KITOZER Precision AC FAQ: Water Leak Alarm Response

Water leak alarm from the condensate drain pan of a KITOZER precision air handler must be treated as immediate. Shut down the indoor fan, isolate the chilled water coil valve if present, and visually trace the drain line. Common causes are clogged condensate trap, missing slope on drain pipe, cracked pan, or blocked UV-dye drain tubing. KITOZER units include a dual-point conductivity sensor in the pan and a 5mm leak detection loop around the base perimeter.

Table of Contents

Recovery Steps

Clear the trap with mild vacuum, verify pan slope toward drain, and run the unit in cooling for 30 minutes to confirm drain flow. Inspect floor and ceiling below for secondary water damage before restoring load.

Price

From $120 for replacement leak sensor cable. Contact +86 13922289957 for leak detection kits.