water Tray (KT-JSP-01), PVC Condensate Pipe (KT-PVC-20), U-type Water Trap (KT-SW-20), Filter Screen (KT-FL-10), Water Leakage Detector (KT-LD-01), Thermal Insulation Sleeve (KT-BW-20)
  • Drainage Mode: Gravity drainage with horizontal pipeline slope ≥1.5%, connected to the nearest building drainage system
  • Leakage Prevention Measures: Water leakage detectors laid along pipelines with backup water trays installed under air conditioners

10.1.3 Solution Advantages

  • Low investment cost, simple installation and short construction cycle
  • Zero energy consumption, low operating cost and easy maintenance
  • High reliability with few failure points, suitable for unattended small computer room scenarios

10.2 Medium Computer Room Solution (100-500㎡)

10.2.1 Solution Overview

For medium computer rooms (enterprise-level data centers, communication rooms, power dispatch centers), the KITOZER pressure drainage system is recommended to solve height difference and long-distance drainage problems and improve system flexibility.

10.2.2 System Configuration

  • Core Components: KITOZER Lifting Pump (KT-TB-10), Double-outlet Water Tray (KT-JSP-03), Pressure Pipeline (KT-PP-16), Check Valve (KT-ZH-16), Intelligent Controller (KT-KZ-01), Water Leakage Detector (KT-LD-02)
  • Drainage Mode: Pressure drainage with lifting pump lift ≥8m, supporting horizontal and vertical pipeline laying
  • Control Mode: Intelligent controller automatically controls pump start-stop, monitors system status and supports remote monitoring
  • Leakage Prevention Measures: Multi-stage water leakage detection with alarm signals connected to the computer room environment monitoring system

10.2.3 Solution Advantages

  • Free from terrain restrictions with flexible installation, adaptable to complex computer room layouts
  • Automatic control and stable operation with minimal manual intervention
  • Support multi-point centralized drainage for convenient system management and maintenance

10.3 Large Data Center Solution (Above 500㎡)

10.3.1 Solution Overview

For large-scale data centers (cloud computing data centers, super-large IDCs), the KITOZER hybrid drainage system is recommended, integrating the advantages of gravity and pressure systems to realize dual protection and enhance system reliability.

10.3.2 System Configuration

  • Core Components: KITOZER Double-outlet Water Tray (KT-JSP-03), Automatic Switching Valve (KT-QH-20), Lifting Pump (KT-TB-20), U-type Water Trap (KT-SW-32), Intelligent Monitoring Host (KT-ZJ-02), Backup Power Supply (KT-BY-01), Wireless Water Leakage Detector (KT-LD-03)
  • Drainage Mode: Pressure drainage as the main system and gravity drainage as the backup system, with automatic switching via switching valve during faults
  • Control Mode: The intelligent monitoring host real-timely monitors the status of two systems, records fault data and supports remote monitoring and data analysis
  • Leakage Prevention Measures: Full-pipeline leakage detection, water baffles and backup water trays under air conditioners, and emergency drainage system

10.3.3 Solution Advantages

  • Dual-system backup with high reliability, suitable for mission-critical data centers
  • Intelligent monitoring and fault early warning reduce downtime risks
  • Support condensate recycling and reuse, complying with green data center standards

10.4 Condensate Recycling Solution

10.4.1 Solution Overview

For computer rooms with high environmental protection requirements and water resource shortages, the KITOZER condensate recycling system is adopted. Collected condensate is filtered and purified for non-potable uses such as cooling tower water replenishment and greening irrigation to save water resources and reduce operating costs.

10.4.2 System Configuration

  • Core Components: KITOZER recycling water tank, filtering device, disinfection device, water pump, intelligent control system
  • Treatment Process: Condensate → Collection → Filtration → Disinfection → Storage → Reuse (cooling tower water replenishment/greening irrigation)
  • Control Mode: The intelligent controller monitors water quality and water level to automatically control the treatment and reuse process

10.4.3 Solution Advantages

  • Save water resources and reduce operating costs (cooling tower water replenishment saves over 30% of tap water consumption)
  • Alleviate municipal drainage pressure and comply with environmental protection policies
  • Condensate is pure water with low treatment cost and high reuse value

11. Product Application Cases

11.1 Case 1: Large Hybrid Drainage System for a Cloud Computing Data Center in Guangzhou

Project Overview

Shopping Cart