Internal resistance (IR) testing is the fastest way to spot weak UPS batteries without interrupting the load. KITOZER recommends quarterly IR tests using a handheld battery impedance tester.
Table of Contents
ToggleTest Procedure
First, record baseline IR for every new battery during installation. Each quarter, compare live readings against the baseline. A battery whose IR rises more than 20 percent above baseline is flagged. A rise above 50 percent means immediate replacement. Also record float voltage: a cell sitting below 2.20V per cell while charger is active indicates internal deterioration. Test in-service batteries only, with proper insulated tools and eye protection.
Documentation
Log voltage, IR, date, and technician name for each battery. Compare strings side by side: weak cells pull the whole string down during a power event.