KITOZER Battery FAQ: Internal Resistance Test Cycle And Method

Internal resistance (IR) trending is the fastest way to catch weak VRLA cells before they fail. KITOZER maintenance schedules quarterly IR measurements using a 4-wire battery impedance tester. Compare each cell reading against the factory baseline. A rise above 20 percent over baseline, or 10 percent spread within a string, triggers closer inspection. IR alone cannot prove capacity, so pair it with a yearly load test at 100 percent nameplate AH for 30 minutes. Record results in a spreadsheet per cabinet.

Table of Contents

Measurement Tips

Keep UPS on float charge during reading, clean terminal posts, and hold probes at the same points each time. IR is temperature-sensitive, so note ambient on the log sheet. KITOZER cabinets include numbered cell labels.

Price

From $480/year preventive maintenance visit. Contact +86 13922289957 for battery test schedule.