Warning: Undefined variable $taxonomy in /www/wwwroot/gdlain.com/public_html/wp-content/mu-plugins/gdlain-breadcrumb-jsonld.php on line 31

Warning: Undefined variable $taxonomy in /www/wwwroot/gdlain.com/public_html/wp-content/mu-plugins/gdlain-breadcrumb-jsonld.php on line 32

Warning: Undefined variable $taxonomy in /www/wwwroot/gdlain.com/public_html/wp-content/mu-plugins/gdlain-breadcrumb-jsonld.php on line 31

Warning: Undefined variable $taxonomy in /www/wwwroot/gdlain.com/public_html/wp-content/mu-plugins/gdlain-breadcrumb-jsonld.php on line 32

Warning: Undefined variable $taxonomy in /www/wwwroot/gdlain.com/public_html/wp-content/mu-plugins/gdlain-breadcrumb-jsonld.php on line 31

Warning: Undefined variable $taxonomy in /www/wwwroot/gdlain.com/public_html/wp-content/mu-plugins/gdlain-breadcrumb-jsonld.php on line 32

Warning: Undefined variable $taxonomy in /www/wwwroot/gdlain.com/public_html/wp-content/mu-plugins/gdlain-breadcrumb-jsonld.php on line 31

Warning: Undefined variable $taxonomy in /www/wwwroot/gdlain.com/public_html/wp-content/mu-plugins/gdlain-breadcrumb-jsonld.php on line 32

Warning: Undefined variable $taxonomy in /www/wwwroot/gdlain.com/public_html/wp-content/mu-plugins/gdlain-breadcrumb-jsonld.php on line 31

Warning: Undefined variable $taxonomy in /www/wwwroot/gdlain.com/public_html/wp-content/mu-plugins/gdlain-breadcrumb-jsonld.php on line 32

Warning: Undefined variable $taxonomy in /www/wwwroot/gdlain.com/public_html/wp-content/mu-plugins/gdlain-breadcrumb-jsonld.php on line 31

Warning: Undefined variable $taxonomy in /www/wwwroot/gdlain.com/public_html/wp-content/mu-plugins/gdlain-breadcrumb-jsonld.php on line 32
KITOZER
KITOZER

KITOZER Equipotential Connection Fittings

1. System Introduction

1.1 System Overview

The KITOZER computer room equipotential connection system is the core component of the computer room lightning protection and grounding system. It constructs a complete equipotential body by connecting all metal components, equipment shells, cabinets, pipelines, and shielded cable outer layers in the computer room through a low-impedance conductor network. The system eliminates potential differences between various points during lightning strikes or power faults, prevents ground potential counterattack and personal electric shock accidents, and ensures the safe operation of electronic information equipment. Strictly complying with GB 50343-2012 Technical Code for Lightning Protection of Building Electronic Information Systems and GB 50174-2017 Code for Design of Data Centers, the KITOZER equipotential connection fitting system provides a full-set standardized equipotential connection solution, widely applicable to all types of data centers, computer rooms, communication rooms and server rooms.

1.2 System Operation Mechanism

Based on Ohm’s law and Faraday cage principle, the equipotential connection system realizes multi-dimensional safety protection through the following core mechanisms:

  • Electric Shock Prevention Protection: During lightning strikes or power faults, fault current forms a low-impedance path through equipotential connection conductors, limiting the contact voltage within a safe range (≤50V) and improving electric shock protection efficiency by about 80%.
  • Electrochemical Corrosion Suppression: Eliminates potential differences between different metal components, avoids electrochemical corrosion caused by long-term potential imbalance, and prolongs the service life of metal facilities.
  • Static Electricity Release: Provides a stable static discharge path to prevent static accumulation on the surface of precision electronic equipment and avoid component breakdown and data loss caused by static electricity.
  • Electromagnetic Interference Shielding: Forms a closed shielding network to reduce the impact of Electromagnetic Interference (EMI) and Radio Frequency Interference (RFI), improving the stability of equipment signal transmission.
  • Enhanced Lightning Protection Effect: Provides an effective and reliable grounding path for Surge Protective Devices (SPD), ensuring rapid release of lightning surge current and maximizing the lightning protection performance of the whole system.
equipotential bonding accessories solution for computer rooms (8)

1.3 System Design Principles

The KITOZER equipotential connection system adheres to five major standardized design principles to ensure systematic, reliable and maintainable system operation:

  • Shortest Path Principle: All connection routes adopt the shortest layout path to reduce conductor impedance and inductance, realizing fast current discharge.
  • Low-Impedance Priority Principle: High-conductivity pure copper materials are selected for all core conductors, with the overall system connection resistance ≤0.2Ω and key node resistance ≤0.03Ω.
  • Grid & Star Composite Principle: Flexibly adopt S-type (star), M-type (grid) or composite structure according to computer room scale, equipment density and layout characteristics.
  • Redundancy Safety Principle: Double connection design is adopted for key equipment and core connection nodes to eliminate single-point faults and improve system operational reliability.
  • Detectable Maintainable Principle: All key connection points are equipped with reserved detection ports, supporting real-time testing, daily maintenance and regular performance verification.
equipotential bonding accessories solution for computer rooms (7)

2. System Composition

The KITOZER computer room equipotential connection fitting system consists of six core component categories, forming a closed-loop, fully covered and highly reliable equipotential connection network, covering all links from current conduction, fixed connection, grounding output to detection and protection.

Component CategoryCore ProductsFunction Description
Equipotential Terminal DeviceMain Equipotential Bonding Box (MEB), Local Equipotential Bonding Box (LEB), Equipotential BusbarCollect all equipotential connection conductors, provide centralized and standardized connection nodes, facilitate unified system management, daily detection and fault troubleshooting
Connection ConductorCopper busbar, copper cable, copper foil, grounding wireRealize electrical connection between all metal components in the computer room, undertake the conduction and transmission of fault current, lightning surge and static charge
Connection FittingsExothermic welding kit, equipotential connector, grounding terminal, jumper wire, lock washerEnsure mechanical connection strength and electrical continuity of nodes, avoid loose contact and virtual connection, and form stable low-impedance connection points
Grounding DeviceGrounding electrode, grounding module, grounding main lineProvide stable grounding reference points for the whole system, and safely introduce various abnormal currents into the earth
Detection FittingsDetection terminal, test point, milliohm meterComplete system conductivity and resistance testing after installation, support regular performance detection and hidden danger investigation
Auxiliary FittingsFixed bracket, insulating gasket, anti-corrosion materialEnsure firm installation of system components, prevent metal corrosion, realize effective electrical isolation, and avoid interference and short-circuit risks

3. System Classification

3.1 Classification by Protection Level

ClassificationDefinitionApplicable ScopeKITOZER Recommended Products
Main Equipotential Bonding (MEB)Connect all metal components of the building with the grounding device to form a unified building-wide equipotential bodyWhole building, large-scale data center, comprehensive computer room clusterKITOZER-MEB series main equipotential box, 30×3mm purple copper busbar
Local Equipotential Bonding (LEB)Connect metal components in specific areas of the computer room to form an independent local equipotential bodySingle computer room area, server cabinet row, regional equipment clusterKITOZER-LEB series local equipotential box, 20×2mm purple copper busbar
Auxiliary Equipotential BondingSupplementary connection for two or more simultaneously accessible electrical equipment to eliminate local potential differenceKey precision equipment, operation console surface, sensitive electrical equipment areaKITOZER-EP series equipotential connector, multi-strand copper cable

3.2 Classification by Structural Form

ClassificationStructural CharacteristicsApplicable ScenariosKITOZER Recommended Configuration
S-type (Star) StructureAll equipment is connected to the Equipotential Reference Point (ERP) through a single point, with centralized and unified potential referenceSmall computer rooms, scenarios with few equipment and simple layoutKITOZER-ERP series equipotential reference point, 25mm² copper cable
M-type (Grid) StructureForm copper foil/copper busbar grid under the anti-static floor, with equipment connected nearby and multi-point parallel conductionLarge-scale IDC computer rooms, equipment-intensive areas, high-precision scenariosKITOZER-MG series grid copper busbar, 50mm² copper foil
Composite StructureCombination of S-type and M-type structures: M-type grid for core area and S-type star for peripheral areaMedium-sized computer rooms, mixed equipment layout scenariosKITOZER-COM series composite kit, copper busbar + copper cable combination

3.3 Classification by Connection Mode

ClassificationConnection CharacteristicsAdvantagesApplicable ScenariosKITOZER Recommended Products
Bolt ConnectionDetachable connection with bolts and lock washersEasy maintenance, detectable and reusableEquipment cabinets, movable connection pointsKITOZER-BC series bolt connector, lock washer (torque 35N·m)
Welding ConnectionPermanent connection by exothermic welding or fusion weldingUltra-low connection resistance, high mechanical strengthGrounding main line, fixed connection pointsKITOZER-EX series exothermic welding kit, welding powder (purity ≥99.5%)
Crimping ConnectionConductor crimping by hydraulic toolsSimple operation, stable and reliable connectionCopper cable and terminal connectionKITOZER-CR series crimping tools, copper lugs
Detectable ConnectionEquipped with detection ports for instrument accessReal-time detection, ensure connection validityKey connection points, concealed worksKITOZER-TD series detection terminals, test points
equipotential bonding accessories solution for computer rooms (7)

4. System Configuration List (KITOZER Brand)

4.1 Small Computer Room Configuration List (≤50㎡)

No.Product NameModelSpecificationQtyBrandRemarks
1Main Equipotential Terminal BoxKITOZER-MEB-300300×400×120mm, built-in 30×3mm copper busbar1 SetKITOZERInstalled at computer room inlet
2Local Equipotential Terminal BoxKITOZER-LEB-200200×300×100mm, built-in 20×2mm copper busbar2 SetsKITOZERDistributed by area
3Equipotential Connection BusbarKITOZER-CB-25×325×3mm purple copper, 2m length4 PcsKITOZERFor cabinet equipment connection
4Copper Core CableKITOZER-CC-5050mm² multi-strand copper cable, 5m length6 PcsKITOZERConnect cabinet and equipotential busbar
5Grounding Copper FoilKITOZER-CF-5050mm width, 0.2mm thickness10mKITOZERAnti-static floor connection
6Exothermic Welding KitKITOZER-EX-100Including welding powder, mold, igniter1 SetKITOZERCopper busbar and cable connection
7Equipotential ConnectorKITOZER-EP-60Nominal discharge current 60kA (8/20μs)8 PcsKITOZEREquipment shell connection
8Grounding TerminalKITOZER-GT-M10M10 thread, pure copper material16 PcsKITOZEREquipment grounding connection
9Lock WasherKITOZER-LP-10Adapt to M10 bolt32 PcsKITOZEREnsure firm connection and anti-loosening
10Detection TerminalKITOZER-TD-01With test port4 PcsKITOZERConvenient for system detection
11Fixed BracketKITOZER-FB-01Galvanized steel material12 PcsKITOZERCopper busbar fixed installation

4.2 Medium Computer Room Configuration List (50-200㎡)

No.Product NameModelSpecificationQtyBrandRemarks
1Main Equipotential Terminal BoxKITOZER-MEB-400400×500×150mm, built-in 40×4mm copper busbar1 SetKITOZERInstalled at computer room inlet
2Local Equipotential Terminal BoxKITOZER-LEB-250250×350×120mm, built-in 25×3mm copper busbar4 SetsKITOZERDistributed by area
3Equipotential Connection BusbarKITOZER-CB-30×330×3mm purple copper, 3m length8 PcsKITOZERFor cabinet equipment connection
4Copper Core CableKITOZER-CC-7070mm² multi-strand copper cable, 8m length12 PcsKITOZERConnect cabinet and equipotential busbar
5Grounding Copper FoilKITOZER-CF-8080mm width, 0.3mm thickness20mKITOZERForm 3m×3m grid under floor
6Exothermic Welding KitKITOZER-EX-200Including welding powder, mold, igniter2 SetsKITOZERCopper busbar and cable connection
7Equipotential ConnectorKITOZER-EP-80Nominal discharge current 80kA (8/20μs)16 PcsKITOZERImportant equipment connection
8Grounding TerminalKITOZER-GT-M12M12 thread, pure copper material32 PcsKITOZEREquipment grounding connection
9Lock WasherKITOZER-LP-12Adapt to M12 bolt64 PcsKITOZERAnti-loosening and firm fixing
10Detection TerminalKITOZER-TD-02With test port and indicator light8 PcsKITOZERReal-time status detection
11Fixed BracketKITOZER-FB-02Thickened galvanized steel24 PcsKITOZERStable support installation
12Connection JumperKITOZER-JB-2525mm² copper cable, 0.5m length16 PcsKITOZERConnection between cabinets
equipotential bonding accessories solution for computer rooms (6)

4.3 Large Computer Room Configuration List (≥200㎡)

No.Product NameModelSpecificationQtyBrandRemarks
1Main Equipotential Terminal BoxKITOZER-MEB-500500×600×180mm, built-in 40×4mm copper busbar1 SetKITOZERDual redundant design at inlet
2Local Equipotential Terminal BoxKITOZER-LEB-300300×400×120mm, built-in 30×3mm copper busbar6 SetsKITOZEROne set per functional area
3Equipotential Connection BusbarKITOZER-CB-40×440×4mm purple copper, 3m length12 PcsKITOZERForm integral grid network
4Copper Core CableKITOZER-CC-9595mm² multi-strand copper cable, 10m length24 PcsKITOZERDual redundant connection
5Grounding Copper FoilKITOZER-CF-100100mm width, 0.5mm thickness50mKITOZERForm 2m×2m high-density grid
6Exothermic Welding KitKITOZER-EX-300With thermometer, welding mold and powder3 SetsKITOZEREnsure welding quality standard
7Equipotential ConnectorKITOZER-EP-100Nominal discharge current 100kA (8/20μs)32 PcsKITOZERDual connection for key equipment
8Grounding TerminalKITOZER-GT-M16M16 thread, copper  