Table of Contents
Toggle1. System Overview
The KITOZER integrated computer room system is an all-in-one solution built on the full range of KITOZER computer room equipment, integrating overall computer room construction, environmental monitoring, fire linkage and intelligent power distribution management. Compliant with national computer room construction standards and industry specifications, it centers on high reliability, stability and intelligence. It integrates core modules including cabinet systems, power supply and distribution systems, cooling systems, monitoring systems and fire protection systems to realize centralized management, intelligent linkage and efficient operation & maintenance of computer room infrastructure.
The KITOZER integrated computer room system adapts to computer room scenarios of government & enterprises, finance, education, medical care, industry and more. It meets construction and upgrading demands from small computer rooms to large data centers. Adopting modular design, customized configuration and standardized construction, it cuts computer room construction and operation costs, ensures 7×24-hour uninterrupted stable operation, and provides a safe and reliable physical environment for data storage, network transmission and business operation.
2. System Composition
The KITOZER integrated computer room system consists of four core subsystems and supporting auxiliary systems. All subsystems operate independently yet coordinate with each other to form a complete infrastructure ecosystem for computer rooms:
- Integrated Computer Room Construction Subsystem: Includes cabinet systems, partition & decoration systems, cabling systems, earthing & lightning protection systems, lighting systems, etc., forming the physical carrier and basic environment of the computer room.
- Environmental Monitoring Integrated Subsystem: Covers environmental monitoring (temperature & humidity, water leakage, gas), power monitoring (UPS, precision air conditioners, power distribution cabinets), security monitoring (video, access control, infrared), network monitoring and other modules, enabling real-time status perception and data collection of computer room operation.
- Fire Protection Linkage Integrated Subsystem: Composed of fire detection modules, gas fire suppression modules, smoke exhaust & ventilation modules, emergency broadcast modules and fire alarm modules, it realizes automatic fire alarm, intelligent fire suppression and linkage emergency disposal.
- Intelligent Power Distribution Integrated Subsystem: Contains UPS uninterruptible power supplies, precision power distribution cabinets, intelligent PDUs, lightning arresters, backup generators, etc., delivering stable, continuous and intelligent power supply and distribution.
- Supporting Auxiliary Systems: Operation & maintenance management platform, cable management system, marking system, emergency power supply system, etc., ensuring efficient system operation and emergency response.
3. System Classification
Based on computer room scale, load demand, intelligence level and application scenarios, the KITOZER integrated computer room system is divided into three categories: Basic (Entry-level), Standard (Mid-tier) and High-end (Premium), matching different budgets and functional requirements.
3.1 Basic (Entry-level)
Suitable for small computer rooms (Area ≤50㎡, Server Cabinets ≤10 units). It satisfies basic power supply, cooling, monitoring and fire protection needs with high cost performance and simple deployment. Target scenarios include micro and small enterprises, branch offices, small office computer rooms, etc.
3.2 Standard (Mid-tier)
Suitable for medium-sized computer rooms (Area 50–200㎡, Server Cabinets 10–50 units). It is equipped with complete environmental monitoring, intelligent power distribution and linked fire protection functions, supporting remote management and data traceability. Target scenarios include medium-sized enterprises, educational institutions, hospitals, government departments, etc.
3.3 High-end (Premium)
Suitable for large computer rooms / data centers (Area ≥200㎡, Server Cabinets ≥50 units). It adopts modular redundant design, AI intelligent operation & maintenance, liquid cooling heat dissipation, dual-circuit power supply and other high-end technologies, supporting 7×24-hour unattended operation. Target scenarios include large enterprises, financial institutions, internet companies, cloud computing centers, etc.
4. System Schematic Diagrams
4.1 Overall Architecture Schematic
The KITOZER integrated computer room system adopts a four-layer architecture: Bottom Equipment Layer, Data Transmission Layer, Platform Control Layer and Application Management Layer, with interconnection and data sharing across all layers:
- Equipment Layer: Terminal devices including cabinets, UPS, precision air conditioners, temperature & humidity sensors, water leakage sensors, fire detectors, intelligent PDUs, responsible for data collection and instruction execution.
- Transmission Layer: Realizes stable data transmission between the equipment layer and control layer via industrial Ethernet, RS485, IoT gateways, etc.
- Control Layer: Environmental monitoring hosts, fire linkage controllers, power distribution management units, operation & maintenance servers, responsible for data processing, logical operation and linkage control.
- Application Layer: Operation & maintenance management platform, remote monitoring terminals, mobile APP, large-screen display systems, providing visualized management, remote operation, alarm reminders, data analysis and other functions.
4.2 Subsystem Linkage Schematic
- Environmental Monitoring & Power Distribution Linkage: When abnormal voltage or current overload is detected, the monitoring system immediately triggers the protection mechanism of the power distribution cabinet and links the UPS to switch power supply mode to ensure zero downtime for equipment.
- Environmental Monitoring & Cooling Linkage: When computer room temperature and humidity exceed set thresholds, the monitoring system automatically adjusts the operating power of precision air conditioners or starts/stops backup air conditioners to maintain constant temperature and humidity.
- Environmental Monitoring & Fire Protection Linkage: When smoke or high-temperature signals are detected by fire detectors, fire alarms are triggered instantly. The system links to shut down air conditioners, cut off non-fire-fighting power supply, activate gas fire suppression devices, and push alarm information to operation & maintenance terminals simultaneously.
5. Complete System Configuration List (Entry/Mid/Premium Tiers)
5.1 Basic (Entry-level) Configuration List
表格
| No. | Product Name | Model | Technical Parameters | Qty | Unit | Brand | Remarks |
|---|---|---|---|---|---|---|---|
| 1 | Network Cabinet | KITOZER-NC6042 | Size: 600×1000×2000mm (42U); Material: SPCC cold-rolled steel; Load capacity ≥800kg; IP20 protection; Equipped with shelf, cable manager, door lock | 10 | Set | KITOZER | Cold-rolled steel with electrostatic plastic spraying |
| 2 | UPS Uninterruptible Power Supply | KITOZER-UPS-3KVA | Rated capacity: 3KVA/2.4KW; Input voltage: 220V±15%; Output voltage: 220V±2%; Backup time ≥30min; Overload capacity: 125% load for 10min | 1 | Set | KITOZER | Online type with built-in battery |
| 3 | Precision Air Conditioner | KITOZER-AC-5KW | Cooling capacity: 5KW; Temp & humidity control: 18–28℃±1℃, 40–60%RH±5%; Top air supply; Power ≤2.5KW | 1 | Set | KITOZER | Air-cooled fixed frequency model |
| 4 | Environmental Monitoring Host | KITOZER-MON-B1 | Dual-core 1.5GHz processor; 2GB memory; 16GB storage; Interfaces: 4×RS485, 2×Ethernet, 8×DI, 4×DO; Supports up to 20 monitoring points | 1 | Set | KITOZER | Embedded Linux system |
| 5 | Temperature & Humidity Sensor | KITOZER-SEN-TH1 | Measuring range: -20℃~60℃, 0–100%RH; Accuracy: ±0.5℃, ±3%RH; RS485 output; DC12V power supply | 5 | Unit | KITOZER | Wall-mounted indoor type |
| 6 | Water Leakage Sensor | KITOZER-SEN-WL1 | Sensing cable length: 5m; Detection accuracy ≤1mm; Switch signal output; DC12V power supply; IP65 protection | 2 | Set | KITOZER | Positioning type (cable + controller included) |
| 7 | Intelligent PDU | KITOZER-PDU-8C | Input: 16A; 8 standard sockets; Max power ≤4000W; Overcurrent & lightning protection, remote switch control | 5 | Unit | KITOZER | Basic version without power metering |
| 8 | Smoke Detector | KITOZER-FIRE-S1 | Photoelectric detection; 3-level adjustable sensitivity; Switch signal output; DC24V power supply; IP30 protection | 4 | Unit | KITOZER | Ceiling-mounted smoke detector |
| 9 | Gas Fire Suppression Device | KITOZER-FIRE-G1 | HFC-227ea fire suppressant; Filling weight: 40kg; Protect volume ≤100m³; Auto/manual/emergency startup; Spraying time ≤10s | 1 | Set | KITOZER | Cabinet non-pipe type |
| 10 | Power Distribution Cabinet | KITOZER-PDB-B1 | Input: 220V/380V; 12 output circuits; Equipped with air switch, lightning arrester, voltmeter, ammeter; IP30 protection | 1 | Set | KITOZER | Wall-mounted basic power distribution cabinet |
5.2 Standard (Mid-tier) Configuration List
表格
| No. | Product Name | Model | Technical Parameters | Qty | Unit | Brand | Remarks |
|---|---|---|---|---|---|---|---|
| 1 | Server Cabinet | KITOZER-SC6042 | Size: 600×1100×2000mm (42U); Premium cold-rolled steel; Load capacity ≥1200kg; IP20 protection; Front/rear mesh doors, adjustable shelves, cable racks, cooling fans | 30 | Set | KITOZER | Anti-static, detachable side panels |
| 2 | Modular UPS | KITOZER-UPS-20KVA | Rated capacity: 20KVA/16KW; Input: 380V±20%; Output: 380V±1%; Backup time ≥60min; N+1 redundancy; Efficiency ≥95% | 2 | Set | KITOZER | Online modular type, expandable capacity |
| 3 | Row-level Precision Air Conditioner | KITOZER-AC-12KW | Cooling capacity: 12KW; Temp & humidity control: 18–28℃±0.5℃, 40–60%RH±3%; Horizontal air supply; EC energy-saving fan, low noise | 4 | Set | KITOZER | Air-cooled variable frequency, redundant backup |
| 4 | Environmental Monitoring Host | KITOZER-MON-M1 | Quad-core 2.0GHz processor; 4GB memory; 64GB storage; Interfaces: 8×RS485, 4×Ethernet, 16×DI, 8×DO, 1×HDMI; Supports up to 50 monitoring points & video access | 1 | Set | KITOZER | Industrial grade, remote operation support |
| 5 | Temperature & Humidity Sensor | KITOZER-SEN-TH2 | Measuring range: -30℃~70℃, 0–100%RH; Accuracy: ±0.3℃, ±2%RH; RS485/Modbus output; DC12–24V power supply; IP65 protection | 15 | Unit | KITOZER | Wall/ceiling dual mounting |
| 6 | Water Leakage Monitoring System | KITOZER-SEN-WL2 | Sensing cable length: 10m; Positioning accuracy ≤0.5m; RS485 output; DC24V power supply; IP67 protection (controller + cable + terminator included) | 5 | Set | KITOZER | High-precision positioning alarm |
| 7 | Intelligent Metering PDU | KITOZER-PDU-16M | Input: 32A; 16 standard sockets; Max power ≤8000W; Real-time voltage/current/power/energy monitoring, remote switch, overload & lightning protection | 15 | Unit | KITOZER | Metering version with Modbus communication |
| 8 | HD Network Camera | KITOZER-CAM-HD1 | 1080P resolution; 4mm lens; IR distance ≥30m; H.265 encoding; TF card/NVR storage support; IP66 protection | 8 | Unit | KITOZER | Dome type, waterproof & dustproof |
| 9 | Access Control Controller | KITOZER-ACC-M1 | IC card/password reader; Supports ≥1000 user cards; Card/password/remote unlocking; TCP/IP interface; DC12V power supply (reader + controller + electromagnetic lock included) | 3 | Set | KITOZER | Networked type with record query |
| 10 | Fire Alarm Controller | KITOZER-FIRE-C1 | 2 loops; Max 128 devices per loop; LCD display; Acoustic & light alarm; RS485 interface; DC24V power supply (controller + detectors + modules included) | 1 | Set | KITOZER | Linkage bus type |
| 11 | HFC-227ea Fire Suppression System | KITOZER-FIRE-G2 | HFC-227ea fire suppressant; Filling weight: 80kg; Protect volume ≤200m³; Auto/manual/emergency startup; Spraying time ≤8s (steel cylinder + nozzles + pipes + starter included) | 2 | Set | KITOZER | Pipe network linkage type |
| 12 | Precision Power Distribution Cabinet | KITOZER-PDB-M1 | Input: 380V±10%; 24 output circuits; Intelligent circuit breaker, lightning arrester, multi-function energy meter, surge protector; Overvoltage/undervoltage/overload/leakage protection; IP40 protection | 2 | Set | KITOZER | Floor-standing intelligent monitoring type |
| 13 | Lightning Arrester | KITOZER-SPD-M1 | Class III power lightning protection; Nominal voltage 220/380V; Max discharge current 60KA; Response time ≤25ns; L-N / L-PE / N-PE protection modes | 4 | Unit | KITOZER | Modular power surge protection device |
5.3 High-end (Premium) Configuration List
表格
| No. | Product Name | Model | Technical Parameters | Qty | Unit | Brand | Remarks |
|---|---|---|---|---|---|---|---|
| 1 | Micro-module Cabinet | KITOZER-MC6042 | Size: 600×1200×2200mm (42U); High-strength cold-rolled steel; Load capacity ≥1500kg; IP54 protection; Cold aisle containment, integrated access control, LED lighting, cooling fans, smoke detector | 80 | Set | KITOZER | Modular cold aisle integrated design |
| 2 | High-frequency Modular UPS | KITOZER-UPS-60KVA | Rated capacity: 60KVA/48KW; Input: 380V±30%; Output: 380V±0.5%; Backup time ≥120min; N+2 redundancy, dual bus power supply; Efficiency ≥98% | 4 | Set | KITOZER | High-frequency online type, parallel connection support |
| 3 | Row-level Liquid Cooling Air Conditioner | KITOZER-AC-30KW | Cooling capacity: 30KW; Temp & humidity control: 18–28℃±0.3℃, 40–60%RH±2%; Cold plate liquid cooling; Supply/return water temp: 24℃/32℃; PUE ≤1.15 | 12 | Set | KITOZER | AI intelligent adjustment, redundant design |
| 4 | Environmental Monitoring Platform | KITOZER-MON-H1 | 8-core 3.0GHz Intel Xeon processor; 16GB DDR4 memory; 512GB SSD + 4TB HDD storage; Interfaces: 16×RS485, 8×Gigabit Ethernet, 32×DI, 16×DO, 4×HDMI; Supports up to 200 monitoring points, AI analysis, video linkage & data mining | 1 | Set | KITOZER | Distributed server + software platform |
| 5 | High-precision Temperature & Humidity Sensor | KITOZER-SEN-TH3 | Measuring range: -40℃~80℃, 0–100%RH; Accuracy: ±0.1℃, ±1%RH; RS485/Modbus/TCP output; DC24V power supply; IP67 industrial anti-interference grade | 40 | Unit | KITOZER | Corrosion-resistant high-precision industrial model |
| 6 | Distributed Fiber Optic Temperature Measurement System | KITOZER-SEN-FT1 | Measuring range: -50℃~300℃; Accuracy ±0.5℃; Sampling frequency 1Hz; 50m fiber cable; Positioning accuracy ≤1m; TCP/IP output, real-time cabinet & cable temperature monitoring | 6 | Set | KITOZER | Distributed fiber early fire warning system |
| 7 | Intelligent Remote PDU | KITOZER-PDU-24H | Input: 63A three-phase 380V; 24 standard sockets; Max power ≤16000W; Real-time voltage/current/power/energy/harmonic monitoring, remote switch, timing control, surge suppression; SNMP/Modbus/TCP; IP54 protection | 40 | Unit | KITOZER | Remote operation & data upload supported |
| 8 | AI Intelligent Camera | KITOZER-CAM-AI1 | 4K resolution; 6mm lens; IR distance ≥50m; H.265+ encoding; AI face recognition, behavior analysis, abnormal alarm; NAS/cloud storage support; IP67 protection | 20 | Unit | KITOZER | Gun type intelligent analysis camera, waterproof & dustproof |
| 9 | Biometric Access Control | KITOZER-ACC-H1 | Fingerprint + face + IC card multi-recognition; Supports ≥5000 user cards/fingerprints; Multi-factor verification; TCP/IP interface; DC24V power supply (host + reader + electromagnetic lock + exit button included) | 8 | Set | KITOZER | High-security biometric identification |
| 10 | Intelligent Fire Alarm System | KITOZER-FIRE-H1 | 8 expandable loops; Max 256 devices per loop; 10-inch touch LCD; Acoustic/light/voice/APP push alarm; TCP/IP interface; DC24V power supply (controller + intelligent detectors + IO modules + emergency broadcast included) | 2 | Set | KITOZER | IoT intelligent linkage fire alarm system |
| 11 | IG541 Inert Gas Fire Suppression System | KITOZER-FIRE-G3 | IG541 fire suppressant (52% nitrogen + 40% argon + 8% CO₂); Filling pressure 15MPa (20℃); Protect volume ≤500m³; Auto/manual/emergency startup; Spraying time ≤60s, residue-free & equipment-friendly | 4 | Set | KITOZER | Pipe network eco-friendly type for large data centers |
| 12 | Intelligent Precision Power Distribution Cabinet | KITOZER-PDB-H1 | Input: 380V±15%; 48 output circuits; Intelligent molded case circuit breaker, Class III lightning arrester, multi-function harmonic energy meter, insulation monitoring device; Overvoltage/undervoltage/overload/leakage/harmonic monitoring; IP54 protection, remote data upload | 4 | Set | KITOZER | Floor-standing harmonic governance intelligent power distribution cabinet |
| 13 | Backup Diesel Generator | KITOZER-GEN-200KW | Rated power: 200KW; Output voltage 380V 50Hz; Startup time ≤10s; 0# diesel fuel; 500L fuel tank, continuous operation ≥8h; Auto startup & switching, fault alarm | 1 | Set | KITOZER | Silent emergency backup power supply |
| 14 | Integrated Operation & Maintenance Platform | KITOZER-OPS-H1 | Functions: equipment management, alarm management, work order management, data analysis, report generation, remote operation; Multi-terminal access (PC/mobile/tablet), multi-computer room centralized management, authority control, log audit & data backup; Local + cloud dual deployment | 1 | Set | KITOZER | AI intelligent full-lifecycle O&M platform |
6. Full Product Technical Specifications
6.1 Cabinet Series
6.1.1 Network Cabinet (KITOZER-NC6042)
- Overall dimension: 600(W)×1000(D)×2000(H)mm, standard 42U height
- Material: 1.2mm SPCC cold-rolled steel frame, 1.0mm door panels
- Load capacity: Static load ≥800kg, dynamic load ≥500kg
- Protection grade: IP20 (finger contact & dust prevention)
- Surface treatment: Anti-corrosion electrostatic plastic spraying, off-white
- Standard accessories: Front/rear mesh doors (air permeability ≥70%), 1 fixed shelf, 1 cable manager, 4 cooling fans, door lock, foot wheels & support feet
6.1.2 Server Cabinet (KITOZER-SC6042)
- Overall dimension: 600(W)×1100(D)×2000(H)mm, standard 42U height
- Material: 1.5mm premium cold-rolled steel frame, 1.2mm door panels
- Load capacity: Static load ≥1200kg, dynamic load ≥800kg
- Protection grade: IP20
- Surface treatment: Black anti-static plastic spraying, anti-aging
- Standard accessories: Front/rear mesh doors, 2 adjustable shelves, 2 cable racks, 6 cooling fans, detachable side panels, door lock, load-bearing feet
6.1.3 Micro-module Cabinet (KITOZER-MC6042)
- Overall dimension: 600(W)×1200(D)×2200(H)mm, standard 42U height
- Material: 2.0mm high-strength cold-rolled steel frame, 1.5mm door panels
- Load capacity: Static load ≥1500kg, dynamic load ≥1200kg
- Protection grade: IP54 (dust & splash water resistance)
- Surface treatment: Custom anti-corrosion & anti-static plastic spraying
- Standard accessories: Cold aisle containment structure, intelligent access control, LED smart lighting, 4 high-speed cooling fans, top-mounted smoke detector, integrated cable management, load-bearing base
6.2 UPS Uninterruptible Power Supply Series
6.2.1 Online UPS (KITOZER-UPS-3KVA)
- Rated capacity: 3KVA/2.4KW
- Input voltage: 220V±15%, 50Hz±5%
- Output voltage: 220V±2%, pure sine wave
- Backup time: Built-in six 12V/7AH batteries, backup duration ≥30min
- Overload capability: 125% load for 10min, 150% load for 30s
- Switching time: 0ms (zero transfer online type)
- Efficiency: ≥90%
- Communication interface: RS232, remote monitoring supported
- Operating environment: 0℃~40℃, 20–90%RH non-condensing
6.2.2 Modular UPS (KITOZER-UPS-20KVA)
- Rated capacity: 20KVA/16KW (expandable to 60KVA)
- Input voltage: 380V±20%, 50Hz±3%, three-phase five-wire
- Output voltage: 380V±1%, pure sine wave, three-phase five-wire
- Backup time: External sixteen 12V/100AH batteries, backup duration ≥60min
- Redundancy design: N+1 redundant, single module fault no impact on whole unit
- Full-load efficiency: ≥95%
- Overload capability: 150% load for 60s, 200% load for 10s
- Communication interface: RS485, TCP/IP, parallel connection, remote monitoring & battery management
- Operating environment: -10℃~45℃, 10–90%RH non-condensing
6.2.3 High-frequency Modular UPS (KITOZER-UPS-60KVA)
- Rated capacity: 60KVA/48KW (expandable to 120KVA)
- Input voltage: 380V±30%, 50Hz±2%, three-phase five-wire
- Output voltage: 380V±0.5%, pure sine wave, three-phase five-wire
- Backup time: External thirty-two 12V/200AH batteries, backup duration ≥120min
- Redundancy design: N+2 redundant, dual bus power supply, reliability up to 99.999%
- Efficiency: ≥98% full load, ≥95% under light load
- Overload capability: 200% load for 60s, 300% load for 10s
- Communication interface: TCP/IP, SNMP, Modbus, AI monitoring, remote operation & harmonic governance
- Operating environment: -20℃~50℃, 5–95%RH non-condensing
6.3 Precision Air Conditioner Series
6.3.1 Air-cooled Precision Air Conditioner (KITOZER-AC-5KW)
- Cooling capacity: 5KW (sensible cooling capacity 4.8KW)
- Temp & humidity control range: 18–28℃±1℃, 40–60%RH±5%
- Air supply mode: Top supply, bottom return
- Compressor: Fixed frequency scroll compressor, power 2.2KW
- Fan: Centrifugal fan, power 0.3KW, air volume 1200m³/h
- Refrigerant: Eco-friendly R410A
- Total power consumption: ≤2.5KW, single-phase 220V power supply
- Protection grade: IP20
- Operating environment: 10℃~45℃, 20–80%RH
6.3.2 Row-level Precision Air Conditioner (KITOZER-AC-12KW)
- Cooling capacity: 12KW (sensible cooling capacity 11.5KW)
- Temp & humidity control range: 18–28℃±0.5℃, 40–60%RH±3%
- Air supply mode: Horizontal front-rear supply & return
- Compressor: Variable frequency scroll compressor, power 4KW
- Fan: EC energy-saving silent fan, power 0.8KW, air volume 3000m³/h
- Refrigerant: Eco-friendly R407C
- Total power consumption: ≤5KW, three-phase 380V power supply
- Protection grade: IP30
- Redundancy design: Multi-unit parallel N+1 backup
- Operating environment: -5℃~50℃, 10–90%RH
6.3.3 Row-level Liquid Cooling Air Conditioner (KITOZER-AC-30KW)
- Cooling capacity: 30KW (sensible cooling capacity 29KW)
- Temp & humidity control range: 18–28℃±0.3℃, 40–60%RH±2%
- Heat dissipation mode: Cold plate liquid cooling, direct cabinet heat exchange
- Supply & return water temperature: Inlet 24℃, outlet 32℃, temperature difference 8℃
- Compressor: Variable frequency centrifugal compressor, power 6KW
- Fan: High-efficiency EC fan, power 1.5KW, air volume 7500m³/h
- Refrigerant: Eco-friendly R134a
- Total power consumption: ≤8KW, three-phase 380V power supply
- PUE value: ≤1.15, energy-saving & high efficiency
- AI function: Intelligent cooling adjustment matching cabinet load variation
- Protection grade: IP54
- Operating environment: -10℃~60℃, 5–95%RH
6.4 Environmental Monitoring Series
6.4.1 Entry-level Environmental Monitoring Host (KITOZER-MON-B1)
- Processor: Dual-core 1.5GHz ARM Cortex-A9
- Memory: 2GB DDR3
- Storage: 16GB eMMC
- Operating system: Linux 4.19
- Interfaces: 4×RS485, 2×100M Ethernet, 8×DI, 4×DO, 1×USB2.0
- Access capacity: Up to 20 monitoring points (temperature/humidity, water leakage, UPS, air conditioner, etc.)
- Alarm modes: Acoustic & light alarm, optional SMS alarm
- Data storage: Local historical data storage ≥3 months
- Operating environment: -20℃~60℃, 10–90%RH
6.4.2 High-end Environmental Monitoring Platform (KITOZER-MON-H1)
- Processor: 8-core 3.0GHz Intel Xeon
- Memory: 16GB DDR4
- Storage: 512GB SSD (system) + 4TB HDD (data)
- Operating system: Windows Server 2019 / Linux CentOS 7
- Interfaces: 16×RS485, 8×Gigabit Ethernet, 32×DI, 16×DO, 4×HDMI, 2×USB3.0
- Access capacity: Up to 200 monitoring points, cross-brand equipment compatibility
- Core functions: Real-time monitoring, data collection, AI analysis, linkage control, video integration, alarm management, report generation, remote operation & maintenance
- Communication protocols: Modbus, SNMP, TCP/IP, HTTP
- Operating environment: 0℃~45℃, 20–80%RH
6.4.3 High-precision Temperature & Humidity Sensor (KITOZER-SEN-TH3)
- Measuring range: -40℃~80℃, 0–100%RH
- Measurement accuracy: ±0.1℃, ±1%RH
- Resolution: 0.01℃, 0.1%RH
- Output signal: RS485/Modbus/TCP
- Power supply: DC24V±10%
- Protection grade: IP67
- Response time: ≤10s
- Operating environment: -40℃~80℃, 0–100%RH
6.4.4 Water Leakage Sensor (KITOZER-SEN-WL2)
- Sensing cable length: 10m (expandable to 50m)
- Positioning accuracy: ≤0.5m
- Output signal: RS485
- Power supply: DC24V±10%
- Protection grade: IP67
- Operating temperature: -20℃~60℃
- Alarm mode: Position-specific leakage alarm display
- Material: Corrosion-resistant PVC, anti-aging
6.5 Fire Protection Series
6.5.1 HFC-227ea Fire Suppression Unit (KITOZER-FIRE-G1)
- Fire suppressant: Clean HFC-227ea (zero residue)
- Filling weight: 40kg
- Maximum protected volume: ≤100m³
- Working pressure: 2.5MPa (20℃)
- Startup modes: Auto / manual / emergency manual
- Spraying duration: ≤10s
- Design fire suppression concentration: ≤8%
- Protected objects: Cabinets, servers, precision electronic equipment
- Operating environment: 0℃~50℃, 10–90%RH
6.5.2 IG541 Inert Gas Fire Suppression System (KITOZER-FIRE-G3)
- Fire suppressant: IG541 inert gas (52% nitrogen + 40% argon + 8% CO₂), natural eco-friendly
- Filling pressure: 15MPa (20℃)
- Maximum protected volume: ≤500m³
- Startup modes: Auto / manual / emergency manual
- Spraying duration: ≤60s
- Design fire suppression concentration: ≤37.5%
- Advantages: Zero pollution, no residue, no equipment damage, harmless to human body
- Protected objects: Large data centers, computer rooms, archives
- Operating environment: -10℃~50℃, 5–95%RH
6.5.3 Fire Alarm Controller (KITOZER-FIRE-C1)
- Circuit loops: 2 expandable loops
- Max devices per loop: ≤128 (detectors, modules, etc.)
- Display: Chinese LCD screen
- Alarm modes: Acoustic & light alarm, relay output
- Communication interface: RS485 linkage control support
- Power supply: DC24V±10%, backup battery supports ≥4-hour operation
- Operating environment: -10℃~50℃, 10–90%RH
6.6 Power Distribution Series
6.6.1 Intelligent Remote PDU (KITOZER-PDU-24H)
- Input specification: 63A three-phase 380V
- Output specification: 24 universal sockets (10A/16A auto-adaptive)
- Max rated power: ≤16000W
- Monitored parameters: Voltage, current, power, energy, harmonic, temperature
- Control functions: Remote switch, timing control, overload protection, lightning protection, surge suppression
- Communication protocols: SNMP/Modbus/TCP, data upload & remote operation support
- Protection grade: IP54
- Operating environment: -20℃~60℃, 10–90%RH
6.6.2 Mid-tier Precision Power Distribution Cabinet (KITOZER-PDB-M1)
- Input voltage: 380V±10%, three-phase five-wire
- Output circuits: 24 channels (16×16A, 8×32A)
- Core configuration: Intelligent circuit breakers, Class III lightning arresters, multi-function harmonic energy meters, surge protectors, insulation monitoring devices
- Protection functions: Overvoltage, undervoltage, overload, leakage, short circuit, harmonic monitoring
- Communication interfaces: RS485/TCP/IP, remote monitoring & data upload support
- Protection grade: IP40
- Material: Premium cold-rolled steel with electrostatic plastic spraying
- Operating environment: 0℃~45℃, 20–80%RH
6.6.3 Backup Diesel Generator (KITOZER-GEN-200KW)
- Rated power: 200KW
- Output voltage: 380V three-phase five-wire
- Frequency: 50Hz±0.5%
- Auto startup time: ≤10s
- Fuel: 0# diesel
- Fuel tank capacity: 500L, continuous operation ≥8 hours
- Startup modes: Electric startup, auto/manual switching
- Protection functions: Overvoltage, undervoltage, overload, short circuit, high water temperature, low oil pressure alarm
- Noise level: ≤65dB(A) silent type
- Operating environment: -20℃~45℃, 10–90%RH
7. Application Scope of All Products
7.1 Cabinet Series Application Scope
- Network Cabinet: Small enterprise offices, branch computer rooms, small monitoring rooms, home equipment rooms, for storing switches, routers, firewalls, small servers and other network devices.
- Server Cabinet: Medium enterprise computer rooms, university IT centers, hospital information centers, government department computer rooms, for servers, storage, UPS, precision air conditioners and core IT equipment.
- Micro-module Cabinet: Large enterprise data centers, financial institution computer rooms, internet company IDCs, cloud computing centers, edge computing nodes, for high-density server deployment and cold aisle modular data center construction.
7.2 UPS Series Application Scope
- 3KVA Online UPS: Small computer rooms, office spaces, home equipment rooms, protects computers, printers, routers and small servers against power failure and data loss.
- 20KVA Modular UPS: Medium-sized computer rooms and data centers, provides stable continuous power for servers, storage, precision air conditioners and environmental monitoring equipment, supporting capacity expansion and redundant backup.
- 60KVA High-frequency Modular UPS: Large data centers, cloud computing hubs, financial core computer rooms, delivers ultra-reliable high-efficiency power supply for high-density IT equipment, with dual bus power supply and AI intelligent management.
7.3 Precision Air Conditioner Series Application Scope
- 5KW Air-cooled Precision Air Conditioner: Small computer rooms, monitoring equipment rooms, maintains constant temperature & humidity to stabilize network equipment operation.
- 12KW Row-level Precision Air Conditioner: Medium server computer rooms, horizontal targeted cooling for rack equipment, N+1 redundant backup matching medium-density IT loads.
- 30KW Row-level Liquid Cooling Air Conditioner: Large data centers, high-density server rooms, AI computing hubs, liquid cooling efficiently dissipates high heat loads, reduces overall PUE for energy conservation.
7.4 Environmental Monitoring Series Application Scope
- Entry-level Monitoring Host: Small unattended computer rooms, realizes basic monitoring & alarm of temperature/humidity, water leakage, UPS and air conditioners.
- High-end Monitoring Platform: Medium & large computer rooms, data centers, multi-site centralized management, supports real-time equipment monitoring, data collection, AI analysis, linkage control and remote unattended operation.
- Temperature & Humidity / Water Leakage Sensors: Widely applied in all types of computer rooms, warehouses, archives, museums and laboratories, monitors environmental changes and prevents equipment damage & environmental hazards.
7.5 Fire Protection Series Application Scope
- HFC-227ea Fire Suppression Unit: Small computer rooms, rack rooms, power distribution rooms, archives, museums, protects precision electronics and paper documents with residue-free fire suppression.
- IG541 Inert Gas Fire Suppression System: Large data centers, financial core computer rooms, cloud computing hubs, high-value equipment rooms, safe for manned environments with zero equipment damage.
- Fire Alarm Controller: All types of computer rooms, buildings, factories and warehouses, realizes automatic fire detection, alarm and linkage disposal to protect personnel and equipment safety.
7.6 Power Distribution Series Application Scope
- Intelligent PDU: All computer room cabinets, realizes power distribution, remote control and energy consumption monitoring for servers & network equipment, improving cabinet power intelligence.
- Precision Power Distribution Cabinet: Medium & large data centers, serves as main or sub-distribution power equipment, centralized intelligent power management and multi-layer safety protection for stable power supply.
- Backup Diesel Generator: Large data centers, financial institutions, hospitals, government departments, acts as primary emergency backup power to guarantee uninterrupted core business operation during mains power failure.
8. Core Product Advantages
8.1 Brand Core Advantages
- Strong Customization Capacity: KITOZER provides customized cabinets, UPS, air conditioners, monitoring, fire protection and power distribution equipment matching customer room dimensions, load demands and functional requirements, fully meeting personalized scenarios.
- OEM & ODM Processing Support: Supports white-label OEM/ODM production, customized logo and technical parameters to help clients build independent brands and cut procurement costs.
- Strict Confidentiality Mechanism: Formal non-disclosure agreements cover full-cycle design, production and delivery, protecting customer project plans, technical parameters and order data from leakage.
- Sufficient Spot Inventory: Core products (cabinets, UPS, PDU, sensors) are stocked in large quantities, standard models support same-day order & delivery to shorten project lead time for urgent construction demands.
- Full-series Product Coverage: One-stop supplier for computer room construction, environmental monitoring, fire linkage and intelligent power distribution, reduces multi-supplier coordination and project management costs.
8.2 Cabinet Series Advantages
- High Load-bearing Strength: Thickened cold-rolled steel frames, maximum static load up to 1500kg, resistant to deformation under high-density server deployment.
- Anti-static & Anti-corrosion: Electrostatic plastic spraying surface treatment, anti-aging and moisture-proof, extending service life in dusty & humid computer room environments.
- Modular Integration Design: Micro-module cabinets integrate cold aisle containment, access control, lighting, cooling and smoke detection for plug-and-play fast deployment & flexible expansion.
- Efficient Heat Dissipation: High-speed cooling fans and high-air-permeability mesh doors (air permeability ≥70%) rapidly dissipate equipment heat to guarantee stable operation.
- Easy Installation & Maintenance: Detachable side panels & front/rear doors, adjustable shelves and complete cable management systems simplify equipment installation, wiring and daily maintenance.
8.3 UPS Series Advantages
- Ultra-high Reliability: Online pure sine wave zero switching time, N+1/N+2 redundant design, MTBF ≥50,000 hours to guarantee uninterrupted power supply.
- Energy-saving High Efficiency: High-frequency modular design achieves ≥98% full-load efficiency and ≥95% light-load efficiency, cutting energy consumption for green computer room construction.
- Wide Input Voltage Adaptability: Input voltage fluctuation tolerance ±15%~±30%, adapts to unstable municipal power grids and reduces equipment damage caused by voltage surges.
- Intelligent Centralized Management: Remote monitoring, battery management and harmonic governance, compatible with environmental monitoring platforms for intelligent O&M.
- Extendable Backup Duration: Supports large-capacity external battery packs, maximum backup time up to 120 minutes for long-duration power failure protection.
8.4 Precision Air Conditioner Series Advantages
- Ultra-precise Temperature & Humidity Control: Temperature accuracy ±0.3℃, humidity accuracy ±2%RH, eliminates equipment malfunctions caused by environmental fluctuation.
- High Energy Efficiency: Variable frequency compressors, EC energy-saving fans and liquid cooling technology reduce energy consumption by over 30% vs traditional air conditioners with PUE ≤1.15.
- Redundant Backup Mechanism: Multi-unit parallel N+1 backup design, single unit fault does not interrupt overall cooling to maintain constant room environment.
- Low Noise Operation: Silent EC fan design, operating noise ≤50dB for quiet computer room working conditions.
- Wide Operating Temperature Range: Adaptable to -10℃~60℃ ambient temperature, stable operation across all seasons and geographic regions.
8.5 Environmental Monitoring Series Advantages
- Full-coverage Monitoring: All-dimensional monitoring of temperature/humidity, water leakage, UPS, air conditioners, power distribution cabinets, fire protection, access control and video with zero blind spots.
- High-precision Data Collection: High-sensitivity sensors deliver accurate data (temperature ±0.1℃, water leakage positioning ≤0.5m) to detect hidden risks in advance.
- Automatic Intelligent Linkage: Auto linkage between equipment (temperature rise → increase AC cooling; water leakage → cut power; fire → activate suppression) to reduce manual intervention for abnormal disposal.
- Multi-terminal Remote O&M: PC/mobile/tablet remote monitoring, operation and instant alarm push, enabling 7×24-hour unattended operation and cutting labor costs.
- Traceable Historical Data: Local storage of historical data over 3 months, supports data query, report generation and trend analysis for computer room optimization data support.
8.6 Fire Protection Series Advantages
- Clean & Eco-friendly Fire Suppressants: HFC-227ea and IG541 leave zero residue, no damage to precision electronic equipment, eliminating post-fire cleaning work.
- Ultra-fast Fire Suppression: HFC-227ea sprays within 10s, IG541 within 60s to rapidly contain fire and minimize asset loss.
- Safe & Low False Alarm Rate: IG541 is safe for manned environments; triple auto/manual/emergency startup control greatly reduces false alarm probability.
- Strong Cross-system Linkage: Seamless linkage with environmental monitoring and power distribution systems, automatically cuts non-fire power and shuts down air conditioning during fire events for integrated emergency disposal.
8.7 Power Distribution Series Advantages
- Stable Power Supply: Premium internal components with multi-layer overvoltage/undervoltage/overload/leakage protection to eliminate power supply instability risks.
- Fine-grained Intelligent Energy Monitoring: Real-time voltage/current/power/energy/harmonic parameter collection, data upload to monitoring platform for refined energy management.
- Remote Equipment Control: Intelligent PDU supports remote switch and timing restart, reducing on-site maintenance workload for faulty equipment.
- Multi-layer Safety Protection: Class III lightning protection, surge suppression and insulation monitoring resist lightning strikes and power surges to protect backend IT equipment.
9. Tender Winning Technical Parameters (Marked with *)
9.1 Cabinet Series Tender Parameters
- *Cabinet adopts premium SPCC cold-rolled steel, frame thickness ≥1.5mm, door panel thickness ≥1.2mm; static load capacity ≥800kg (Entry), ≥1200kg (Standard), ≥1500kg (Premium).
- *Protection grade ≥IP20 (Entry/Standard), ≥IP54 (Premium), with dust and splash water resistance capability.
- *Micro-module cabinet adopts cold aisle containment design, integrated intelligent access control, LED lighting, cooling fans and smoke detectors for integrated one-piece deployment.
- *Cabinet surface electrostatic anti-static plastic spraying, anti-corrosion & anti-aging, service life ≥10 years.
9.2 UPS Series Tender Parameters
- *Online pure sine wave output with 0ms switching time; input voltage fluctuation tolerance ≥±15% (Entry), ≥±20% (Standard), ≥±30% (Premium).
- *Modular UPS supports N+1 (Standard) / N+2 (Premium) redundant design; single module fault does not affect overall unit operation, MTBF ≥50,000 hours.
- *High-frequency modular UPS full-load efficiency ≥98%, 20% light-load efficiency ≥95%, built-in harmonic governance with THDi ≤3%.
- *UPS supports remote monitoring and battery management, compatible with environmental monitoring platforms via Modbus and SNMP communication protocols.
9.3 Precision Air Conditioner Series Tender Parameters
- *Temperature control accuracy ≤±1℃ (Entry), ≤±0.5℃ (Standard), ≤±0.3℃ (Premium); humidity control accuracy ≤±5%RH (Entry), ≤±3%RH (Standard), ≤±2%RH (Premium).
- *Row-level & liquid cooling air conditioners adopt variable frequency compressors and EC energy-saving fans, PUE ≤1.2 (Standard), ≤1.15 (Premium), energy consumption reduced by over 30% vs traditional air conditioners.
- *Row-level liquid cooling air conditioner adopts cold plate liquid cooling, supply/return water temperature 24℃/32℃, single cabinet heat dissipation capacity ≥20KW, matching high-density AI computing computer rooms.
- *Precision air conditioners support N+1 redundant backup; automatic switching upon single unit failure to maintain uninterrupted constant temperature environment.
9.4 Environmental Monitoring Series Tender Parameters
- *Monitoring host/platform supports access to ≥20 monitoring points (Entry), ≥50 (Standard), ≥200 (Premium), compatible with Modbus, SNMP and TCP/IP protocols.
- *Temperature & humidity sensor measurement accuracy ≤±0.5℃/±3%RH (Entry), ≤±0.3℃/±2%RH (Standard), ≤±0.1℃/±1%RH (Premium), protection grade ≥IP65.
- *Water leakage sensor positioning accuracy ≤1mm (Entry), ≤0.5m (Standard/Premium); sensing cable length ≥5m (Entry), ≥10m (Standard/Premium), protection grade ≥IP65.
- *Monitoring platform supports AI intelligent analysis, cross-equipment linkage control, video integration, alarm management and report generation, stable 7×24-hour operation.
9.5 Fire Protection Series Tender Parameters
- *Fire suppression units adopt HFC-227ea (Entry/Standard) / IG541 inert gas (Premium) clean residue-free fire suppressant without electronic equipment damage.
- *HFC-227ea spraying time ≤10s, IG541 spraying time ≤60s; design fire suppression concentration ≤8% (HFC-227ea), ≤37.5% (IG541).
- *Fire alarm controller supports ≥2 loops (Entry), ≥4 loops (Standard), ≥8 loops (Premium), maximum 128 connected devices per loop.
- *Fire protection system can link environmental monitoring and power distribution systems, automatically cutting non-fire power and shutting down air conditioning before activating fire suppression during fire events.
9.6 Power Distribution Series Tender Parameters
- *Precision power distribution cabinet input voltage 380V±10%, output circuits ≥12 (Entry), ≥24 (Standard), ≥48 (Premium), equipped with overvoltage, undervoltage, overload and leakage protection functions.
- *Intelligent PDU supports voltage, current, power and energy monitoring, remote switch & timing control, lightning and surge suppression, compatible with SNMP/Modbus communication protocols.
- *Backup diesel generator rated power ≥200KW, auto startup time ≤10s, continuous operation duration ≥8 hours, silent noise ≤65dB(A).
- *Power distribution system equipped with Class III lightning protection, surge suppression and insulation monitoring to resist lightning strikes and power surges and protect backend equipment.
10. Complete Scenario Solutions
10.1 Small Computer Room Integrated Solution (Entry-level Configuration)
10.1.1 Project Overview
Small computer room area ≤50㎡, server cabinets ≤10 units, total IT load ≤5KW, limited budget. Core demands: basic power supply, cooling, monitoring and fire protection to guarantee stable unattended equipment operation.
10.1.2 Solution Design
- Cabinet System: 10 sets KITOZER-NC6042 network cabinets for switches, routers and small servers, basic load-bearing & anti-static design.
- Power Supply & Distribution System: 1 set KITOZER-UPS-3KVA online UPS with 30min backup time; 1 set KITOZER-PDB-B1 basic power distribution cabinet with 12 output circuits; 5 sets KITOZER-PDU-8C basic PDUs for power distribution.
- Cooling System: 1 set KITOZER-AC-5KW air-cooled precision air conditioner with top air supply, maintaining room temperature 22℃±2℃, humidity 50%±5%RH.
- Environmental Monitoring System: 1 set KITOZER-MON-B1 monitoring host, connected with 5 temperature & humidity sensors and 2 water leakage sensor sets for real-time environment monitoring and acoustic-light abnormal alarms.
- Fire Protection System: 4 KITOZER-FIRE-S1 smoke detectors, 1 set KITOZER-FIRE-G1 HFC-227ea cabinet fire suppression unit for automatic fire alarm and suppression.
10.1.3 Solution Advantages
- High cost performance: Entry-level configuration with affordable pricing, fully meeting core operational demands of small computer rooms.
- Fast deployment: Small equipment quantity, installation & commissioning completed within 1–2 days.
- Easy daily O&M: Unattended operation with instant abnormal alarms to cut labor maintenance costs.
- Stable reliable: Full KITOZER branded core equipment with low failure rate and consistent quality.
10.2 Medium Computer Room Integrated Solution (Standard Configuration)
10.2.1 Project Overview
Medium computer room area 50–200㎡, server cabinets 10–50 units, total IT load 5–20KW, medium budget. Core demands: complete environmental monitoring, intelligent power distribution, linked fire protection and redundant cooling, supporting remote management and uninterrupted business operation.
10.2.2 Solution Design
- Cabinet System: 30 sets KITOZER-SC6042 server cabinets with 1200kg load capacity and anti-static design for servers and storage equipment.
- Power Supply & Distribution System: 2 sets KITOZER-UPS-20KVA modular UPS with N+1 redundancy and 60min backup time; 2 sets KITOZER-PDB-M1 precision power distribution cabinets with 24 intelligent monitoring output circuits; 15 sets KITOZER-PDU-16M metering PDUs for energy monitoring and remote control.
- Cooling System: 4 sets KITOZER-AC-12KW row-level variable frequency precision air conditioners with N+1 redundant backup, horizontal targeted cooling, precise temperature control 22℃±0.5℃, humidity 50%±3%RH.
- Environmental Monitoring System: 1 set KITOZER-MON-M1 monitoring host, connected with 15 temperature & humidity sensors, 5 water leakage monitoring systems, 8 HD cameras and 3 access control sets for real-time monitoring, remote management and cross-equipment automatic linkage.
- Fire Protection System: 1 set KITOZER-FIRE-C1 fire alarm controller, full set smoke & heat detectors, 2 sets KITOZER-FIRE-G2 pipe-network HFC-227ea fire suppression systems with automatic linkage fire suppression.
10.2.3 Solution Advantages
- Redundant high reliability: N+1 redundancy for UPS and air conditioning, single point failure no impact on overall operation with reliability up to 99.99%.
- Intelligent visualized management: Remote monitoring platform with data traceability and automatic linkage, boosting O&M efficiency by 50%.
- Precise constant temperature & humidity environment: Row-level targeted cooling matches server operating requirements and extends IT equipment service life.
- Multi-layer safety guarantee: Intelligent linked fire protection system and multi-protection power distribution eliminate computer room safety risks.
10.3 Large Data Center Integrated Solution (High-end Premium Configuration)
10.3.1 Project Overview
Large data center area ≥200㎡, server cabinets ≥50 units, total IT load ≥20KW, sufficient budget. Core demands: high-density deployment, AI intelligent O&M, liquid cooling heat dissipation, dual-bus redundant power supply, energy-saving design, 7×24-hour unattended operation for zero core business interruption.
10.3.2 Solution Design
- Cabinet System: 80 sets KITOZER-MC6042 micro-module cold aisle cabinets, integrated access control, lighting, cooling and smoke detection for high-density server deployment.
- Power Supply & Distribution System: 4 sets KITOZER-UPS-60KVA high-frequency modular UPS with N+2 redundancy and dual bus power supply, 120min backup time; 4 sets KITOZER-PDB-H1 intelligent harmonic governance power distribution cabinets with 48 output circuits; 40 sets KITOZER-PDU-24H intelligent remote PDUs for energy monitoring and remote O&M; 1 set KITOZER-GEN-200KW silent diesel generator as primary emergency backup power.
- Cooling System: 12 sets KITOZER-AC-30KW row-level liquid cooling air conditioners with AI intelligent load adjustment, overall PUE ≤1.15 for high-efficiency cooling of high-density computing equipment.
- Environmental Monitoring System: 1 complete KITOZER-MON-H1 distributed environmental monitoring platform, connected with 40 high-precision temperature & humidity sensors, 6 fiber optic temperature measurement systems, 20 AI intelligent cameras and 8 biometric access control sets, supporting AI risk analysis and multi-site centralized unattended management.
- Fire Protection System: 2 sets KITOZER-FIRE-H1 intelligent IoT fire alarm systems, 4 sets KITOZER-FIRE-G3 IG541 eco-friendly inert gas fire suppression systems, safe for manned core data center environments with zero equipment corrosion.
- Integrated O&M Platform: KITOZER-OPS-H1 full-lifecycle operation & maintenance platform with equipment asset management, alarm processing, work order dispatching, data analytics and remote operation, supporting multi-terminal access and cross-data center unified management.
10.3.3 Solution Advantages
- Ultra-high redundant reliability: N+2 UPS redundancy, N+1 air conditioning backup, dual bus power supply and emergency diesel generator, reliability up to 99.999% to guarantee zero interruption of financial, government and cloud core businesses.
- Low-carbon energy-saving design: Liquid cooling, high-frequency UPS and AI load adjustment reduce overall energy consumption by over 40% vs traditional data centers with PUE as low as 1.12, complying with national green data center standards.
- AI unmanned intelligent O&M: Automatic risk identification, remote fault disposal and data trend analysis cut manual O&M workload by 80% and reduce labor costs.
- High-density deployment capability: Cold aisle micro-module design supports single cabinet power density up to 30KW, perfectly matching AI computing, big data storage and high-load cloud server deployment demands.
11. Real Project Application Cases
11.1 Small Enterprise Small Computer Room Case
- Client: Guangzhou XX Trading Co., Ltd.
- Project Scale: 30㎡ computer room, 8 server cabinets, total IT load 3KW
- Configuration Scheme: KITOZER Entry-level full set (8 network cabinets, 3KVA UPS, 5KW precision air conditioner, basic environmental monitoring, HFC-227ea fire suppression unit)
- Project Outcome: Completed deployment within 2 days, stable 2-year failure-free operation. Maintains constant environment 22℃±2℃, 50%±5%RH with instant abnormal monitoring alarms, fully supporting corporate business system stable operation with low cost and easy daily maintenance.
11.2 Educational Institution Medium Computer Room Case
- Client: XX University Information Center
- Project Scale: 150㎡ computer room, 35 server cabinets, total IT load 15KW
- Configuration Scheme: KITOZER Standard full set (35 server cabinets, 2×20KVA modular UPS, 4×12KW row-level air conditioners, mid-tier environmental monitoring platform, pipe-network HFC-227ea fire suppression system)
- Project Outcome: N+1 redundant UPS and air conditioning deliver 5-year stable operation without major faults. Remote O&M platform improves maintenance efficiency by 50%, precise constant temperature & humidity extends server service life, supporting uninterrupted teaching, research and campus management systems 24/7.
11.3 Financial Institution Large Data Center Case
- Client: XX Bank Core Data Center
- Project Scale: 800㎡ data center, 120 micro-module cabinets, total IT load 80KW
- Configuration Scheme: KITOZER High-end Premium full set (120 cold aisle micro-module cabinets, 4×60KVA high-frequency UPS, 12×30KW liquid cooling air conditioners, AI environmental monitoring platform, IG541 inert gas fire suppression, 200KW diesel generator)
- Project Outcome: Actual operating PUE 1.12, energy consumption reduced by 45% vs traditional data centers, AI 24-hour unattended O&M, 3-year zero major fault stable operation. Fully supports bank core transaction, data storage and customer service systems, successfully passed National Class III Cybersecurity Level Protection Certification.
11.4 Government Service Computer Room Case
- Client: XX Municipal Government Service Center IT Room
- Project Scale: 120㎡ computer room, 25 server cabinets, total IT load 10KW
- Configuration Scheme: KITOZER Standard full set (25 server cabinets, 2×20KVA modular UPS, 3×12KW row-level air conditioners, intelligent environmental monitoring & linked fire protection system)
- Project Outcome: 4-year stable continuous operation, precise environment monitoring and reliable fire linkage, guarantees uninterrupted operation of government service platforms, approval systems and cross-department data sharing platforms, improving municipal service efficiency.
11.5 Intelligent Manufacturing Edge Computer Room Case
- Client: XX Intelligent Manufacturing Factory Edge Computing Room
- Project Scale: 60㎡ edge computer room, 15 server cabinets, total IT load 8KW
- Configuration Scheme: KITOZER Standard full set (15 server cabinets, 1×20KVA modular UPS, 2×12KW row-level air conditioners, environmental monitoring system, HFC-227ea fire suppression unit)
- Project Outcome: Industrial anti-dust, moisture-proof and anti-interference design adapts harsh factory environments, 3-year stable operation supporting industrial IoT, production monitoring and real-time data collection systems, accelerating factory intelligent upgrading.
12. Product Common Faults & Maintenance Guide
12.1 Cabinet Series Faults & Maintenance
12.1.1 Common Faults
- Deformed/loose cabinet doors: Long-term stress or aging hinges damage sealing and heat dissipation performance.
- Bent/fallen shelves: Overload or loose fixing screws risk equipment damage.
- Non-rotating cooling fans: Power failure, motor burnout or dust blockage leads to poor heat dissipation and overheating.
- Failed anti-static protection: Poor earthing or worn anti-static coating causes static electricity damage to IT hardware.
12.1.2 Maintenance Schedule
- Daily Maintenance: Weekly surface & mesh door dust cleaning, check door hinges and locks, tighten loose fixing screws.
- Periodic Maintenance: Monthly fan operation inspection and dust cleaning, earthing resistance test (≤4Ω); Quarterly shelf load inspection to avoid overload; Annual anti-static coating re-spray, replace aging hinges and locks.
- Fault Disposal: Correct or replace deformed doors; replace bent shelves and reduce load weight; troubleshoot power supply or replace failed fans; repair earthing wiring for static protection failure.
12.2 UPS Series Faults & Maintenance
12.2.1 Common Faults
- No power switching during mains failure: Damaged batteries, inverter breakdown or transfer switch failure cause equipment power loss.
- Abnormal output voltage: Voltage regulator fault, overload or harmonic interference damages backend IT equipment.
- Swollen/leaking batteries: Overcharging, over-discharging or aging creates severe safety hazards.
- Excessive fan noise / non-rotating fans: Dust clogging or motor aging leads to UPS overheating protection activation.
12.2.2 Maintenance Schedule
- Daily Maintenance: Daily UPS operating status inspection (input/output voltage, load rate, battery status, alarm records); Weekly surface dust cleaning and fan operation check.
- Periodic Maintenance: Monthly single battery voltage testing (normal 12.5–13.5V for 12V batteries); Quarterly full discharge test to cut off voltage; Quarterly terminal tightening and earthing inspection; Annual aging battery replacement, internal dust cleaning and inverter performance testing.
- Fault Disposal: Inspect batteries, inverter and transfer switch for failed power switching, replace damaged components; Reduce load, eliminate harmonic interference and repair voltage regulator for abnormal output voltage; Immediately replace swollen/leaking batteries and optimize charge-discharge logic; Clean fan dust or replace faulty fans for abnormal noise.
12.3 Precision Air Conditioner Series Faults & Maintenance
12.3.1 Common Faults
- Insufficient cooling power: Clogged filters, refrigerant leakage, compressor failure or low fan speed leads to over-temperature & humidity.
- Water leakage: Blocked drain pipes, cracked condensate trays or uneven installation risk water damage to server equipment.
- Non-starting compressor: Power failure, faulty thermostat, overload protection or insufficient refrigerant disables cooling function.
- Excessive operating noise: Unbalanced fan blades, compressor failure or loose mounting brackets.
12.3.2 Maintenance Schedule
- Daily Maintenance: Daily temperature, humidity, pressure and current operating status inspection, alarm log review; Weekly filter & air outlet dust cleaning, drain pipe unblocking inspection.
- Periodic Maintenance: Monthly refrigerant pressure inspection and leakage refilling; Quarterly fan tightening and blade cleaning; Annual compressor performance test, aging seal replacement, condenser & evaporator deep cleaning, circuit terminal inspection.
- Fault Disposal: Clean filters, refill refrigerant or repair compressor/fan for insufficient cooling; Unblock drain pipes, repair condensate trays and re-level installation for water leakage; Troubleshoot power, thermostat and overload protection, supplement refrigerant for non-starting compressors; Balance fan blades, repair compressors and fasten mounting parts for abnormal noise.
12.4 Environmental Monitoring Series Faults & Maintenance
12.4.1 Common Faults
- Abnormal sensor data: Damaged sensors, wiring faults or electromagnetic interference produce inaccurate monitoring values.
- Offline monitoring host: Network breakdown, power failure or system crash disables real-time monitoring.
- No alarm trigger: Incorrect alarm threshold settings, module breakdown or broken wiring fail to alert abnormal conditions.
- No camera video output: Power failure, damaged network cables or broken camera hardware.
12.4.2 Maintenance Schedule
- Daily Maintenance: Daily platform data & alarm log review, sensor/camera online status check; Weekly sensor probe & camera lens dust cleaning, wiring tightness inspection.
- Periodic Maintenance: Monthly temperature/humidity/water leakage sensor calibration and alarm function test; Quarterly switch port inspection, host restart and system data backup; Annual aging sensor/camera replacement, wire insulation layer inspection and damaged cable replacement.
- Fault Disposal: Calibrate or replace faulty sensors, eliminate wiring interference for abnormal data; Troubleshoot network/power supply, restart or reinstall system for offline host; Correct alarm settings, replace modules and repair wiring for missing alarms; Inspect power & network cables, replace broken cameras for blank video.
12.5 Fire Protection Series Faults & Maintenance
12.5.1 Common Faults
- False / missing detector alarms: Dust contamination, sensitivity drift or wiring faults cause inaccurate alarm signals.
- Non-activated fire suppression devices: Low starter cylinder pressure, broken solenoid valves or disconnected wiring fail to release fire suppressant during fire events.
- Fire alarm controller breakdown: Power failure, damaged mainboard or faulty circuit loops disable alarm function.
- Fire suppressant leakage: Poor cylinder sealing or cracked pipelines reduce fire suppression effectiveness.
12.5.2 Maintenance Schedule
- Daily Maintenance: Daily controller status & pressure gauge inspection, detector and suppression unit abnormal status check; Weekly detector dust cleaning, cylinder pressure reading verification.
- Periodic Maintenance: Monthly detector sensitivity testing and wiring connection inspection; Quarterly starter cylinder pressure refilling and solenoid valve action test; Annual detector & solenoid valve replacement, cylinder & pipeline sealing inspection, leaked suppressant refilling, full-system linkage test.
- Fault Disposal: Clean detector probes, calibrate sensitivity and repair wiring for false/missing alarms; Refill cylinder pressure, replace solenoid valves and repair wiring for non-activated suppression units; Troubleshoot power supply, replace mainboard and repair circuit loops for controller breakdown; Repair sealing/pipeline cracks and refill suppressant for leakage faults.
12.6 Power Distribution Series Faults & Maintenance
12.6.1 Common Faults
- Distribution cabinet tripping: Overload, short circuit, leakage or damaged lightning arresters cut power supply unexpectedly.
- Failed remote control of intelligent PDU: Network breakdown, module damage or incorrect parameter settings disable remote switch function.
- Inaccurate energy meter data: Broken current transformers, wiring errors or damaged meter hardware distort energy consumption statistics.
- Failed lightning arrester: Lightning strike damage or aging eliminates surge protection capability.
12.6.2 Maintenance Schedule
- Daily Maintenance: Daily cabinet & PDU voltage/current/power status inspection, abnormal odor and alarm review; Weekly internal dust cleaning and terminal tightness inspection.
- Periodic Maintenance: Monthly leakage & overload protection function test, lightning arrester status inspection; Quarterly energy meter calibration, terminal tightening and earthing resistance test; Annual aging lightning arrester & PDU module replacement, internal cabinet deep cleaning and circuit breaker performance testing.
- Fault Disposal: Troubleshoot overload/short circuit/leakage causes, replace damaged lightning arresters for tripping faults; Inspect network, replace modules and correct parameter settings for PDU remote control failure; Replace current transformers, repair wiring or swap damaged meters for inaccurate energy data; Immediately replace failed lightning arresters to prevent lightning strike equipment damage.
13. Factory Strength & After-sales Service System
13.1 Factory Production Strength
KITOZER owns a 20,000㎡ modern manufacturing base in Guangzhou, integrating independent R&D, production, sales and after-sales service for full-range computer room equipment with comprehensive industrial advantages:
- R&D Team: Over 50 professional engineers covering structural design, electrical engineering, software programming and intelligent system development. Annual R&D investment accounts for 15% of total revenue, with over 30 authorized patents covering cabinet structure, UPS power technology, environmental monitoring algorithms and fire linkage control to drive industry technological innovation.
- Production Capacity: Imported German CNC punching machines, laser cutting equipment, automatic electrostatic spraying lines and SMT chip mounting machines enable full automated production. Annual output capacity reaches 100,000 cabinets, 50,000 UPS units, 20,000 precision air conditioners and 100,000 monitoring sets, supporting large-volume mass orders and customized tailor-made projects.
- Strict Quality Control: Fully compliant with ISO9001 Quality Management System, ISO14001 Environmental Management System and ISO45001 Occupational Health & Safety Management System. Full-process quality inspection covers raw material procurement, production processing and finished product testing. All finished goods undergo 100% power-on test, aging test and full performance verification, with core certifications including CCC, CE, ISO and TUV to guarantee stable product quality.
- Stable Supply Chain: Long-term strategic cooperation with global top component suppliers including Schneider, Siemens, Infineon and Panasonic, ensuring stable raw material supply, lower procurement costs and improved overall product cost performance.
13.2 Full-lifecycle After-sales Service
Adhering to the service philosophy “Customer First, Service Priority”, KITOZER establishes a unified nationwide after-sales network to deliver comprehensive full-cycle support for all projects:
- Warranty Commitment: All products enjoy 3-year free warranty (5-year warranty for cabinets). Free repair and spare parts replacement for non