KITOZER
KITOZER

KITOZER High-Voltage Metering Cabinet Solution

Table of Contents

1. System Overview

The KITOZER high-voltage metering cabinet is a core high-voltage power distribution and metering device developed under the KITOZER brand of Guangzhou Lai’an Intelligent System Development Co., Ltd. It is applicable to 3kV~35kV three-phase AC 50Hz power systems. Integrating accurate electric energy metering, operating status monitoring, anti-electricity theft management, safety interlock protection and remote data transmission, this special cabinet serves as a key node equipment for electric energy settlement, energy consumption statistics and power grid dispatching in power systems. It is widely deployed in substations, industrial and mining enterprises, urban power grids, new energy power stations (photovoltaic/wind power/energy storage), rail transit, data centers and other scenarios.

Designed and manufactured in strict compliance with standards including GB 3906, GB/T 16934, DL/T 448 and IEC 62271, the system adopts a fully enclosed metal armored structure featuring four core characteristics: five-prevention interlock, IP54 protection, high-precision metering and intelligent operation & maintenance. It can operate stably under environments of -40℃~+55℃, altitude ≤3000m and pollution class III, with electric energy metering error ≤±0.2%, data upload delay ≤3s and fault positioning accuracy ≤1m. It delivers a full-process high-voltage electric energy metering solution that is safe, accurate, efficient and traceable.

2. System Composition

The KITOZER high-voltage metering cabinet adopts a modular architecture consisting of primary circuit, secondary circuit and intelligent auxiliary system. Each unit operates independently and collaborates in linkage to guarantee metering accuracy and operational safety.

2.1 Primary Main Circuit Unit

Responsible for high-voltage power input, voltage/current signal conversion and short-circuit protection, its core components are as follows:

  • Cabinet body: High-quality cold-rolled steel plate (thickness ≥2.5mm), formed by laser cutting and welding, electrostatic powder coated surface, protection class IP54.
  • Current Transformer (CT): 0.2S high-precision grade, collects large line current signals and converts them into standard small current (5A/1A).
  • Voltage Transformer (PT): 0.2 high-precision grade, collects bus high-voltage signals and converts them into standard low voltage (100V).
  • High-voltage fuse: Protects PT against short-circuit faults and quickly melts to cut off faulty circuits.
  • Zinc oxide arrester: Suppresses lightning overvoltage and switching overvoltage to protect internal equipment insulation of the cabinet.
  • Disconnector/Earthing switch: Enables primary circuit isolation and earthing safety protection, equipped with mechanical interlock.

2.2 Secondary Metering Circuit Unit

Responsible for signal processing, electric energy metering, data display and transmission, its core components are as follows:

  • Multi-function electric energy meter: 0.2S grade, measures active/reactive electric energy, voltage, current, power, power factor and frequency, supports peak-valley time-of-use metering.
  • Data acquisition terminal: Collects metering data and equipment status, supports 4G/5G, Ethernet and RS485 communication.
  • Secondary terminal block: Flame-retardant material, standardized wiring for easy commissioning and maintenance, with anti-misconnection design.
  • Electric energy meter sealing device: Prevents electricity theft and ensures metering data cannot be tampered with.

2.3 Intelligent Auxiliary System Unit

Responsible for safety protection, environmental monitoring and remote operation & maintenance, its core components are as follows:

  • Five-prevention interlock mechanism: Dual mechanical and electrical interlock to realize “prevent accidental closing/opening of circuit breakers, prevent closing/opening disconnectors under load, prevent earthing wire hanging under live condition, prevent closing circuit breakers with earthing wires connected, prevent entry into live compartments”.
  • Live display device: Real-time monitoring of live status of high-voltage circuits to avoid live operation.
  • Temperature & humidity controller: Monitors internal temperature and humidity of the cabinet, automatically activates heating/cooling devices to prevent moisture and condensation.
  • Intelligent lockset: Dynamic encrypted authorization, remote unlocking records, prevents unauthorized operation.
  • Fault alarm module: Triggers sound-light alarm and uploads signals upon abnormalities (overvoltage, overcurrent, phase loss, excessive temperature/humidity).

3. System Classification

The KITOZER high-voltage metering cabinet is classified from four dimensions: voltage class, structural form, metering function and intelligence level, covering all scenario requirements.

3.1 Classification by Voltage Class

  • 10kV high-voltage metering cabinet: Adapted to 10kV power grid, the most commonly used type for industrial and mining enterprises, urban distribution substations and photovoltaic power stations.
  • 35kV high-voltage metering cabinet: Adapted to 35kV power grid, applied to large substations, wind power bases and energy storage power stations.
  • 6kV high-voltage metering cabinet: Adapted to 6kV power grid, used for small industrial and mining enterprises and internal power distribution of industrial parks.

3.2 Classification by Structural Form

  • Middle-mounted metering cabinet (KYN28-12): Metal armored withdrawable type with trolley structure for convenient maintenance and high protection class, installed indoors.
  • Fixed metering cabinet (XGN-12): Fixed cabinet body with fixedly installed CT/PT, low cost and simple structure, available for indoor/outdoor installation.
  • Floor-mounted metering box (HYJL-12): Fully sealed and fully insulated with IP67 protection, installed outdoors for residential quarters, streets, mines and other scenarios.

3.3 Classification by Metering Function

  • Pure metering type: Only realizes electric energy metering and data display without control functions, used for basic energy consumption statistics.
  • Prepaid metering type: Integrated prepaid control with automatic tripping upon arrears and support for remote recharge, applied to commercial power consumption and temporary electricity usage.
  • Load control metering type: Integrated load control to remotely regulate loads and communicate with power supply background, for large industrial users.
  • Multi-function intelligent metering type: Integrates metering, monitoring, protection, communication and anti-electricity theft, suitable for smart power grids.

3.4 Classification by Intelligence Level

  • Basic type: Local metering, manual meter reading and mechanical interlock without remote functions.
  • Intelligent type: Remote meter reading, data upload, remote monitoring, fault alarm and intelligent temperature & humidity control.
  • IoT type: Connected to KITOZER IoT platform, supporting real-time monitoring, remote operation & maintenance, big data analysis and energy consumption optimization.

4. System Schematic Diagram

4.1 Primary System Schematic Diagram (10kV Three-Phase Three-Wire)

The core adopts 2CT+2PT two-element wiring, applicable to 10kV neutral point non-effectively earthed system.

  • High-voltage bus → Disconnector → CT (Phase A/C) → PT (V/V wiring) → High-voltage fuse → Arrester → Cable outgoing line.
  • CT secondary side (5A) → Current circuit of electric energy meter; PT secondary side (100V) → Voltage circuit of electric energy meter.

4.2 Secondary System Schematic Diagram

  • Metering circuit: CT/PT secondary signals → Multi-function electric energy meter → Data acquisition terminal → Communication module → Remote platform.
  • Control circuit: Temperature & humidity controller, live display device, intelligent lock, alarm module → Secondary power supply → Control bus.
  • Interlock circuit: Five-prevention interlock mechanism → Disconnector/Earthing switch → Circuit breaker interlock to prevent misoperation.

5. Full System Configuration List (Basic/Mid/High-End Grades)

5.1 Basic Grade (Basic Pure Metering Type, Indoor Fixed XGN-12)

表格

No.Product NameModel & SpecificationTechnical ParametersQtyUnitBrandRemarks
1High-Voltage Metering Cabinet BodyXGN-12-10kVRated voltage 10kV, rated current 630A, short-circuit breaking current 20kA, protection class IP54, 2.5mm cold-rolled steel plate, electrostatic powder coating1SetKITOZERIndoor fixed type, size 800×1200×2200mm
2Current Transformer (CT)LMK-10-0.2SRated voltage 10kV, ratio 200/5A, accuracy class 0.2S, rated burden 10VA, insulation class F2SetKITOZERInstalled on Phase A/C, dedicated for metering
3Voltage Transformer (PT)JDZJ-10-0.2Rated voltage 10/√3/0.1/√3kV, accuracy class 0.2, rated burden 15VA, insulation class F, V/V wiring2SetKITOZERDedicated for metering, with fuse protection
4High-Voltage FuseRN2-10/0.5ARated voltage 10kV, rated current 0.5A, breaking current 50kA, protects PT against short circuit3PieceKITOZERInstalled on high-voltage side of PT
5Zinc Oxide ArresterHY5WZ-17/45Rated voltage 17kV, residual voltage 45kV, nominal discharge current 10kA, suppresses overvoltage1GroupKITOZERThree-phase group, installed on bus side
6Multi-Function Electric Energy MeterDT862-100V/5AVoltage 100V, current 5A, accuracy class 0.2S, three-phase three-wire, active/reactive energy metering, local display1PieceKITOZERSealed design for anti-electricity theft
7Secondary Terminal BlockJH2-2.5Rated voltage 660V, rated current 20A, 24 positions, flame-retardant ABS material2BlockKITOZERSecondary circuit wiring
8Five-Prevention Interlock MechanismMatched with XGN-12Mechanical interlock for misoperation prevention, matched with cabinet body1SetKITOZERStandard configuration to ensure operation safety
9Live Display DeviceDXN-10TRated voltage 10kV, induction type with live indicator light display, no secondary power supply required1SetKITOZERThree-phase display, high-voltage side monitoring
10Secondary Power SupplyAC/DC220VInput AC220V, output DC24V/AC220V, power 100W1SetKITOZERPower supply for secondary circuit

5.2 Mid-End Grade (Intelligent Metering Type, Indoor Middle-Mounted KYN28-12)

表格

No.Product NameModel & SpecificationTechnical ParametersQtyUnitBrandRemarks
1High-Voltage Metering Cabinet BodyKYN28-12-10kVRated voltage 10kV, rated current 1250A, short-circuit breaking current 31.5kA, protection class IP54, 3mm cold-rolled steel plate, electrostatic powder coating, trolley structure1SetKITOZERIndoor middle-mounted type, size 800×1500×2300mm
2Metering TrolleyKYN28-12-CT/PTIntegrated CT/PT, trolley type, rated current 1250A, strong interchangeability1SetKITOZEREasy to pull out for maintenance
3Current Transformer (CT)LZZBJ9-10-0.2SRated voltage 10kV, ratio 500/5A, accuracy class 0.2S, rated burden 15VA, insulation class F, cast insulation2SetKITOZERInstalled on Phase A/C, dedicated for metering
4Voltage Transformer (PT)JDZ9-10-0.2Rated voltage 10/√3/0.1/√3kV, accuracy class 0.2, rated burden 20VA, insulation class F, cast insulation, V/V wiring2SetKITOZERDedicated for metering, with fuse protection
5High-Voltage FuseXRNT-10/1ARated voltage 10kV, rated current 1A, breaking current 63kA, protects PT against short circuit3PieceKITOZERInstalled on high-voltage side of PT
6Zinc Oxide ArresterHY5WZ-17/50Rated voltage 17kV, residual voltage 50kV, nominal discharge current 20kA, suppresses overvoltage1GroupKITOZERThree-phase group, installed on bus side
7Multi-Function Intelligent Electric Energy MeterDSZ862-100V/5AVoltage 100V, current 5A, accuracy class 0.2S, three-phase three-wire, active/reactive/peak-valley metering, RS485 communication, local LCD display1PieceKITOZERSealed design for anti-electricity theft, supports remote meter reading
8Data Acquisition TerminalKT-600Supports RS485/Ethernet, collects energy data and equipment status, stores 1-year data, DL/T698 protocol1SetKITOZERUploads data to background system
9Secondary Terminal BlockJH2-4.0Rated voltage 660V, rated current 32A, 36 positions, flame-retardant ABS material2BlockKITOZERSecondary circuit wiring
10Five-Prevention Interlock MechanismMatched with KYN28-12Dual mechanical and electrical interlock for misoperation prevention, matched with cabinet body1SetKITOZERStandard configuration to ensure operation safety
11Live Display DeviceDXN-10T/CSRated voltage 10kV, induction type with live indicator light display and interlock function1SetKITOZERThree-phase display, high-voltage side monitoring
12Temperature & Humidity ControllerWK-100Temperature range -20℃~+60℃, humidity range 0~100%RH, automatic heating/cooling, RS485 communication1SetKITOZERInternal cabinet environmental monitoring & control
13Fault Alarm ModuleALM-200Alarms for overvoltage, overcurrent, phase loss and excessive temperature/humidity, sound-light prompt, dry contact output1SetKITOZERAbnormality early warning
14Secondary Power SupplyAC/DC220V/DC24VInput AC220V, output DC24V/AC220V, power 200W, redundant design1SetKITOZERStable power supply for secondary circuit

5.3 High-End Grade (IoT Prepaid Metering Type, Optional Outdoor Floor-Mounted/Middle-Mounted)

表格

No.Product NameModel & SpecificationTechnical ParametersQtyUnitBrandRemarks
1High-Voltage Metering Cabinet BodyKYN28-12-35kV/HYJL-12Rated voltage 35kV/10kV, rated current 1600A, short-circuit breaking current 40kA, protection class IP54/IP67, 3mm cold-rolled steel plate, electrostatic powder coating, trolley/full-sealed structure1SetKITOZEROptional indoor middle-mounted/outdoor floor-mounted type
2Metering Trolley/Fixed CT/PTMatched with cabinet bodyIntegrated CT/PT/fuse, trolley/fixed type, rated current 1600A, high insulation design1SetKITOZERMatched with cabinet body for easy maintenance
3Current Transformer (CT)LZZBJ9-35-0.2SRated voltage 35kV, ratio 1000/5A, accuracy class 0.2S, rated burden 20VA, insulation class F, cast insulation, partial discharge ≤50pC2SetKITOZERInstalled on Phase A/C, dedicated for metering
4Voltage Transformer (PT)JDZ9-35-0.2Rated voltage 35/√3/0.1/√3kV, accuracy class 0.2, rated burden 25VA, insulation class F, cast insulation, V/V wiring, partial discharge ≤50pC2SetKITOZERDedicated for metering, with fuse protection
5High-Voltage FuseXRNT-35/2ARated voltage 35kV, rated current 2A, breaking current 80kA, protects PT against short circuit3PieceKITOZERInstalled on high-voltage side of PT
6Zinc Oxide ArresterHY5WZ-51/134Rated voltage 51kV, residual voltage 134kV, nominal discharge current 25kA, suppresses overvoltage1GroupKITOZERThree-phase group, installed on bus side
7Multi-Function IoT Electric Energy MeterDSZ862-100V/5A-4GVoltage 100V, current 5A, accuracy class 0.2S, three-phase three-wire, active/reactive/peak-valley/time-of-use metering, 4G/5G/Ethernet communication, local LCD display, prepaid control1PieceKITOZERSealed design for anti-electricity theft, supports remote recharge/tripping
8IoT Data Acquisition TerminalKT-800Supports 4G/5G/Ethernet/RS485, collects energy data, equipment status and environmental data, stores 3-year data, DL/T698/Modbus protocol, connects to IoT platform1SetKITOZERUploads data to cloud for remote operation & maintenance
9Secondary Terminal BlockJH2-6.0Rated voltage 660V, rated current 40A, 48 positions, flame-retardant ABS material, gold-plated contacts2BlockKITOZERSecondary circuit wiring, anti-oxidation
10Five-Prevention Interlock MechanismMatched with cabinet bodyTriple mechanical, electrical and intelligent interlock for misoperation prevention, remote interlock control, matched with cabinet body1SetKITOZERStandard configuration to ensure operation safety
11Intelligent Live Display DeviceDXN-35T/CSRated voltage 35kV, induction type with live indicator light display, interlock/communication function, uploads live status1SetKITOZERThree-phase display, high-voltage side monitoring
12Intelligent Temperature & Humidity ControllerWK-200Temperature range -40℃~+80℃, humidity range 0~100%RH, automatic heating/cooling, 4G communication, remote parameter setting1SetKITOZERInternal cabinet environmental monitoring & control, suitable for harsh environments
13Intelligent Fault Alarm ModuleALM-300Alarms for overvoltage, overcurrent, phase loss, excessive temperature/humidity and door opening, sound-light prompt, 4G alarm upload and SMS push1SetKITOZERReal-time abnormality early warning with remote notification
14Intelligent LocksetSL-100Dynamic encrypted authorization, remote lock/unlock, uploads unlocking records, prevents unauthorized operation1SetKITOZERCabinet door lock control for safety management
15Redundant Secondary Power SupplyAC/DC220V/DC24V-2Input AC220V, output DC24V/AC220V, power 300W, dual power redundant design with automatic switching upon fault1SetKITOZERStable power supply for secondary circuit
16Anti-Electricity Theft Monitoring ModuleEFM-100Monitors abnormal wiring, cover opening and data tampering, real-time alarm and anti-theft event recording1SetKITOZERSafeguards metering against electricity theft

6. Full Product Technical Parameters

6.1 Technical Parameters of High-Voltage Metering Cabinet Body

  • Rated voltage: 6kV/10kV/35kV
  • Rated frequency: 50Hz
  • Rated current: 630A/1250A/1600A
  • Rated short-circuit breaking current: 20kA/31.5kA/40kA
  • Protection class: IP54 (indoor)/IP67 (outdoor)
  • Cabinet material: Cold-rolled steel plate (thickness ≥2.5mm)
  • Insulation class: F
  • Dimension (W×D×H): 800×1200×2200mm (Basic Grade), 800×1500×2300mm (Mid/High-End Grade)
  • Ambient temperature: -40℃~+55℃
  • Altitude: ≤3000m
  • Pollution class: III

6.2 Technical Parameters of Current Transformer (CT)

  • Rated voltage: 6kV/10kV/35kV
  • Ratio: 200/5A~1000/5A (customizable)
  • Accuracy class: 0.2S (dedicated for metering)
  • Rated burden: 10VA/15VA/20VA
  • Insulation class: F
  • Partial discharge: ≤50pC (35kV)
  • Power frequency withstand voltage: 42kV/1min (10kV), 95kV/1min (35kV)
  • Lightning impulse withstand voltage: 75kV (10kV), 185kV (35kV)

6.3 Technical Parameters of Voltage Transformer (PT)

  • Rated voltage: 6/√3/0.1/√3kV, 10/√3/0.1/√3kV, 35/√3/0.1/√3kV
  • Accuracy class: 0.2 (dedicated for metering)
  • Rated burden: 15VA/20VA/25VA
  • Insulation class: F
  • Partial discharge: ≤50pC (35kV)
  • Power frequency withstand voltage: 42kV/1min (10kV), 95kV/1min (35kV)
  • Lightning impulse withstand voltage: 75kV (10kV), 185kV (35kV)
  • Wiring mode: V/V wiring (three-phase three-wire)

6.4 Technical Parameters of Multi-Function Electric Energy Meter

  • Rated voltage: 100V
  • Rated current: 5A
  • Accuracy class: 0.2S
  • Metering mode: Three-phase three-wire
  • Measurable parameters: Active energy, reactive energy, voltage, current, power, power factor, frequency, peak-valley time-of-use metering
  • Communication interface: RS485/Ethernet/4G/5G
  • Operating temperature: -20℃~+60℃
  • Storage capacity: ≥1-year data (Mid-End Grade), ≥3-year data (High-End Grade)

6.5 Technical Parameters of Data Acquisition Terminal

  • Communication protocol: DL/T698, Modbus-RTU/TCP
  • Communication interface: RS485, Ethernet, 4G/5G
  • Power supply: AC220V/DC24V
  • Operating temperature: -40℃~+70℃
  • Data storage: ≥1-year data (Mid-End Grade), ≥3-year data (High-End Grade)
  • Acquisition accuracy: ≤±0.1%

6.6 Technical Parameters of Zinc Oxide Arrester

  • Rated voltage: 17kV (10kV), 51kV (35kV)
  • Continuous operating voltage: 13.6kV (10kV), 40.8kV (35kV)
  • Nominal discharge current: 10kA/20kA/25kA
  • Residual voltage: 45kV/50kV/134kV
  • Current capacity: 100A
  • Insulation resistance: ≥1000MΩ

6.7 Technical Parameters of Temperature & Humidity Controller

  • Temperature measurement range: -40℃~+80℃
  • Humidity measurement range: 0~100%RH
  • Control accuracy: Temperature ±1℃, Humidity ±5%RH
  • Output mode: Relay output (heating/cooling)
  • Communication interface: RS485/4G
  • Power supply: AC220V/DC24V

6.8 Technical Parameters of Fault Alarm Module

  • Monitored parameters: Overvoltage, overcurrent, phase loss, excessive temperature/humidity, door opening, cover opening
  • Alarm mode: Sound-light alarm, dry contact output, 4G SMS push
  • Alarm accuracy: Voltage ±5%, Current ±10%
  • Power supply: DC24V
  • Operating temperature: -20℃~+60℃

7. Full Product Application Scope

7.1 Application Scope of High-Voltage Metering Cabinet Body

  • Power industry: Substations, distribution substations, power grid renovation projects, smart grid construction
  • Industrial sector: Industrial and mining enterprises, chemical, metallurgical, building materials and manufacturing workshop power distribution, energy consumption metering
  • New energy sector: Photovoltaic power stations, wind power bases, energy storage power stations, high-voltage metering for charging pile clusters
  • Infrastructure: Rail transit, data centers, airports, ports, hospitals, schools, commercial complexes
  • Other scenarios: Urban residential quarters, streets, mines, oil fields, temporary electricity consumption, prepaid metering for commercial power usage

7.2 Application Scope of Current/Voltage Transformer (CT/PT)

  • High-voltage electric energy metering: Electric energy settlement, energy consumption statistics and peak-valley time-of-use metering for 10kV/35kV power grids
  • Power grid monitoring: Real-time monitoring of bus voltage and line current to provide data support for dispatching
  • Industrial power distribution: Monitoring and metering of current and voltage for high-voltage motors, transformers and lines in industrial and mining enterprises
  • New energy power stations: High-voltage side current and voltage collection and electric energy metering for photovoltaic/wind power/energy storage booster stations

7.3 Application Scope of Multi-Function Electric Energy Meter

  • High-precision high-voltage electric energy metering: 0.2S high precision for power settlement, energy consumption audit and anti-electricity theft
  • Peak-valley time-of-use metering: Peak-valley electricity price settlement for commercial and industrial users to optimize power consumption costs
  • Prepaid control: Commercial power consumption, temporary electricity consumption and residential quarter power distribution with automatic tripping upon arrears and remote recharge
  • Remote data upload: Smart power grids and IoT platforms to realize remote meter reading and energy consumption monitoring

7.4 Application Scope of Data Acquisition Terminal

  • Data collection and transmission: Collect energy meter, transformer, temperature & humidity and alarm data, upload to background/cloud platform
  • Remote operation & maintenance: Remote parameter setting, data query, fault diagnosis and equipment control
  • IoT platform access: Connect to KITOZER IoT platform to realize big data analysis, energy consumption optimization and equipment health management

7.5 Application Scope of Zinc Oxide Arrester

  • Overvoltage protection: Suppress lightning and switching overvoltage in 10kV/35kV power grids to protect internal equipment insulation of cabinets
  • Substation/distribution substation: Overvoltage protection for busbars, transformers, circuit breakers, transformers and other equipment
  • New energy power stations: High-voltage side overvoltage protection for photovoltaic/wind power/energy storage booster stations

7.6 Application Scope of Temperature & Humidity Controller

  • Internal cabinet environmental control: Monitor temperature and humidity in high-voltage switchgears, metering cabinets and ring main units, automatically heat/cool to prevent moisture and condensation
  • Harsh environment adaptation: Stable environmental control for cabinets in high-temperature, low-temperature, humid and heavily polluted areas

7.7 Application Scope of Fault Alarm Module

  • Equipment abnormality alarm: Real-time alarm for overvoltage, overcurrent, phase loss, excessive temperature/humidity, door opening and cover opening
  • Safety protection: Anti-electricity theft, prevention of unauthorized operation and equipment fault early warning to guarantee stable equipment operation

8. Full Product Advantages

8.1 Core Brand Exclusive Advantages of KITOZER

  • Customized design: Supports customization of voltage class, transformation ratio, dimension and functions to adapt to diverse scenario requirements
  • OEM/ODM service: Provides OEM/ODM processing and customer brand labeling with flexible cooperation modes
  • Strict confidentiality mechanism: Signs confidentiality agreements to protect customer technical drawings, parameters and solutions and eliminate information leakage
  • Spot fast delivery: Core models kept in stock for shipment within 72 hours to shorten project cycles and guarantee construction schedules

8.2 Advantages of High-Voltage Metering Cabinet Body

  • High safety protection: Fully enclosed metal armored structure, IP54/IP67 protection and five-prevention interlock to eliminate misoperation risks
  • High-precision metering: 0.2S grade CT/PT + 0.2S grade electric energy meter with metering error ≤±0.2%, complying with State Grid standards
  • Intelligent operation & maintenance: Integrated temperature & humidity control, fault alarm and remote communication to realize unattended and remote monitoring
  • Durable and reliable: High-quality cold-rolled steel plate with electrostatic powder coating, anti-corrosion and anti-rust, passing 1000-hour neutral salt spray test with service life ≥20 years
  • Strong environmental adaptability: Stable operation under -40℃~+55℃, altitude ≤3000m and pollution class III environments

8.3 Advantages of CT/PT

  • High precision: 0.2S/0.2 grade with accurate metering and minor errors to meet power settlement requirements
  • High insulation: F-class insulation with vacuum casting process, partial discharge ≤50pC and qualified power frequency/lightning impulse withstand voltage
  • Low loss: High-quality iron core material with low exciting current and loss for energy efficiency
  • Long service life: Epoxy resin vacuum casting, moisture-proof, dust-proof and anti-aging with service life ≥25 years

8.4 Advantages of Multi-Function Electric Energy Meter

  • High-precision metering: 0.2S grade supporting peak-valley time-of-use and active/reactive metering with accurate and traceable data
  • Anti-electricity theft design: Sealing device, cover opening alarm and abnormal wiring monitoring to eliminate electricity theft
  • Remote communication: RS485/Ethernet/4G/5G for real-time data upload, remote meter reading and parameter setting
  • Prepaid function: Remote recharge and arrears tripping suitable for commercial and temporary electricity scenarios

8.5 Advantages of Data Acquisition Terminal

  • Multi-protocol compatibility: Supports DL/T698, Modbus and other protocols with strong compatibility for mainstream equipment
  • Stable transmission: 4G/5G/Ethernet with data upload delay ≤3s for stable and lossless transmission
  • Large storage capacity: ≥3-year data storage supporting historical data query and export
  • Remote operation & maintenance: Remote diagnosis, upgrade and control to reduce operation & maintenance costs and improve efficiency

8.6 Advantages of Zinc Oxide Arrester

  • Excellent protection performance: Low residual voltage and large current capacity to effectively suppress overvoltage and protect equipment insulation
  • Sealed and moisture-proof: Fully sealed structure resistant to moisture, dust and aging, suitable for harsh outdoor environments
  • Long service life: High-quality zinc oxide resistance sheets with stable performance and service life ≥20 years

8.7 Advantages of Temperature & Humidity Controller

  • Precise control: Temperature ±1℃, Humidity ±5%RH with automatic heating/cooling to maintain stable internal cabinet environment
  • Wide operating temperature range: -40℃~+80℃ adaptable to high-temperature and low-temperature harsh environments
  • Remote monitoring: RS485/4G communication for remote viewing of temperature & humidity data and parameter setting

8.8 Advantages of Fault Alarm Module

  • Comprehensive monitoring: Full coverage of abnormalities including overvoltage, overcurrent, phase loss, excessive temperature/humidity, door opening and cover opening without blind spots
  • Timely alarm: Sound-light, SMS and platform push with alarm response time ≤1s for rapid early warning
  • Event recording: Stores alarm events with precise timestamps for convenient fault tracing and analysis

9. Full Product Bid Controlling Parameters (Marked with *)

9.1 Bid Controlling Parameters of High-Voltage Metering Cabinet Body

*1. Rated voltage: 10kV/35kV (customizable)

*2. Rated short-circuit breaking current: ≥31.5kA (Mid/High-End Grade)

*3. Protection class: IP54 (indoor)/IP67 (outdoor)

*4. Cabinet material: Cold-rolled steel plate thickness ≥2.5mm, electrostatic powder coating, passing 1000-hour neutral salt spray test

*5. Five-prevention interlock: Dual mechanical and electrical interlock with standard misoperation prevention function

*6. Ambient temperature: -40℃~+55℃

*7. Altitude: ≤3000m

9.2 Bid Controlling Parameters of Current Transformer (CT)

*1. Rated voltage: 10kV/35kV

*2. Accuracy class: 0.2S (dedicated for metering)

*3. Rated burden: ≥15VA

*4. Insulation class: F

*5. Partial discharge: ≤50pC (35kV)

*6. Power frequency withstand voltage: 42kV/1min (10kV), 95kV/1min (35kV)

9.3 Bid Controlling Parameters of Voltage Transformer (PT)

*1. Rated voltage: 10/√3/0.1/√3kV, 35/√3/0.1/√3kV

*2. Accuracy class: 0.2 (dedicated for metering)

*3. Rated burden: ≥20VA

*4. Insulation class: F

*5. Partial discharge: ≤50pC (35kV)

*6. Wiring mode: V/V wiring (three-phase three-wire)

9.4 Bid Controlling Parameters of Multi-Function Electric Energy Meter

*1. Accuracy class: 0.2S

*2. Rated voltage: 100V

*3. Rated current: 5A

*4. Communication interface: RS485 + Ethernet (Mid/High-End Grade)

*5. Metering functions: Active/reactive/peak-valley time-of-use metering

*6. Anti-electricity theft: Sealing + cover opening alarm + abnormal wiring monitoring

9.5 Bid Controlling Parameters of Data Acquisition Terminal

*1. Communication protocols: DL/T698 + Modbus

*2. Communication interface: 4G/5G + Ethernet (High-End Grade)

*3. Data storage: ≥3 years

*4. Acquisition accuracy: ≤±0.1%

*5. Operating temperature: -40℃~+70℃

9.6 Bid Controlling Parameters of Zinc Oxide Arrester

*1. Rated voltage: 17kV (10kV), 51kV (35kV)

*2. Nominal discharge current: ≥20kA

*3. Residual voltage: ≤50kV (10kV), ≤134kV (35kV)

*4. Current capacity: ≥100A

9.7 Bid Controlling Parameters of Temperature & Humidity Controller

*1. Temperature measurement range: -40℃~+80℃

*2. Humidity measurement range: 0~100%RH

*3. Control accuracy: Temperature ±1℃, Humidity ±5%RH

*4. Communication interface: RS485 (Mid-End Grade), 4G (High-End Grade)

9.8 Bid Controlling Parameters of Fault Alarm Module

*1. Monitored parameters: Overvoltage, overcurrent, phase loss, excessive temperature/humidity, door opening, cover opening

*2. Alarm mode: Sound-light + SMS + platform push (High-End Grade)

*3. Alarm response time: ≤1s

10. Full Product Solutions

10.1 10kV High-Voltage Metering Solution for Industrial & Mining Enterprises

10.1.1 Demand Pain Points

  • Industrial and mining enterprises feature numerous high-voltage motors and transformers with high energy consumption, requiring accurate metering, energy consumption statistics and cost accounting
  • Workshops are humid and dusty, leading to easy cabinet moisture, condensation and insulation aging, demanding environmental control and fault early warning
  • Anti-electricity theft and unauthorized operation prevention are required to guarantee metering safety

10.1.2 Solution Configuration

  • Cabinet body: KYN28-12 middle-mounted high-voltage metering cabinet (IP54 protection, five-prevention interlock)
  • CT/PT: LZZBJ9-10-0.2S CT (500/5A) + JDZ9-10-0.2 PT
  • Electric energy meter: DSZ862-100V/5A intelligent electric energy meter (0.2S grade, RS485 communication)
  • Auxiliary equipment: Temperature & humidity controller, fault alarm module, zinc oxide arrester, live display device

10.1.3 Solution Advantages

  • Accurate metering: 0.2S high precision delivers precise energy consumption data to support cost accounting and energy-saving optimization
  • Environment adaptation: Temperature & humidity control prevents moisture and condensation, suitable for humid and dusty workshop environments
  • Safe and reliable: Five-prevention interlock, anti-electricity theft and fault alarm guarantee stable equipment operation
  • Intelligent operation & maintenance: Remote meter reading, data monitoring and fault early warning reduce operation & maintenance costs

10.2 35kV High-Voltage Metering Solution for Photovoltaic Power Stations

10.2.1 Demand Pain Points

  • 35kV booster stations of photovoltaic power stations require accurate metering of power generation and grid-connected power for power grid settlement
  • Outdoor harsh environments with extreme high/low temperature, humidity and frequent lightning demand high protection and overvoltage protection for equipment
  • Remote monitoring and operation & maintenance are required to realize unattended operation and cut labor costs

10.2.2 Solution Configuration

  • Cabinet body: KYN28-12-35kV middle-mounted high-voltage metering cabinet (IP54 protection, fully sealed structure)
  • CT/PT: LZZBJ9-35-0.2S CT (1000/5A) + JDZ9-35-0.2 PT (partial discharge ≤50pC)
  • Electric energy meter: DSZ862-100V/5A-4G IoT electric energy meter (0.2S grade, 4G communication, prepaid function)
  • Auxiliary equipment: 4G data acquisition terminal, intelligent temperature & humidity controller, fault alarm module, HY5WZ-51/134 arrester, intelligent lockset

10.2.3 Solution Advantages

  • High-precision metering: 0.2S grade accurately measures power generation and grid-connected power to guarantee fair settlement
  • Harsh environment adaptation: IP54 protection, temperature & humidity control and overvoltage protection adapt to outdoor extreme temperature and lightning environments
  • Intelligent operation & maintenance: Connects to IoT platform for remote monitoring, meter reading and fault early warning to realize unattended operation
  • Anti-electricity theft: Intelligent lock, cover opening alarm and abnormality monitoring safeguard metering data security

10.3 10kV Prepaid Metering Solution for Urban Residential Quarters

10.3.1 Demand Pain Points

  • Commercial and residential power consumption in residential quarters requires prepaid control with automatic tripping upon arrears and remote recharge
  • Outdoor installation with limited space demands miniaturized fully sealed equipment with IP67 protection
  • Anti-electricity theft and anti-damage functions are needed to guarantee power safety and electricity fee recovery

10.3.2 Solution Configuration

  • Cabinet body: HYJL-12 floor-mounted metering box (IP67 protection, fully sealed miniaturized structure)
  • CT/PT: LMK-10-0.2S CT (200/5A) + JDZJ-10-0.2 PT
  • Electric energy meter: DSZ862-100V/5A-4G prepaid electric energy meter (0.2S grade, 4G remote recharge)
  • Auxiliary equipment: 4G data acquisition terminal, fault alarm module, zinc oxide arrester, intelligent lockset

10.3.3 Solution Advantages

  • Prepaid management: Remote recharge and arrears tripping guarantee electricity fee recovery and eliminate bad debt risks
  • Outdoor adaptation: IP67 fully sealed design resistant to moisture, dust and damage, suitable for outdoor installation in residential quarters
  • Miniaturization: Compact size with flexible installation to save space
  • Anti-electricity theft: Intelligent lock, cover opening alarm and abnormality monitoring eliminate electricity theft incidents

11. Full Product Application Cases

11.1 10kV Chemical Enterprise High-Voltage Metering Project in Guangdong

  • Project scale: 10kV power distribution system with 5 sets of KYN28-12 high-voltage metering cabinets for metering workshop high-voltage motors and transformers
  • Configuration scheme: Mid-End Grade KYN28-12 cabinet body + 0.2S grade CT/PT + intelligent electric energy meter + temperature & humidity controller + fault alarm module
  • Project effects:
    1. Metering accuracy reaches 0.18%, complying with State Grid standards, with precise energy consumption data cutting annual costs by approximately RMB 500,000
    2. Stable temperature & humidity control eliminates internal cabinet condensation and insulation aging, reducing equipment failure rate by 80%
    3. Remote meter reading and fault early warning cut operation & maintenance staff by 60% and operation & maintenance costs by 50%

11.2 35kV Photovoltaic Power Station High-Voltage Metering Project in Inner Mongolia

  • Project scale: 35kV booster station with 2 sets of KYN28-12-35kV high-voltage metering cabinets for metering power generation and grid-connected power
  • Configuration scheme: High-End Grade 35kV cabinet body + low-partial-discharge 0.2S grade CT/PT + IoT electric energy meter + 4G acquisition terminal + intelligent lockset
  • Project effects:
    1. Metering accuracy hits 0.19%, precise settlement of power generation and grid-connected power reduces annual settlement error losses by approximately RMB 300,000
    2. Adapts to outdoor extreme environments of -30℃~+45℃ with stable equipment operation and zero fault shutdowns
    3. Connects to KITOZER IoT platform for remote monitoring and operation & maintenance, realizing unattended operation and cutting annual labor costs by approximately RMB 200,000

11.3 10kV Commercial Residential Quarter Prepaid Metering Project in Shenzhen

  • Project scale: 10kV power distribution system with 8 sets of HYJL-12 floor-mounted metering boxes for commercial and temporary power consumption in the quarter
  • Configuration scheme: High-End Grade floor-mounted metering box + 0.2S grade CT/PT + 4G prepaid electric energy meter + intelligent lockset
  • Project effects:
    1. Prepaid management achieves 100% electricity fee recovery with zero bad debt, solving arrears issues
    2. IP67 protection delivers 3 years of damage-free outdoor installation without electricity theft incidents, ensuring reliable power safety
    3. Remote recharge and alarm notifications improve user experience and boost operation & maintenance efficiency by 70%

12. Full Product Faults and Maintenance Specifications

12.1 Common Faults and Troubleshooting Methods

12.1.1 Excessive Metering Error

  • Fault causes: Degraded CT/PT accuracy, loose secondary circuit wiring, faulty electric energy meter, unbalanced load
  • Troubleshooting steps: a. Calibrate CT/PT; replace with 0.2S grade CT/PT if accuracy fails to meet standards b. Inspect secondary circuit wiring and tighten terminals to eliminate looseness and oxidation c. Calibrate electric energy meter; replace with same-model 0.2S grade meter upon failure d. Adjust loads to maintain three-phase load balance

12.1.2 Internal Cabinet Condensation and Humidity

  • Fault causes: High ambient humidity, faulty temperature & humidity controller, damaged heating/cooling components, poor cabinet sealing
  • Troubleshooting steps: a. Inspect temperature & humidity controller; replace upon failure and set reasonable parameters (temperature 10~30℃, humidity 40%~60%RH) b. Inspect heating/cooling components and replace damaged units to ensure normal operation c. Inspect cabinet sealing, repair sealing strips and seal gaps to block moisture ingress

12.1.3 Frequent Equipment Alarms

  • Fault causes: Overvoltage/overcurrent, phase loss, excessive temperature/humidity, door/cover opening, wiring errors
  • Troubleshooting steps: a. Inspect primary circuit voltage and current; identify overvoltage/overcurrent causes (overloaded load, power grid fluctuation), adjust loads or install voltage stabilizers b. Inspect three-phase power supply; locate phase loss causes (blown fuse, broken wire), replace fuses and repair circuits c. Check temperature and humidity, adjust controller parameters to eliminate condensation and high temperature issues d. Ensure cabinet doors and meter covers are fully closed and intelligent locks are fastened to prevent accidental opening

12.1.4 Remote Communication Disconnection

  • Fault causes: Faulty communication module, weak network signal, loose wiring, platform failure
  • Troubleshooting steps: a. Inspect communication module (4G/Ethernet); replace faulty modules and restart the module b. Check network signal strength; reposition antennas to ensure signal strength ≥3 grids c. Inspect communication wiring and tighten terminals to eliminate looseness and oxidation d. Contact platform operation & maintenance personnel to troubleshoot platform faults and restore connectivity

12.2 Maintenance Specifications

12.2.1 Daily Maintenance (Daily)

  • Inspect cabinet appearance: No deformation or corrosion with intact sealing and door locks
  • Inspect indicator lights: Live display and alarm indicators function normally without abnormal alarms
  • Check temperature & humidity: Internal cabinet temperature and humidity stay within normal ranges (10~30℃, 40%~60%RH)
  • Remote inspection: View equipment operating data, metering data and alarm records via IoT platform for abnormalities

12.2.2 Monthly Maintenance (Monthly)

  • Cabinet cleaning: Remove internal dust and debris to prevent short circuits caused by dust accumulation
  • Wiring inspection: Tighten primary and secondary circuit wiring with no looseness, oxidation or heating signs
  • Instrument calibration: Verify normal display of electric energy meter and data acquisition terminal with accurate data and no abnormal errors
  • Function testing: Test temperature & humidity control, fault alarm, communication and intelligent lock functions for normal operation

12.2.3 Annual Maintenance (Yearly)

  • Insulation test: Test insulation resistance of CT/PT, cabinet body and secondary circuit, which shall be ≥1000MΩ; conduct treatment if unqualified
  • Accuracy calibration: Entrust third-party institutions to calibrate CT/PT and electric energy meters; replace units failing accuracy standards
  • Component inspection: Inspect arresters, fuses, five-prevention interlocks and heating/cooling components; replace aged/damaged parts
  • Software upgrade: Upgrade firmware of data acquisition terminal and IoT modules to fix vulnerabilities and optimize functions

12.2.4 Maintenance Precautions

  • Safety first: Disconnect primary and secondary power supply, conduct live test and earthing before maintenance; strictly follow five-prevention interlock rules to avoid electric shock and misoperation
  • Professional operation: Maintenance personnel must hold valid certificates and be familiar with equipment structure, principles and operation procedures
  • Record filing: Document all maintenance and fault handling work for filing to establish complete equipment maintenance archives
  • Spare parts reserve: Stock common spare parts (CT/PT, electric energy meter, fuse, communication module) for rapid replacement to reduce downtime

13. Factory Strength and After-Sales Service

13.1 Factory Strength

  • Enterprise background: Guangzhou Lai’an Intelligent System Development Co., Ltd., a core manufacturer of KITOZER brand with 15 years of deep engagement in power distribution industry, integrating R&D, production, sales and service of high-voltage power distribution, metering and monitoring equipment
  • Production scale: Modern production base in Panyu, Guangzhou with 10,000㎡ factory area, 5 production lines and annual output of 10,000 high-voltage metering cabinets/switchgears to meet mass order demands
  • Technical R&D: 30-person R&D team including 10 senior engineers with 20 patents (5 invention patents), focusing on R&D of high-voltage metering, intelligent power distribution and IoT technologies for continuous technological innovation
  • Production technology: Adopts advanced processes including laser cutting, numerical control bending, electrostatic powder coating and vacuum casting with automated core procedures for high precision and consistent stable product quality
  • Quality control: Strictly follows ISO9001 quality management system and ISO14001 environmental management system certification; full-process control of raw material procurement, production and factory inspection. Every unit undergoes 10 strict tests including insulation test, withstand voltage test, accuracy calibration and function test before delivery to guarantee 100% qualification
  • Qualification certifications: Possesses high-voltage electrical production license, type test report, 3C certification, CE certification and State Grid supplier qualification; products comply with national, industrial and international standards for bidding in large domestic and overseas projects

13.2 After-Sales Service

13.2.1 Service Commitment

  • Warranty period: 3-year full machine warranty, 5-year warranty for core components (CT/PT, electric energy meter); free repair and component replacement within warranty period with no labor or travel fees charged
  • Response time: 7×24-hour technical support with fault response within 2 hours; on-site service within 4 hours in Guangdong Province and 24 hours nationwide for rapid issue resolution
  • Lifetime service: Lifelong technical support and maintenance after warranty expiration with only component cost charged; free software upgrade and technical training provided

13.2.2 Service System

  • National service network: Five regional service centers in South China, East China, North China, Southwest China and Northwest China, 30 provincial service stations and 100 professional service engineers covering the whole country for nearby service
  • Service contents: a. Pre-sales service: Free scheme design, technical consultation, on-site survey and parameter customization to deliver optimal solutions b. In-sales service: Free installation guidance, commissioning and technical training to teach users equipment operation, maintenance and troubleshooting c. After-sales service: Fault repair, regular inspection, spare parts supply, software upgrade, technical training and energy consumption optimization suggestions
  • Service process: a. User fault report: Submit fault information via phone, WeChat or platform; customer service records and assigns orders b. Technical response: Engineers contact users within 2 hours for remote diagnosis and guide simple troubleshooting c. On-site service: If remote resolution fails, nearby engineers arrive within 24 hours for repair, commissioning and testing to restore equipment operation d. Acceptance and filing: User acceptance, service form signing, fault cause and handling process recording for filing

13.2.3 Technical Training

  • Free operation, maintenance and troubleshooting training combining online and offline modes with integrated theory and practical operation to ensure user staff master equipment operation, maintenance and fault handling skills proficiently
  • Provide training manuals, videos and drawings for users to review and study at any time

14. Conclusion

As the core product under Guangzhou Lai’an Intelligent System Development Co., Ltd., the KITOZER high-voltage metering cabinet delivers full-process high-voltage electric energy metering solutions widely applied in power, industrial, new energy and infrastructure sectors, supported by five core strengths: accurate metering, safe reliability, intelligent operation & maintenance, strong environmental adaptability and customized services.

The company boasts robust R&D capacity, advanced production technology, strict quality control and comprehensive after-sales service, delivering stable, reliable products recognized by customers at home and abroad. Moving forward, KITOZER will continue to deepen R&D in high-voltage metering, intelligent power distribution and IoT technologies, continuously innovate, optimize product performance and upgrade service quality to provide safer, more accurate, intelligent and efficient high-voltage metering equipment and solutions for customers. We will support smart grid construction, new energy development and industrial energy conservation and consumption reduction, working hand in hand with customers for win-win results and a promising future.

15. SEO Optimization (Keywords & Tag System)

15.1 Core Keywords

  • Core primary keywords: High-voltage metering cabinet, KITOZER high-voltage metering cabinet, 10kV high-voltage metering cabinet, 35kV high-voltage metering cabinet
  • High-conversion long-tail keywords: High-voltage metering cabinet for industrial & mining enterprises, high-voltage metering cabinet for photovoltaic power stations, prepaid metering cabinet for residential quarters, intelligent high-voltage metering cabinet, IoT high-voltage metering cabinet
  • Industry traffic keywords: High-voltage power distribution equipment, electric energy metering cabinet, CT/PT metering cabinet, high-voltage switchgear, intelligent metering device
  • Brand exclusive keywords: KITOZER, Lai’an Intelligence, Guangzhou Lai’an, KITOZER metering cabinet, Lai’an high-voltage metering cabinet
  • Drop-down/related search keywords: High-voltage metering cabinet price, high-voltage metering cabinet manufacturer, high-voltage metering cabinet configuration, high-voltage metering cabinet schematic diagram, high-voltage metering cabinet maintenance

15.2 SEO Optimization Tag System

15.2.1 Core Page Optimization Tag

  • Core tag: High-Voltage Metering Cabinet _ KITOZER High-Voltage Metering Cabinet _ 10kV/35kV Intelligent Metering Cabinet Manufacturer

15.2.2 Title Tag

  • KITOZER High-Voltage Metering Cabinet _ 10kV/35kV Intelligent Electric Energy Metering Cabinet _ Dedicated for Industry, Photovoltaic and Residential Quarters

15.2.3 Meta Keywords

  • High-voltage metering cabinet, KITOZER high-voltage metering cabinet, 10kV high-voltage metering cabinet, 35kV high-voltage metering cabinet, intelligent metering cabinet, prepaid metering cabinet, industrial & mining enterprise metering cabinet, photovoltaic power station metering cabinet, high-voltage power distribution equipment, Lai’an Intelligence

15.2.4 Meta Description

  • KITOZER high-voltage metering cabinet manufacturer provides 10kV/35kV intelligent electric energy metering cabinet solutions applicable to industrial & mining enterprises, photovoltaic power stations and residential prepaid scenarios. Featuring 0.2S high precision, five-prevention interlock and IoT remote operation & maintenance, customized OEM/ODM processing and spot supply available with 3-year warranty.

15.2.5 H1 Tag

  • KITOZER High-Voltage Metering Cabinet _ Dedicated 10kV/35kV Intelligent Electric Energy Metering Equipment

15.2.6 H2 Tags

  • System Overview, System Composition, System Classification, System Schematic Diagram, System Configuration List, Product Technical Parameters, Product Application Scope, Product Advantages, Bid Controlling Parameters, Solutions, Application Cases, Faults and Maintenance Specifications, Factory Strength and After-Sales Service, Conclusion

15.2.7 Internal Link Optimization Tags (Natural Embedded Anchor Text)

  • Core anchor text: High-voltage metering cabinet, KITOZER high-voltage metering cabinet, 10kV high-voltage metering cabinet
  • Long-tail anchor text: Intelligent high-voltage metering cabinet, high-voltage metering cabinet for photovoltaic power stations, prepaid metering cabinet
  • Associated anchor text: High-voltage power distribution equipment, electric energy metering cabinet, CT/PT transformer, high-voltage switchgear
Shopping Cart